background image

5

Pressure test the system using dry nitrogen and soapy water
to locate leaks.  If you wish to use a leak detector, charge the
system to 10 psi using the appropriate refrigerant then use
nitrogen to finish charging the system to working pressure then
apply the detector to suspect areas. If leaks are found, repair
them. After repair, repeat the pressure test. If no leaks exist,
proceed to system evacuation.

System Evacuation

Condensing unit liquid and suction valves are closed.  The unit
is shipped with the valve stems closed and caps installed.

REFRIGERANT UNDER PRESSURE!

 

Failure to follow proper procedures may cause 
property damage, personal injury or death.

WARNING

NOTE: 

Scroll compressors should never be used to evacuate

or pump down a heat pump or air conditioning system.

NOTICE

THIS UNIT IS SHIPPED WITH A NITROGEN/HELIUM 
HOLDING CHARGE ONLY.  UNIT MUST BE 
EVACUATED AND CHARGED PER INSTALLATION 
INSTRUCTIONS WITH REFRIGERANT LISTED ON 
SERIAL RATING PLATE.

UNITS SHIPPED WITH A HOLDING CHARGE ARE
INTENDED FOR COMPONENT REPLACEMENT 
ONLY ON EXISTING SYSTEMS, AND NOT 
INTENDED FOR USE IN NEW SYSTEMS OR NEWLY
CONSTRUCTED HOMES.

NOTICE

NOTICE

UNITS MUST ONLY BE USED AS REPLACEMENT
COMPONENTS FOR PRE-2010 INSTALLED
SYSTEMS.

NOTE:

 Holding charge must be removed before brazing.

Prolonged operation at suction pressures less than 20 
psig for more than 5 seconds will result in overheating of 
the scrolls and permanent damage to the scroll tips, drive 
bearings and internal seal.

CAUTION

1. Open service valves before attaching vacuum pump.

2. Connect the vacuum pump with 250 micron capability to

the service valves.

3. Evacuate the system to 250 microns or less using suc-

tion 

and

 liquid service valves.  Using both valves is nec-

essary as some compressors create a mechanical seal
separating the sides of the system.

4. Close pump valve and hold vacuum for 10 minutes.  Typi-

cally pressure will rise during this period.

If the pressure rises to 1000 microns or less and remains
steady the system is considered leak-free; proceed to
startup.

5000

4500

4000

3500

3000

2500

2000

1500

1000

500

0      1      2      3      4       5      6      7      8       9

10

LEAK(S)
PRESENT

MINUTES

V

ACU

U

M

 

IN

 

MI

CR

O

N

S

CONDENSIBLES OR SMALL
LEAK PRESENT

NO LEAKS
NO CONDENSIBLES

If pressure rises above 1000 microns but holds steady
below 2000 microns, moisture and/or noncondensibles
may be present or the system may have a small leak.
Return to step 2: If the same result is encountered check
for leaks as previously indicated and repair as necessary
then repeat evacuation.

If pressure rises above 2000 microns, a leak is present.
Check for leaks as previously indicated and repair as nec-
essary then repeat evacuation.

Electrical Connections

HIGH VOLTAGE!

 

Disconnect ALL power before servicing.
Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death due to electric shock.
Wiring must conform with NEC or CEC and all
local codes. Undersized wires could cause
poor equipment performance, equipment damage
or fire.

WARNING

To avoid the risk of fire or equipment damage, use
copper conductors.

WARNING

NOTICE

Units with reciprocating compressors and non-bleed TXV’s
require a Hard Start Kit.

The condensing unit rating plate lists pertinent electrical data
necessary for proper electrical service and overcurrent protec-
tion.  Wires should be sized to limit voltage drop to 2% (max.)
from the main breaker or fuse panel to the condensing unit.
Consult the NEC, CEC, and all local codes to determine the
correct wire gauge and length.

Summary of Contents for GSC13018

Page 1: ...ds It is the owner s and installer s responsibility to read and com ply with all safety information and instructions accompanying these symbols Failure to heed safety information increases the risk of...

Page 2: ...t in a structure that is not complete either as part of new construction or renovation will void the warranty Installation Clearances Special consideration must be given to location of the con densing...

Page 3: ...onger than necessary for installation CAUTION Use only refrigerant grade dehydrated and sealed copper tub ing to connect the condensing unit with the indoor evaporator After cutting the tubing install...

Page 4: ...tion when using the heat trap compound Note Remove Schrader valves from service valves before brazing tubes to the valves Use a brazing alloy of 2 minimum silver content Do not use flux Torch heat req...

Page 5: ...or less using suc tion and liquid service valves Using both valves is nec essary as some compressors create a mechanical seal separating the sides of the system 4 Close pump valve and hold vacuum for...

Page 6: ...ow proper procedures may cause property damage personal injury or death WARNING 1 Add refrigerant amount shown in table below for the unit being installed Local codes often require a disconnect switch...

Page 7: ...nit disposal 1 Purge gauge lines Connect service gauge manifold to base valve service ports Run system at least 10 minutes to allow pressure to stabilize 2 Temporarily install thermometer on suction l...

Page 8: ...10 105 220 108 225 110 235 113 245 116 255 119 265 121 275 124 285 127 295 130 305 133 325 137 355 144 375 148 405 155 415 157 425 n a 435 n a 445 n a 475 n a 500 n a 525 n a 550 n a 575 n a 600 n a 6...

Page 9: ...it Test Control Circuit with Voltmeter Low Voltage Test Voltage Faulty Evaporator Fan Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resis...

Page 10: ...10 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 11: ...11 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 12: ...ty standards regardless of size or effi ciency We have designed these units to significantly reduce the most frequent causes of product failure They are simple to service and forgiving to operate We u...

Reviews: