18
be stopped by tightening it further; on the contrary, the tightening can only damage the tap.
The closed-circuit pressure system requires the use of pressure mixer taps. For safety
reasons the supply pipe must be itted with a return safety valve or alternatively, a valve of
the safety class that prevents the pressure in the tank from exceeding the nominal pressure
by more than 0.1 MPa. The outlet opening on the relief valve must be equipped with an outlet
for atmospheric pressure.
The heating of water in the heater causes the pressure in the tank to increase to the level set
by the safety valve. As the water cannot return to the water supply system, this can result in
the dripping from the outlet of the safety valve. The drip can be piped to the drain by installing
a catching unit just below the safety valve. The drain installed below the safety valve outlet
must be piped down vertically and located in the environment that is free from the onset of
freezing conditions.
In case the existing plumbing does not enable you to pipe the dripping water from the return
safety valve into the drain, you can avoid the dripping by installing a 3-litre expansion tank
on the inlet water pipe of the boiler.
In order to provide correct operation of the relief valve, periodical inspections of the relief
valve must be carried out by the user. To check the valve, you should open the outlet of the
return safety valve by turning the handle or unscrewing the nut of the valve (depending on
the type of the valve). The valve is operating properly if the water comes out of the nozzle
when the outlet is open.
How to connect to water heater water systems
Legend:
1 - Safety valve
2 - Test valve
3 - Non-return valve
4 - Pressure reduction valve
5 - Closing valve
H - Cold water
T - Hot water
Between the water heater and return safety valve no closing valve may be built-in
because with it the function of return safety valve would be impeded.
The water heater may be connected to the water network in the house without reduction
valve if the pressure in the network is lower than 0.5 MPa (5 bar). If the pressure exceeds
0.5 MPa (5 bar), a reduction valve must be installed. Prior to the electric connection the
water heater must obligatorily be illed with water. By irst illing the tap for the hot water upon
the mixing tap must be opened. When the heater is illed with water, the water starts to run
through the outlet pipe of the mixing tap.
CONNECTION OF THE WATER HEATER TO THE ELECTRIC NETWORK
Before connecting to power supply network, install a power supply cord in the water heater,
with a min. diameter of 1,5 mm
2
(H05VV-F 3G 1,5 mm
2
). For it the protection plate must be
EN
Summary of Contents for GBU 100 EDD/V6
Page 1: ...GBU 50 200 EDD V6 ...
Page 2: ...2 ...
Page 3: ...3 Instructions for Use 16 10 4 ...
Page 6: ...6 0 8 1 2 3 4 5 H T 1 5 2 1 2 3 1000 4 L N N H L MG GND UA ...
Page 7: ...7 35ºC 75ºC 1 C 1 C 2 7ºC 55ºC 35ºC 75ºC 1ºC 7ºC 55 C 55ºC UA ...
Page 8: ...8 35ºC 1ºC 3 Mg LED 0ºC o 75ºC 0ºC 75ºC E1 UA ...
Page 9: ...9 E2 E3 E4 E5 100ºC 7 C UA ...
Page 12: ...12 B 0 1 c B c 3 1 2 3 4 5 K 1 5 2 H05VV F 3G1 5 2 RUS ...
Page 13: ...13 1 2 1000 4 L N 35 C 75ºC 2s 7º N H L MG GND RUS ...
Page 14: ...14 55ºC 35 C 75ºC 1ºC 7ºC 55ºC 35ºC 1ºC Mg RUS ...
Page 15: ...15 0ºC 75ºC 0ºC 75ºC E1 E2 E3 E4 E5 100ºC ry c o ry a RUS ...
Page 22: ...22 ...
Page 23: ...23 ...
Page 24: ...03 2010 276014 ...