OM-05815
ULTRA V SERIES
PAGE B - 6
INSTALLATION
Air Release Valve Installation
The Automatic Air Release Valve must be inde
pendently mounted in a horizontal position be
tween the pump discharge port
and the inlet side of
the discharge check valve (see Figure 2). The inlet
opening in the Air Release Valve is equipped with
standard 1‐inch NPT pipe threads.
DISCHARGE PIPE
DISCHARGE
CHECK VALVE
PUMP DISCHARGE
SELF‐PRIMING
CENTRIFUGAL
PUMP
SUCTION
LINE
SUPPORT
BRACKET
CLEAN‐OUT
COVER
INSTALL AIR RELEASE VALVE
IN HORIZONTAL POSITION
90
_
LONG
RADIUS
ELBOW
WET WELL
OR SUMP
BLEED LINE 1”
(25,4 MM) DIA. MIN.
(CUSTOMER FUR
NISHED) DO NOT EX
TEND BELOW PUMP
OFF LIQUID LEVEL
Figure 2. Typical Automatic Air Release Valve Installation
Connect the valve outlet to a bleed line which
slopes back to the wet well or sump. The bleed line
must be the same size as the outlet opening or
larger, depending on which Air Release Valve is be
ing used. If
piping
is used for the bleed line, avoid
the use of elbows whenever possible.
NOTE
For multiple pump installations, it is recommended
that each Air Release Valve be fitted with an inde
pendent bleeder line directed back to the wet well.
If multiple Air Release Valves are installed in a sys
tem,
do not
direct bleeder lines to a common mani
fold pipe. Contact your Gorman‐Rupp distributor or
the Gorman‐Rupp Company for information about
installation of an Automatic Air Release Valve for
your specific application.
ALIGNMENT
The alignment of the pump and its power source is
critical for trouble‐free mechanical operation. In
either a flexible coupling or belt‐driven system, the
driver and pump must be mounted so that their
shafts are aligned with and parallel to each other. It
is imperative that alignment be checked after the
pump and piping are installed, and before opera
tion.
NOTE
Check
Rotation
, Section C, before final alignment
of the pump.