HEATING SPECIFICATIONS

capacity

 btuh

c.o.p.

4.8

9.6

14.4

19.2

65

22.63

4.23

39.008

55.391

71.7732

88.156

60

21.42

4.09

37.802

54.185

70.5672

86.950

55

20.16

3.93

36.542

52.925

69.3072

85.690

50

18.85

3.75

35.228

51.611

67.9932

84.376

45

17.44

3.54

33.824

50.207

66.5892

82.972

40

16.20

3.36

32.582

48.965

65.3472

81.730

35

14.94

3.16

31.322

47.705

64.0872

80.470

30

13.55

2.88

29.933

46.315

62.6975

79.080

25

12.51

2.72

28.889

45.271

61.6535

78.036

20

11.52

2.56

27.899

44.281

60.6638

77.046

15

10.47

2.39

26.855

43.237

59.6198

76.002

10

9.40

2.19

25.778

42.161

58.5432

74.926

5

8.33

1.99

24.713

41.095

57.4775

73.860

0

7.26

1.78

23.647

40.029

56.4117

72.794

-5

6.20

1.56

22.581

38.964

55.346

71.728

-10

5.08

1.31

21.461

37.843

54.2258

70.608

Capacity of Unit

 With KW of Auxiliary heat 

Outdoor 
Ambient 

   °F.

Model: GHS140181A* / CA*F3TXV / MBR800**-1
Condition: 600 CFM Indoor Air @ 70°F DB

Basic Unit without 

Auxiliary Heat

capacity

 btuh

c.o.p.

4.8

9.6

14.4

19.2

65

30.17

4.30

46.550

62.933

79.315

95.698

60

28.56

4.14

44.942

61.325

77.707

94.090

55

26.88

3.98

43.262

59.645

76.027

92.410

50

25.13

3.79

41.510

57.893

74.275

90.658

45

23.26

3.58

39.638

56.021

72.403

88.786

40

21.60

3.39

37.982

54.365

70.747

87.130

35

19.92

3.19

36.302

52.685

69.067

85.450

30

18.76

2.91

35.146

51.528

67.911

84.293

25

17.32

2.74

33.700

50.083

66.465

82.847

20

15.95

2.58

32.330

48.712

65.095

81.477

15

14.50

2.40

30.884

47.267

63.649

80.031

10

13.01

2.21

29.393

45.776

62.158

78.541

5

11.54

2.00

27.918

44.300

60.682

77.065

0

10.06

1.79

26.442

42.824

59.207

75.589

-5

8.58

1.57

24.966

41.348

57.731

74.113

-10

7.03

1.32

23.415

39.797

56.180

72.562

C apacity of Unit

 W ith KW  of  Auxiliary heat 

Outdoor 
Ambient 

   °F.

M odel: G SH140241A* / CA*F3TXV / M BR800**1
Condition: 850 CFM  Indoor Air @  70°F DB

Basic Unit without 

Auxiliary Heat

capacity

 btuh

c.o.p.

4.8

9.6

14.4

19.2

65

43.49

4.37

59.875

76.257

92.6394

109.022

60

41.17

4.22

57.556

73.939

90.3212

106.704

55

38.75

4.04

55.134

71.517

87.8992

104.282

50

36.23

3.86

52.609

68.991

85.3734

101.756

45

33.53

3.64

49.910

66.292

82.6746

99.057

40

31.14

3.45

47.522

63.905

80.2872

96.670

35

28.72

3.25

45.100

61.483

77.8652

94.248

30

26.94

2.98

43.325

59.707

76.0895

92.472

25

24.87

2.82

41.249

57.631

74.0137

90.396

20

22.90

2.65

39.281

55.664

72.046

88.428

15

20.82

2.46

37.205

53.588

69.9701

86.353

10

18.68

2.26

35.065

51.447

67.8295

84.212

5

16.56

2.06

32.946

49.328

65.7104

82.093

0

14.44

1.84

30.827

47.209

63.5914

79.974

-5

12.33

1.61

28.708

45.090

61.4723

77.855

-10

10.10

1.35

26.480

42.863

59.2451

75.628

Basic Unit w ithout 

Auxiliary Heat

Model: GSH140361A* / CA*F4TXV / MBR1600**-1
Condition: 1,065 CFM Indoor Air @ 70°F DB

Outdoor 

Ambient 

   °F.

Capacity of Unit

 With KW of Auxiliary heat 

capacity

 btuh

c.o.p.

