PACKAGE HEAT PUMP SPECIFICATIONS
26
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1.
As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low
and high side pressures and power will not change.
2.
As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will
occur in low and high side pressures and power.
A properly operating unit should be within plus or minus
3 degrees
of the typical (
Delta T)
value shown.
A properly operating unit should be within plus or minus
7 PSIG
of the
HI PR
shown.
A properly operating unit should be within plus or minus
3 PSIG
of the
LO PR
shown.
A properly operating unit should be within plus or minus
3 Amps
of the typical value shown.
GPH14[42-60]H41A*
EXPANDED PERFORMANCE DATA
MODEL: GPH1442H41A*
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
47.1
44.6
42.0
39.3
37.5
36.3
33.8
31.1
26.7
24.6
22.7
21.4
20.6
18.5
16.4
14.3
12.2
10.0
DELTA T
33.6
31.8
29.9
28.0
26.7
25.9
24.0
22.2
19.0
17.5
16.1
15.2
14.7
13.2
11.7
10.2
8.7
7.1
KW
3.07
3.01
2.95
2.89
2.85
2.83
2.77
2.71
2.39
2.33
2.28
2.25
2.23
2.18
2.12
2.07
2.02
1.97
AMPS
12.5
11.6
10.9
10.3
9.9
9.8
9.2
8.8
8.4
8.1
7.7
7.5
7.5
7.1
6.7
6.3
5.9
5.3
COP
4.50
4.34
4.17
3.98
3.85
3.76
3.57
3.36
3.27
3.09
2.91
2.78
2.71
2.49
2.26
2.02
1.77
1.49
EER
15.4
14.8
14.2
13.6
13.1
12.9
12.2
11.5
11.2
10.5
9.9
9.5
9.2
8.5
7.7
6.9
6.0
5.1
HI PR
370
355
341
326
319
313
301
288
276
264
253
247
243
234
225
215
208
200
LO PR
137
127
119
109
103
99
91
81
73
65
58
54
52
44
38
32
28
22
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
MODEL: GPH1448H41A*
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
56.6
53.6
50.4
47.1
45.0
43.6
40.5
37.4
32.4
29.9
27.5
26.0
25.0
22.5
19.9
17.4
14.8
12.1
DELTA T
32.7
31.0
29.2
27.3
26.0
25.2
23.4
21.6
18.7
17.3
15.9
15.0
14.5
13.0
11.5
10.1
8.6
7.0
KW
3.61
3.54
3.47
3.40
3.36
3.33
3.26
3.19
3.17
3.10
3.03
2.99
2.96
2.89
2.82
2.75
2.67
2.60
AMPS
18.5
17.2
16.2
15.4
14.9
14.6
13.8
13.2
12.7
12.2
11.7
11.5
11.3
10.8
10.2
9.7
9.1
8.3
COP
4.59
4.43
4.25
4.06
3.92
3.84
3.64
3.43
2.99
2.82
2.66
2.55
2.48
2.28
2.07
1.85
1.62
1.37
EER
15.7
15.1
14.5
13.9
13.4
13.1
12.4
11.7
10.2
9.6
9.1
8.7
8.5
7.8
7.1
6.3
5.5
4.7
HI PR
383
368
353
338
330
324
311
299
286
273
262
256
251
242
233
223
215
208
LO PR
135
126
118
108
102
98
90
80
73
65
57
53
51
43
37
31
27
22
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
MODEL: GPH1460H41A*
HEATING OPERATION
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
68.5
64.9
61.0
57.1
54.5
52.8
49.1
45.2
42.1
38.9
35.8
33.8
32.5
29.2
25.9
22.6
19.3
15.8
DELTA T
39.6
37.5
35.3
33.0
31.5
30.6
28.4
26.2
24.4
22.5
20.7
19.6
18.8
16.9
15.0
13.1
11.1
9.1
KW
4.76
4.67
4.57
4.47
4.41
4.37
4.28
4.18
4.08
3.98
3.88
3.83
3.79
3.69
3.59
3.50
3.40
3.30
AMPS
23.9
22.2
20.9
19.7
19.0
18.7
17.7
16.8
16.1
15.4
14.8
14.4
14.2
13.6
12.7
12.0
11.2
10.2
COP
4.21
4.07
3.91
3.74
3.61
3.54
3.36
3.17
3.02
2.86
2.70
2.58
2.51
2.32
2.11
1.89
1.66
1.40
EER
14.4
13.9
13.4
12.8
12.3
12.1
11.5
10.8
10.3
9.8
9.2
8.8
8.6
7.9
7.2
6.5
5.7
4.8
HI PR
407
390
375
358
350
343
330
317
303
290
278
272
267
257
247
237
228
220
LO PR
130
121
113
104
98
94
87
77
70
62
55
51
49
41
36
30
26
21
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.