SSZ160241A* / CA*F3636*6A* + TXV / MBE1600**-1
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
30.2
28.6
26.9
25.1
24.0
23.3
21.6
19.9
18.7
17.3
15.9
15.0
14.4
13.0
11.5
10.0
8.6
7.0
∆T
31.9
30.2
28.4
26.6
25.4
24.6
22.9
21.1
19.8
18.3
16.8
15.9
15.3
13.7
12.2
10.6
9.0
7.4
kW
1.79
1.75
1.72
1.68
1.7
1.65
1.62
1.58
1.68
1.64
1.60
1.58
1.56
1.52
1.48
1.45
1.41 1.37
Amps
8.4
7.8
7.3
6.9
6.7
6.6
6.2
5.9
5.7
5.4
5.2
5.1
5.0
4.7
4.4
4.2
3.9
3.5
COP
4.93
4.76
4.57
4.37
4.22
4.13
3.91
3.69
3.26
3.08
2.91
2.79
2.71
2.49
2.27
2.03
1.78 1.50
EER
16.9
16.3
15.6
14.9
14.4
14.1
13.4
12.6
11.2
10.5
9.9
9.5
9.3
8.5
7.7
6.9
6.1
5.1
Hi PR
349
334
322
307
300
295
283
272
260
249
239
233
229
220
212
203
196
189
Lo PR 144
133
125
115
108
104
96
85
77
69
60
56
54
46
40
33
29
23
SSZ160361A* / CA*F4860*6A*+TXV/ MBE2000**-1
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
43.2
40.9
38.5
36.0
34.4
33.3
31.0
28.6
26.2
24.2
22.2
21.0
20.2
18.1
16.1
14.0
12.0
9.8
∆T
33.4
31.6
29.7
27.8
26.5
25.7
23.9
22.0
20.2
18.6
17.2
16.2
15.6
14.0
12.4
10.8
9.2
7.6
kW
2.70
2.65
2.59
2.54
2.5
2.48
2.43
2.37
2.46
2.40
2.34
2.31
2.28
2.22
2.16
2.11
2.05 1.99
Amps 13.1
12.1
11.3
10.6
10.3
10.1
9.5
9.0
8.6
8.2
7.9
7.7
7.6
7.2
6.7
6.3
5.8
5.3
COP
4.68
4.52
4.35
4.15
4.02
3.93
3.73
3.52
3.12
2.95
2.78
2.67
2.59
2.39
2.17
1.95
1.71 1.44
EER
16.0
15.5
14.9
14.2
13.7
13.4
12.7
12.0
10.6
10.1
9.5
9.1
8.9
8.2
7.4
6.7
5.8
4.9
Hi PR
389
373
359
343
335
329
316
303
291
277
266
260
255
246
236
227
218
211
Lo PR 147
136
127
117
110
106
98
87
78
70
62
57
55
47
40
34
30
23
SSZ160481A* / CA*F4860*6A* + TXV / MBE2000**-1
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
59.1
55.9
52.6
49.2
47.0
45.5
42.3
39.0
35.4
32.6
30.1
28.4
27.3
24.5
21.7
19.0
16.2 13.3
∆T
35.3
33.4
31.4
29.4
28.1
27.2
25.3
23.3
21.1
19.5
18.0
17.0
16.3
14.7
13.0
11.3
9.7
7.9
kW
3.69
3.62
3.54
3.47
3.4
3.40
3.32
3.25
3.14
3.06
2.99
2.95
2.92
2.85
2.78
2.71
2.63 2.56
Amps 17.6
16.3
15.2
14.3
13.8
13.5
12.7
12.1
11.5
11.0
10.5
10.2
10.1
9.6
8.9
8.4
7.7
6.9
COP
4.68
4.52
4.35
4.15
4.01
3.93
3.72
3.51
3.30
3.12
2.94
2.82
2.74
2.52
2.29
2.05
1.80 1.51
EER
16.0
15.5
14.9
14.2
13.7
13.4
12.7
12.0
11.3
10.7
10.0
9.6
9.4
8.6
7.8
7.0
6.1
5.2
Hi PR
405
388
373
357
348
342
328
315
302
288
277
270
265
255
246
235
227
219
Lo PR 140
130
122
112
106
102
94
83
75
67
59
55
53
45
39
33
28
22
SSZ160601A* / CA*F4860*6A* + TXV / MBE2000**-1
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
71.6
67.8
63.8
59.7
57.0
55.2
51.3
47.3
44.9
41.4
38.1
36.0
34.7
31.1
27.6
24.0
20.5 16.8
∆T
36.9
34.9
32.8
30.7
29.3
28.4
26.4
24.3
23.1
21.3
19.6
18.5
17.8
16.0
14.2
12.4
10.6
8.6
kW
4.73
4.63
4.53
4.44
4.4
4.34
4.25
4.15
4.27
4.16
4.06
4.00
3.96
3.86
3.76
3.66
3.55 3.45
Amps 21.7
20.0
18.7
17.6
16.9
16.6
15.6
14.8
14.1
13.5
12.8
12.5
12.3
11.6
10.8
10.2
9.3
8.4
COP
4.44
4.29
4.12
3.94
3.81
3.73
3.54
3.34
3.08
2.91
2.75
2.63
2.56
2.36
2.15
1.92
1.69 1.42
EER
15.2
14.7
14.1
13.5
13.0
12.7
12.1
11.4
10.5
9.9
9.4
9.0
8.7
8.1
7.3
6.6
5.8
4.9
Hi PR
395
379
364
348
340
334
321
308
295
282
270
264
259
249
240
230
222
214
Lo PR 133
124
116
106
101
97
89
79
71
64
56
52
50
43
37
31
27
21
High pressure is measured at the suction service valve ( the larger valve).
Low pressure is measured at the gauge port connection.
Amps = Outdoor unit amps (comp.+fan)
Calculations are based on nominal CFM and 70 °F indoor dry bulb.
kW = Total system power
Shaded area is AHRI Rating Conditions at 47°F outdoor ambient temperature