Page 36
Heat Pump Settings
Aux Heat Lockout Temp
(65 )
HP Lockout Outdoor Temp
(65 )
Heat Pump will not run below this temp. (20 - 75 deg. F)
Aux Heat will not run above this temp. (20 - 75 deg. F)
GAS/EL or HP
dip
switch must be set for
HP
and
GAS or ELEC
dip switch must be set for
ELEC
.
Settings
The Main Menu Buttons
Aux Heat Lockout - DISABLED
Aux Heat Lockout - ENABLED
Turns on Aux Heat Lockout.
Dual Fuel Settings
Dual Fuel - ON/OFF
Changeover With Outdoor - ON/OFF
Adjust Balance Point
Uses outdoor sensor for changeover.
Choose the temperature for changeover to fossil fuel. (5 - 60 deg. F)
This feature is for heat pump applications only.
This will only appear if the
GAS/EL or HP
is set for
HP
and the
GAS
or ELEC
is set for
Gas
.
dip switch
dip switch
When Dual Fuel is ON,
an outdoor temperature or a demand for third stage
heat will be used to stop running the heat pump and switch to a fossil fuel
source of heat.
NOTE:
Once the change to fossil fuel is made, the heat
demand
must finish with fossil fuel. Additional heat demands within 10 minutes
will also use fossil fuel, regardless of outdoor temperature or stage demand.
Installation Settings
(Continued)
Heat Pump Lockout - DISABLED
Heat Pump Lockout - ENABLED
Turns on Heat Pump Lockout.
(Only available
when dip switch
is set for Heat
Pump operation.)