ROUBLESHOOTING
C
HART
Associated
LED Code
2
2
LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.
• Induced draft blower runs
continuously. No furnace
operation.
• Integrated control module
diagnostic
LED
is flashing
continuously.
C
CONTINUOUS
• Polarity of 115
or 24 volt
power is
reversed.
• Polarity of 115 volt AC
power to furnace or
integrated control module
is reversed.
• Red and blue wires to
transformer are reversed.
• Poor unit ground.
• Review wiring diagram to
correct polarity.
• Verify proper ground.
Correct if necessary.
• Reverse red and blue
wires connected to
transformer.
• Turn power OFF
prior to repair.
• Normal operation.
• LED is steady on
STEADY
• Furnace not operating.
• Integrated control module
diagnostic
LED
is
flashing
EIGHT
(8)
flashes.
8 FLASHES
• Problem with
igniter circuit.
• Improperly connected
igniter.
• Bad igniter.
• Poor unit ground.
• Poor burner ground.
• Faulty integrated control
module.
• Check and correct wiring
from integrated control
module to igniter.
• Replace bad igniter.
• Check and correct unit
ground wiring.
• Replace bad integrated
control module.
• Turn power OFF
prior to repair.
• Replace igniter
with proper
replacement part.
• Read precautions
in “Electrostatic
Discharge”
section of manual.
Cautions
& Notes
Corrective Action
Possible Causes
Fault
Description(s)
Symptoms of
Abnormal Operation
FLASHING