4.8

9.6

14.4

19.2

65

57.82

4.21

74.204

90.587

106.969

123.352

60

54.74

4.07

71.122

87.505

103.887

120.270

55

51.52

3.90

67.902

84.285

100.67

117.050

50

48.16

3.72

64.544

80.927

97.3092

113.692

45

44.57

3.52

60.956

77.339

93.7212

110.104

40

41.40

3.33

57.782

74.165

90.5472

106.930

35

38.18

3.14

54.562

70.945

87.3272

103.710

30

37.68

3.05

54.058

70.440

86.8225

103.205

25

34.77

2.88

51.155

67.537

83.9198

100.302

20

32.02

2.71

48.403

64.786

81.1682

97.551

15

29.12

2.52

45.501

61.883

78.2654

94.648

10

26.12

2.32

42.507

58.890

75.272

91.654

5

23.16

2.10

39.544

55.926

72.3087

88.691

0

20.20

1.88

36.581

52.963

69.3455

85.728

-5

17.24

1.65

33.617

50.000

66.3823

82.765

-10

14.12

1.38

30.503

46.885

63.2679

79.650

Capacity of Unit

 With KW of Auxiliary heat 

Basic Unit without 

Auxiliary Heat

Model: GSH140481A* / CA*F4860D6A* +TXV / MBR2000**-1
Condition: 1,550 CFM Indoor Air @ 70°F DB

Outdoor 
Ambient 

   °F.

capacity

 btuh

c.o.p.

4.8

9.6

14.4

19.2

65

69.14

4.81

85.517

101.900

118.282

134.665

60

65.45

4.65

81.832

98.215

114.597

130.980

55

61.60

4.46

77.982

94.365

110.747

127.130

50

57.59

4.26

73.967

90.350

106.732

123.115

45

53.30

4.03

69.677

86.060

102.442

118.825

40

49.50

3.82

65.882

82.265

98.647

115.030

35

45.65

3.60

62.032

78.415

94.797

111.180

30

41.02

3.24

57.404

73.787

90.169

106.552

25

37.86

3.06

54.244

70.626

87.009

103.391

20

34.87

2.89

51.248

67.630

84.013

100.395

15

31.70

2.69

48.087

64.470

80.852

97.234

10

28.45

2.47

44.828

61.210

77.593

93.975

5

25.22

2.25

41.601

57.984

74.366

90.749

0

21.99

2.01

38.375

54.757

71.140

87.522

-5

18.77

1.77

35.149

51.531

67.913

84.296

-10

15.38

1.49

31.757

48.140

64.522

80.905

M ODEL GSH140601A* / CA*F4860D6A* +TXV / M BR2000**-1
Condition: 1,850 CFM  Indoor Air @ 70°F DB

Capacity of Unit

 With KW of Auxiliary heat 

Outdoor 
Am bient 

   °F.

Basic Unit without 

Auxiliary Heat

capacity

 btuh

c.o.p.

4.8

9.6

14.4

19.2

65

49.78

4.56

66.160

82.542

98.9244

115.307

60

47.12

4.39

63.506

79.889

96.2712

112.654

55

44.35

4.21

60.734

77.117

93.4992

109.882

50

41.46

4.02

57.844

74.226

90.6084

106.991

45

38.37

3.79

54.755

71.137

87.5196

103.902

40

35.64

3.59

52.022

68.405

84.7872

101.170

35

32.87

3.38

49.250

65.633

82.0152

98.398

30

31.24

3.16

47.627

64.009

80.3919

96.774

25

28.84

2.98

45.220

61.602

77.9846

94.367

20

26.56

2.81

42.938

59.320

75.7027

92.085

15

24.15

2.61

40.531

56.913

73.2954

89.678

10

21.67

2.40

38.048

54.430

70.8129

87.195

5

19.21

2.17

35.591

51.973

68.3554

84.738

0

16.75

1.94

33.133

49.516

65.898

82.280

-5

14.29

1.70

30.676

47.058

63.4405

79.823

-10

11.71

1.43

28.093

44.475

60.8577

77.240

Model: GSH140421A* / CA*F4TXV / MBR2000**-1
Condition: 1,400 CFM Indoor Air @ 70°F DB

Outdoor 

Ambient 

   °F.

Capacity of Unit

 With KW of Auxiliary heat 

Basic Unit without 

Auxiliary Heat

capacity

 btuh

c.o.p.

4.8

9.6

14.4

19.2

65

34.69

4.53

51.076

67.458

83.8404

100.223

60

32.84

4.37

49.226

65.609

81.9912

98.374

55

30.91

4.19

47.294

63.677

80.0592

96.442

50

28.90

4.00

45.280

61.662

78.0444

94.427

45

26.74

3.77

43.127

59.509

75.8916

92.274

40

24.84

3.57

41.222

57.605

73.987

90.370

35

22.91

3.36

39.290

55.673

72.0552

88.438

30

20.93

2.97

37.311

53.694

70.0763

86.459

25

19.32

2.80

35.699

52.081

68.4638

84.846

20

17.79

2.63

34.170

50.553

66.9352

83.318

15

16.18

2.45

32.558

48.940

65.3227

81.705

10

14.51

2.25

30.895

47.277

63.660

80.042

5

12.87

2.04

29.249

45.631

62.0137

78.396

0

11.22

1.82

27.603

43.985

60.3676

76.750

-5

9.57

1.59

25.957

42.339

58.7215

75.104

-10

7.84

1.34

24.227

40.609

56.9914

73.374

Basic Unit without 

Auxiliary Heat

Outdoor 
Ambient 

   °F.

