54
GMC-I Messtechnik GmbH
5.9.2
Master-Slave Parallel Connection
Functions
As opposed to direct parallel connection, master-slave parallel
connection offers significant
advantages
:
Equally suitable for
voltage
and
current regulation
Output parameters
(output voltage, cumulative current limiting,
output on/off) are set
entirely
by the
master device
.
All
interconnected KONSTANTERs are
equally loaded
.
Connection
Define
one power supply as a
master device
.
Connect
master
and
slave
devices as shown in Figure 5.9.2.
Connect the
output leads
(
refer to
Balance
the individual
output current values
. Keep connector
cable as
short
as possible, and use the
largest
possible
conductor cross-section. Perform balancing with R
R
sym
.
Figure 5.9.2 Wiring for Master-Slave Parallel Connection
Settings
Initial power-up:
Short circuit the load.
Switch the
master
on (mains) and
configure
settings:
SIG1 out
Pon rcl
OUTPUT
off
USET =
Uset
Desired output voltage
ISET
=
Isoll / n
Iset: Desired cumulative current
n: Number of devices
Only valid if
nominal data
are
identical
for all devices, see notes.
Switch
slave 1
on (mains) and
configure
:
trG out
SIG1 out
Pon rcl
USET > USET
master
The voltage setpoint at the slave devices
must be set at least 1% higher than at the
master device, e.g. to maximum.
ISET
= 0 A
The ISET rotary knob can be deactivated if
desired by setting ILIM to 0 A.
Use the same procedure for additional slave devices.
Press the
OUTPUT ON
key at the master.
All slave
outputs are
switched on simultaneously
and configured.
Check output current at the slave device displays.
Output current at each of the slaves
can be precisely
matched
to
master output current by adjusting
R
sym
. Changes appear
immediately at the respective display.
Undo short-circuiting of the load.
From this point on,
setting
and
regulation
of (cumulative) output
parameters are controlled
entirely
by the
master
device.
Power-up after initial settings:
Devices can be switched on and off in
any desired order
.
Functional Principle
The master controls output current of the downstream device
(slave 1) via the slave’s
current control input
with the help of the
current monitoring signal
.
Slave 1 functions
as a
master
device for the next downstream
slave (
slave 2
), and so forth.
Cumulative output current is thus always proportional to
master output current.
The master controls the
output on / off status
of the slave
devices via the
connection
from the
master SIG1
output (
SIG1 out
setting
) to the
Slave TRG
input (
trG out
setting
).
Notes:
KONSTANTERs with Differing Nominal Values
The KONSTANTER with the
smallest nominal voltage
value must
always be used as the
master
device.
The
voltage setting range
of the other KONSTANTERs must be
limited
to this lowest value with the
ULIM
parameter.
Slave output current
Iout
corresponds to master output current
Iout
as a percentage only, relative to I
nom
.
Example:
General
A
wire connection
can be used instead of
R
sym
if
no precise
setpoint value
is required for cumulative output current. In this
case, each
slave
device supplies slightly
more current
than the
master device.
If analog interface connector cables and the sensing leads are
longer than 1 meter
,
shielded
cable should be used.
The
shield
is connected to the
ground terminal on the housing
or
to
OUT
.
The master device’s measuring function acquires
commonly
generated
output voltage
for all interconnected KONSTANTERs,
but
only
acquires its
own output current
.
The individual measured current values for each of the
interconnected KONSTANTERs must be
added
together in
order to arrive at
cumulative output current
.
+ SENSE
OUT
OUT
SENSE
Analog Interface
SIG1 OUT
SIG2 OUT
TRG IN
TRG IN
+15 V
AGND
Uset
Uset +
Iset +
U-MON
I-MON
+ OUT
+ OUT
Master
Settings
USET = Uset
ISET = Iset / n
OUTPUT on/off
+ SENSE
OUT
OUT
SENSE
Analog Interface
SIG1 OUT
SIG2 OUT
TRG IN
TRG IN
+15 V
AGND
Uset
Uset +
Iset +
U-MON
I-MON
+ OUT
+ OUT
Slave 1
Settings
USET > Uset
master
ISET = 0 A
OUTPUT on
+ SENSE
OUT
OUT
SENSE
Analog Interface
SIG1 OUT
SIG2 OUT
TRG IN
TRG IN
+15 V
AGND
Uset
Uset +
Iset +
U-MON
I-MON
+ OUT
+ OUT
Load
= only required for sensing mode operation
1 k
Slave 2
Settings
USET > Uset
master
ISET = 0 A
OUTPUT on
1 k
Output
Output
Output
R
sym
R
sym
trG out
SIG1 out
trG out
SIG1 out
SSP KONSTANTER
SSP KONSTANTER
SSP KONSTANTER
Master
:
SSP 120-20
U
nom
20 V
I
nom
10 A
Settings:
USET
: 12 V
ISET
:
3 A (30%)
Slave 1
: SSP 120-20
U
nom
20 V
I
nom
10 A
Results in
Uout
:
12 V
Iout
:
3 A (30%)
Slave 2
: SSP 120-40
U
nom
40 V
I
nom
6 A
Results in
Uout
:
12 V
Iout
: 1.8 A (30%)
Summary of Contents for SSP 120 Series
Page 2: ...2 GMC I Messtechnik GmbH ...