PACKAGE COOLING SPECIFICATIONS
12
GPC13[48-60]H41BA
IMPORTANT:
While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
(1)
Maximum Overcurrent Protection Device:
MUST
use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
*
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice.
ALWAYS
refer to the units serial plate for the most up-to-date general and electrical information.
GPC1348H41BA
GPC1360H41BA
COOLING
COOLING CAPACITY, BT UH
45,500
57,500
CAPACITY
SEER
13.0
13.0
UNIT
VOLTAGE (NAMEPLATE)
208-230/1/60
208-230/1/60
ELECTRICAL
AMPS (TOTAL)
24.17
33.6
SPECIFICATION
MINIMUM CIRCUIT AMPACITY
29.2
40.2
MAXIMUM OVERCURRENT PROTECT ION
(1)
45
60
COMPRESSOR
TYPE
SCROLL
SCROLL
RATED LOAD AMPS
19.9
26.4
LOCKED ROT OR AMPS
109
134
CONDENSER
HORSEPOWER
1/4
1/4
F AN MOTOR
RPM
1075
1075
FULL LOAD AMPS
1.4
1.4
LOCKED ROT OR AMPS
2.9
2.9
CONDENSER FAN
BLADE DIAMET ER (INCHES) /# OF BLADES
22 / 4
22 / 4
CONDENSER
FACE AREA - SQ. FT.
19.1
19.1
COIL
NUMBER OF ROWS
1
2
FINS PER INCH
21
16
EVAPORATOR
HORSEPOWER - NO. OF SPEEDS
1/2 - 3
3/4 - 3
BLOWER
FULL LOAD AMPS
2.87
5.8
MOTOR
LOCKED ROT OR AMPS
4.9
NA
MOTOR SPEED TAP - COOLING
MEDIUM
T 2
RPM
1075
1075
EVAPORATOR
DIAMETER X WIDTH (INCHES)
10 x 8
11 x 8
BLOWER
RATED SCFM COOLING
1,585
1,850
MAX EXTERNAL STATIC PRESS ("w.c.)
0.5
0.5
EVAPORATOR
FACE AREA - SQ. FT.
6.2
7.0
COIL
NUMBER OF ROWS
4
4
FINS PER INCH
14
14
GENERAL
FILTER SIZE - SQ. FT. *
(2) 20 x 20 x 1
(2) 20 x 25 x 1
INFORMATION
DRAIN SIZE (INCHES)
3/4"
3/4"
EXPANSION DEVICE
ORRIFICE (0.076)
ORIFICE (0.088)
REFRIGERANT CHARGE R-410A (Oz.)
110
160
POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN.)
3/4, 1, 1-1/4
3/4, 1, 1-1/4
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.)
1/2
1/2
SHIPPING WEIGHT LBS.
400
400
OPERAT ING WEIGHT LBS.
390
390