Capacity of Unit

 With KW of Auxiliary heat 

Model: GSH140301A* / CA*F3TXV / MBR1200**-1
Condition: 1,080 CFM Indoor Air @ 70°F DB

Summary of Contents for GSC140421A

Page 1: ...l Models listed on page 3 GSH 14 SEER Remote Heat Pump RT6213004 April 2006 This manual is to be used by qualified HVAC technicians only Goodman does not assume any responsibility for property damage...

Page 2: ...TIONING AND REFRIGERATION INSTITUTE ARI MAY USE THIS INFORMATION AT TEMPTING TO INSTALL OR REPAIR THIS UNIT WITHOUT SUCH BACK GROUND MAY RESULT IN PRODUCT DAMAGE PERSONAL INJURY OR DEATH WARNING WARNI...

Page 3: ...O PREVENT THE RISK OF PROPERTY DAMAGE PERSONAL INJURY OR DEATH DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASO LINE OR OTHER FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPLIANCE The model numb...

Page 4: ...roll compared to the traditional recip rocating compressor Due to their design Scroll compressors are inherently more tolerant of liquid refrigerant GSH14 model heat pumps do not use a reversing relay...

Page 5: ...4 16 18 3 19 8 L R Amps 41 0 54 0 63 0 73 0 88 0 109 0 137 0 Loss of Charge Pressure Switch Open Close 7 PSIG 25 PSIG 7 PSIG 25 PSIG 7 PSIG 25 PSIG 7 PSIG 25 PSIG 7PSIG 25 PSIG 7 PSIG 25 PSIG 7PSIG 2...

Page 6: ...0 17 1 17 6 19 1 20 5 16 7 17 2 18 6 20 0 15 9 16 3 17 7 19 0 14 7 15 1 16 4 17 6 S T 0 85 0 76 0 57 0 37 0 88 0 79 0 60 0 38 0 90 0 81 0 61 0 39 0 93 0 83 0 63 0 41 0 97 0 86 0 65 0 42 0 97 0 87 0 66...

Page 7: ...5 9 5 7 5 8 6 0 6 3 6 0 6 2 6 4 6 6 HI PR 138 148 156 163 154 166 175 183 176 189 199 208 200 215 227 237 225 242 256 267 248 267 282 295 LO PR 62 66 72 76 65 69 76 81 68 72 79 84 71 76 83 88 75 79 87...

Page 8: ...25 0 26 9 21 9 22 6 24 4 26 2 20 8 21 4 23 2 24 9 19 3 19 9 21 5 23 1 S T 0 86 0 77 0 58 0 38 0 89 0 80 0 60 0 39 0 92 0 82 0 62 0 40 0 94 0 85 0 64 0 41 0 98 0 88 0 66 0 43 0 99 0 88 0 67 0 43 Delta...

Page 9: ...12 1 12 3 12 6 12 3 12 5 12 8 13 1 HI PR 134 144 152 158 150 161 170 178 170 183 194 202 194 209 221 230 218 235 248 259 241 260 274 286 LO PR 64 68 74 79 67 72 78 83 70 75 81 87 74 78 85 91 77 82 90...

Page 10: ...6 26 6 27 4 29 6 31 8 26 0 26 7 28 9 31 0 24 7 25 4 27 5 29 5 22 8 23 5 25 5 27 3 S T 0 91 0 81 0 62 0 40 0 94 0 84 0 64 0 41 0 97 0 87 0 66 0 42 1 00 0 89 0 68 0 44 1 00 0 93 0 70 0 45 1 00 0 94 0 71...

Page 11: ...8 6 8 3 8 5 8 8 9 1 8 8 9 0 9 3 9 6 HI PR 134 145 153 159 151 162 171 179 172 185 195 203 195 210 222 232 220 237 250 261 243 261 276 288 LO PR 63 67 73 78 66 71 77 82 69 73 80 85 73 77 84 90 76 81 8...

Page 12: ...3 8 36 6 39 3 32 1 33 0 35 7 38 4 30 5 31 4 34 0 36 4 28 2 29 1 31 5 33 8 S T 0 81 0 72 0 55 0 35 0 84 0 75 0 57 0 37 0 86 0 77 0 58 0 38 0 89 0 80 0 60 0 39 0 92 0 83 0 62 0 40 0 93 0 83 0 63 0 41 De...

Page 13: ...1 11 4 11 7 12 2 11 8 12 0 12 4 12 9 HI PR 135 145 154 160 152 163 172 180 173 186 196 204 196 211 223 233 221 238 251 262 244 263 278 289 LO PR 61 65 71 76 65 69 75 80 68 72 78 83 71 75 82 88 74 79 8...

Page 14: ...1 37 6 38 7 41 9 45 0 36 7 37 8 40 9 43 9 34 9 35 9 38 9 41 7 32 3 33 3 36 0 38 6 S T 0 89 0 80 0 60 0 39 0 92 0 83 0 63 0 40 0 95 0 85 0 64 0 41 0 98 0 88 0 66 0 43 1 00 0 91 0 69 0 44 1 00 0 92 0 69...

Page 15: ...6 3 5 9 6 2 6 6 7 1 6 6 6 9 7 3 7 9 HI PR 133 143 152 158 150 161 170 177 170 183 193 202 194 209 220 230 218 235 248 258 241 259 274 286 LO PR 62 66 72 76 65 69 76 81 68 72 79 84 71 76 83 88 75 79 8...

Page 16: ...43 7 45 0 48 7 52 3 42 6 43 9 47 5 51 0 40 5 41 7 45 1 48 5 37 5 38 6 41 8 44 9 S T 0 84 0 75 0 57 0 37 0 87 0 78 0 59 0 38 0 89 0 80 0 61 0 39 0 92 0 83 0 63 0 40 0 96 0 86 0 65 0 42 0 97 0 86 0 65...

Page 17: ...3 7 8 7 3 7 7 8 2 8 8 8 2 8 6 9 1 9 8 HI PR 127 137 145 151 143 154 162 169 163 175 185 193 185 199 210 219 208 224 237 247 230 248 262 273 LO PR 60 64 70 75 64 68 74 79 66 71 77 82 70 74 81 86 73 78...

Page 18: ...3 58 8 63 1 51 4 53 0 57 3 61 5 48 9 50 3 54 5 58 5 45 3 46 6 50 5 54 2 S T 0 87 0 78 0 59 0 38 0 90 0 80 0 61 0 39 0 92 0 82 0 62 0 40 0 95 0 85 0 64 0 41 0 99 0 88 0 67 0 43 1 00 0 89 0 67 0 43 Del...

Page 19: ...9 16 3 16 9 17 5 16 9 17 3 17 9 18 6 HI PR 130 139 147 154 145 156 165 172 165 178 188 196 188 203 214 223 212 228 241 251 234 252 266 277 LO PR 58 62 68 72 62 65 71 76 64 68 74 79 67 71 78 83 70 75...

Page 20: ...7 11 520 2 712 85 35 465 24 386 11 079 2 791 90 35 033 24 477 10 556 2 860 95 34 600 24 558 10 042 2 929 100 33 735 24 398 9 337 2 988 105 32 870 24 214 8 656 3 047 110 31 659 23 420 8 239 3 097 115 3...

Page 21: ...01A CA F3636B6A TXV MBR1200 1 HEATING OPERATION Outdoor Ambient Temperature 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 5 10 MBh 34 7 32 8 30 9 28 9 27 6 26 7 24 8 22 9 20 9 19 3 17 8 16 8 16 2 14 5 1...

Page 22: ...14 3 06 2 98 AMPS 20 9 18 7 17 0 15 5 14 6 14 2 12 9 11 8 10 9 10 1 9 2 8 8 8 6 7 7 6 6 5 8 4 7 3 4 COP 4 21 4 07 3 90 3 72 3 60 3 52 3 33 3 14 3 05 2 88 2 71 2 59 2 52 2 32 2 10 1 88 1 65 1 38 EER 14...

Page 23: ...05 54 058 70 440 86 8225 103 205 25 34 77 2 88 51 155 67 537 83 9198 100 302 20 32 02 2 71 48 403 64 786 81 1682 97 551 15 29 12 2 52 45 501 61 883 78 2654 94 648 10 26 12 2 32 42 507 58 890 75 272 9...

Page 24: ...ht increase will occur in indoor temperature drop Delta T A slight decrease will occur in low and high side pressures and power A properly operating unit should be within plus or minus 2 degrees of th...

Page 25: ...GE DEFROST RELAY LVJB LOW VOLTAGE JUNCTION BOX RCCF RUN CAPACITOR FOR COMPRESSOR FAN RVC REVERSING VALVE COIL SA START ASSIST SC START CAPACITOR FOR COMPRESSOR OPTIONAL S R START RELAY FOR COMPRESSOR...

Reviews: