Measurement Types
You can choose one of two different types of measurement:
•
Measuring sequence with automatic polarity reversal (reversal
of current flow direction)
•
Manual measurement with specified current flow direction
8.1
Measurement with Automatic Polarity Reversal – AUTO Function
Automatic polarity reversal is selected as a default value.
MAN
does
not
appear at the display.
Ð
Start measurement in both current flow directions by briefly
pressing the
START
key for one-time polarity reversal or start
continuous measurement for permanent polarity reversal by
briefly pressing the
CONTIN
. key.
After the measuring sequence has been started, the instrument performs
measurement with automatic polarity reversal, first with current flow in
one direction (
Ω→
), and then in the other (
←Ω
).
DATA
blinks at the display
until the measured value has settled in. The larger (worst) measured value
is displayed.
←Ω→
appears at the display.
Difference > 10%
If, during measurement with automatic polarity reversal, the difference
between
Ω→
and
←Ω
is greater than 10%, the resistance values for
both polarities (current flow directions) are displayed separately (sepa-
rated by an underscore).
Δ
Rlo>10% appears at the display.
Limit Value Indication
If the measured value is less than or equal to 2
Ω
, the
Limit
LED
lights up green. If the measured value is greater than 2
Ω
, the LED
lights up red. As a prerequisite, the
LiLED
parameter must be set
to “on” (see page 13).
Resistances which do not demonstrate a stable value until after a
“settling in period” should not be measured with automatic polar-
ity reversal. Measurement with automatic polarity reversal may
lead to varying and/or inflated measurement values, and thus to
an ambiguous reading.
Ω→
←Ω
Δ
Rlo>10%:
←Ω
&
Ω
→
AUTO:
Ω→
DATA
00
.
1
DATA
00
.
7
Rlo
07
.
_
0
.
1
Δ
Rlo>10%
Ω→
Rlo
←Ω
DATA
Limit
< Limit R
LO
= OK
3
←Ω
Δ
Rlo
≤
10% ?
←Ω→
Δ
Rlo > 10% ?
←
Ω
&
Ω
→
www.
GlobalTestSupply
.com
Find Quality Products Online at: