3
EN
LED Indicators
Indicator
Color
Explanation
Green ON
The charger is standby.
Flash in Green The system of the charger is upgrading.
Blue ON
The charger is in charging.
Red ON
A fault has occurred.
Cable Requirements
Cable
Type
Cable Specification
AC Cable
Three core outdoor AC
cable
GW7K-HCA
•
Copper, -30℃ ~ +50℃, 450/750V
•
Outer diameter: 11~17mm
• Conductor cross-sectional area: 6mm
2
Five core outdoor AC cable
GW11K-HCA
•
Copper, -30℃ ~ +50℃, 450/750V
•
Outer diameter: 11~17mm
• Conductor cross-sectional area: 2.5mm
2
GW22K-HCA
•
Copper, -30℃ ~ +50℃, 450/750V
•
Outer diameter: 11~17mm
• Conductor cross-sectional area: 6mm
2
RCD Requirements
Charger
Model
RCD Type
RCD
Instantaneous
Tripping
Characteristic
RCD
Tripping Current
RCD
Norminal
Current
RCD
Norminal
Voltage
GW7K-HCA
TYPE A
C
30mA
40A
AC 230V
(2P)
GW11K-
HCA
25A
AC 400V
(4P)
GW22K-
HCA
40A
AC 400V
(4P)