PACKAGE COOLING SPECIFICATIONS
8
All wires and overcurrent protection devices are sized for use with electric heaters only and without
refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See
PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent
protection during refrigeration cycle.
WARNING
WARNING
GPC14[24-36]H41A*
IMPORTANT:
While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
(1)
Maximum Overcurrent Protection Device:
MUST
use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
*
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice.
ALWAYS
refer to the units serial plate for the most up-to-date general and electrical information.
GPC1424H41*
GPC1430H41*
GPC1436H41*
COOLING
COOLING CAPACITY, BTUH
24,600
28,400
35,600
CAPACITY
SEER / EER
14.5 / 12.1
14.0 / 12.0
14.0 / 12.0
UNIT
VOLTAGE (NAMEPLATE)
208-230/1/60
208-230/1/60
208-230/1/60
ELECTRICAL
AMPS (TOTAL)
10.5
13.16
20.06
SPECIFICATION
MINIMUM CIRCUIT AMPACITY
12.5
15.6
24.2
MAXIMUM OVERCURRENT PROTECTION
(1)
20
25
40
COMPRESSOR
TYPE
RECIP
RECIP
SCROLL
RATED LOAD AMPS
7.9
9.8
16.7
LOCKED ROTOR AMPS
41
55
79
CONDENSER
HORSEPOWER
1/6
1/4
1/4
FAN MOTOR
RPM
815
830
830
FULL LOAD AMPS
1.1
1.5
1.5
LOCKED ROTOR AMPS
1.7
3.0
3.0
CONDENSER FAN
BLADE DIAMETER (INCHES) / NUMBER OF BLADES
22 / 3
22 / 3
22 / 3
CONDENSER
FACE AREA - SQ. FT.
13.4
13.4
13.4
COIL
NUMBER OF ROWS
1
1
1
FINS PER INCH
24
24
24
EVAPORATOR
HORSEPOWER - NO. OF SPEEDS
1/2 - 5
1/2 - 5
1/2 - 5
BLOWER
FULL LOAD AMPS
1.5
1.86
1.86
MOTOR
LOCKED ROTOR AMPS
NA
NA
NA
MOTOR SPEED TAP - COOLING
T2
T2
T2
RPM
1050
1050
1050
EVAPORATOR
DIAMETER X W IDTH (INCHES)
10 X 8
10 X 8
10 X 8
BLOWER
HI EFFICIENCY COOLING CFM
850
1,050
1,200
5 TON NOMINAL COOLING CFM
NA
NA
NA
FAN ONLY COOLING CFM
800
950
1,100
MAX EXTERNAL STATIC PRESS ("w.c.)
0.5
0.5
0.5
EVAPORATOR
FACE AREA - SQ. FT.
5.25
4.67
5.2
COIL
NUMBER OF ROWS
3
4
3
FINS PER INCH
16
16
14
GENERAL
FILTER SIZE - SQ. FT. *
20 x 20 x 1
20 x 25 x 1
25 x 25 x 1
INFORMATION
DRAIN SIZE (INCHES)
3/4"
3/4"
3/4"
EXPANSION DEVICE
ORIFICE (0.057)
ORIFICE (0.060)
ORIFICE (0.065)
REFRIGERANT CHARGE R-410A (Oz.)
83
78
80
POWER SUPPLY CONDUIT KNOCKOUT SIZE (INCHES)
3/4, 1, 1-1/4
3/4, 1, 1-1/4
3/4, 1, 1-1/4
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (INCHES)
1/2
1/2
1/2
SHIPPING WEIGHT LBS.
310
310
370
OPERATING WEIGHT LBS.
300
300
360