Goodman GSZ16 Installation & Service Reference Download Page 7

7

1. Break vacuum by fully opening liquid and suction base

valves.

2. Set thermostat to call for cooling.  Check indoor and out-

door fan operation and allow system to stabilize for 10
minutes for fixed orifices and 20 minutes for expansion
valves.

Charge Verification

REFRIGERANT UNDER PRESSURE!

 

 Do not overcharge system with refrigerant.

 Do not operate unit in a vacuum or at negative pres-

  sure.
Failure to follow proper procedures may cause 
property damage, personal injury or death.

WARNING

Use refrigerant certified 

 standards. Used refrigerant

may cause compressor damage.  Most portable machines
cannot clean used refrigerant to meet 

tandards.

to AHRI

AHRI s

CAUTION

NOTICE

Violation of EPA regulations may result in fines or other
penalties.

Damage to the unit caused by operating the compressor with the 
suction valve closed is not covered under the warranty and may 

cause serious compressor damage.

CAUTION

Final Charge Adjustment

The outdoor temperature must be 60

°

F or higher. Set the room

thermostat to COOL, fan switch to AUTO, and set the tem-
perature control well below room temperature.

Purge gauge lines.  Connect  service gauge manifold to base-
valve service ports.  Run the system (on low stage for two-
stage units) for 10 minutes to allow pressures to stabilize,
then check subcooling and/or superheat as detailed in the fol-
lowing sections.

Superheat = Suct. Line Temp. - Sat. Suct. Temp.

Subcooling = Sat. Liquid Temp. - Liquid Line Temp.

CAUTION

To prevent personal injury, carefully connect and disconnect
manifold gauge hoses. Escaping liquid refrigerant can cause
burns. Do not vent refrigerant into the atmosphere. Recover
all refrigerant during system repair and before final unit
disposal.

SUPERHEAT FORMULA = SUCT. LINE TEMP. - SAT. SUCT. TEMP.

55

57

59

61

63

65

67

69

71

10

13

17

20

23

26

29

30

31

8

11

14

16

19

22

26

27

29

5

8

10

13

15

19

23

24

25

---

---

6

9

11

15

20

21

23

---

---

---

---

7

12

17

18

20

---

---

---

---

---

8

13

15

16

---

---

---

---

---

7

10

11

13

---

---

---

---

---

---

7

8

10

---

---

---

---

---

---

---

7

8

---

---

---

---

---

---

---

---

7

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

---

SYSTEM SUPERHEAT (+/- 1°F)

Indoor Wet Bulb Temperature, °F

Outdoor Dry Bulb 

Temperature, °F

60
65
70

105
110
115

75
80
85
90
95

100

Summary of Contents for GSZ16

Page 1: ...lity of the carrier Verify the model number specifications electrical characteristics and accessories are correct prior to installation The distribu tor or manufacturer will not accept claims from dea...

Page 2: ...r springs can be installed between the con densing unit legs or frame and the roof mounting assembly to reduce noise vibration NOTE These units require special location consideration in areas of heavy...

Page 3: ...tance Cond Unit Tons Suct Liq Suct Liq Suct Liq 1 1 2 5 8 1 4 3 4 3 8 3 4 3 8 2 5 8 1 4 3 4 3 8 3 4 3 8 2 1 2 5 8 1 4 3 4 3 8 7 8 3 8 3 3 4 3 8 7 8 3 8 1 1 8 3 8 3 1 2 7 8 3 8 1 1 8 3 8 1 1 8 3 8 4 7...

Page 4: ...ented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing NOTE Before brazing verify indoor piston size...

Page 5: ...ch located near the unit do not install the switch on the unit Refer to the installa tion instructions supplied with the indoor furnace air handler for specific wiring connections and indoor unit conf...

Page 6: ...f disabling this function is desired move the jumper from DLY to NORM on the defrost control Adequate refrigerant charge for the matching HSVTC evapora tor coil and 15 feet of lineset is supplied with...

Page 7: ...Charge Adjustment The outdoor temperature must be 60 F or higher Set the room thermostat to COOL fan switch to AUTO and set the tem perature control well below room temperature Purge gauge lines Conne...

Page 8: ...URATED SUCTION TEMPERATURE F LIQUID PRESSURE PSIG R 22 R 410A 200 101 70 210 105 73 220 108 76 225 110 78 235 113 80 245 116 83 255 119 85 265 121 88 275 124 90 285 127 92 295 130 95 305 133 97 325 13...

Page 9: ...nit and refrigerant tubing sizes These adjustments should only be performed by qualified service personnel AdvancedAdjustmentRecommendations SUPERHEATFORMULA SUCTIONLINETEMPERA TURE SATURATEDSUCTIONTE...

Page 10: ...t with Voltmeter Low Voltage Test Voltage Faulty Evap Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortag...

Page 11: ...airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually c...

Page 12: ...gh not required to get the protection of the standard warranty registering your product is a relatively short process and entitles you to additional warranty protection except that failure by Californ...

Reviews: