Goodman GMNTE Installation & Operating Instructions Manual Download Page 12

IO-231

  6/03

12

below 55

o

 F during heating operation. This will minimize the

possibility of condensate forming inside the heat exchanger.
When this type of system is utilized the volume of air must
not be reduced.
Plenum chambers and air ducts must be installed in
accordance with the Standard for the Installation of Air
Conditioning and Ventilating Systems, NFPA #90A, or the
Standard for the Installation of Warm Air Heating and Air
Conditioning Systems, NFPA
# 90B.
If installed in parallel with a cooling unit the damper or other
means used to control the flow of air must be adequate to
prevent chilled air from entering the furnace, and if manually
operated must be equipped with means to prevent
operation of the other unit unless the damper is in the full
heat or cool position.

NOTE:

 UPON INITIAL START-UP SOME SMOKE OR AN

ODOR MAY BE PRESENT. THIS IS NORMAL AND
SHOULD DISAPPEAR IN A SHORT AMOUNT OF TIME.
IT IS

 

RECOMMENDED THAT WINDOWS AND DOORS

BE OPENED UPON INITIAL START-UP TO VENT THIS

NON-TOXIC

 SMOKE.

One of the most common causes of problems, including
premature heat exchanger failure, in a forced air heating
system is insufficient return air. The return air connections
to the furnace should be approximately equal to the area
of warm air discharge. Consult local codes for specific
requirements.
All return ducts must be adequately secured to the furnace
and sealed airtight. All other ductwork must be secured
with approved connections and sealed airtight.
When the furnace is mounted on a platform it must be
sealed air tight between the furnace and the return
ductwork. The floor or platform must provide sound physical
support for the furnace without cracks, gaps, sagging, etc.
around the base as to provide an airtight seal between the
support and the base.
Install the return air to terminate through the base under
the furnace. For installations where return air ducts cannot
be run under the floor, the return air supply may be taken
from the side(s).
Embosses are provided on the sides of the furnace for use
as a template for the ductwork connection.
Where the maximum required airflow is 

1800 c.f.m.

 or

greater, the bottom or both sides must be utilized for return
air supply. Never use the rear of the furnace for the return
connection.

ELECTRICAL SUPPLY CONNECTIONS

The electrical requirements are 115Volts, 60 Hz., 1 Ph. A
separate supply line with a current overload device and a
manual switch, where required, must be installed. Type “T”
wire or equivalent with a minimum rating of 95

o

F (35

o

C)

temperature rise must be run directly from the main power
supply. Use copper conductors only.

Holes are provided on both sides of the furnace for electrical
connection. The junction box may be moved to either side.
The entry holes for supply and low voltage control wires are
for use with ½” electrical connectors.
All electrical wiring entering the furnace must be secured to
the casing with proper methods of strain relief. Solderless
connectors may be used to connect wires inside the junction
box for supply wires.

It is recommended that a means of shutting off the power
be within sight of the furnace.

CONTROL VOLTAGE CONNECTIONS

Thermostat Installation

Install the thermostat in accordance with the instructions
accompanying the thermostat. Connect the thermostat
wiring to the thermostat terminal block on the furnace
control board.  The thermostat wiring should be a minimum
of 18 gauge. Adhere to recommended color code to
facilitate future troubleshooting.
The thermostat should be located near the return air grille
or opening. It should be approximately 5 feet from the floor
level. Never locate the thermostat where it will be influenced
by heat generated by hot water pipes, lamps, televisions,
direct sunlight, supply air registers, etc.
Interconnecting wiring must be secured and protected from
damage or disconnection. The use of solderless connectors
or equivalent is recommended.

Setting The Heat Anticipator

Following the instructions accompanying the thermostat for
proper adjustment of the anticipator.

FEATURES

The integrated control board in this furnace has terminals
provided for added features. These features are a 115v.
Humidifier, an Electronic Air Cleaner, Blower “OFF” Timing
and a 24v. Dehumidifier.

115 Volt Humidifier

The “115v HUM” terminal is located on the high voltage side
of the board. This terminal is energized whenever the power
vent blower is energized.

Installation of the electrical supply must be in accordance
with local codes.  In the absence of local codes refer to
the National Electrical Code ANSI/NFPA No. 7 (latest edi-
tion), which can be obtained from the National Fire Pro-
tection Association, Batterymarch Park, Quincy, MA 02269.
In Canada refer to the latest edition of the Canadian Elec-
trical Code C22.1 Part I.

Summary of Contents for GMNTE

Page 1: ...NOT USE THIS FURNACE IF ANY PART HAS BEEN UNDERWATER IMMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT THE FURNACE AND TO REPLACE ANY PART OF THE CONTROL SYSTEM AND ANY GAS CON TROL THAT HAS...

Page 2: ...t switch Roll out switch Transformer Door interlock switch Air pressure switch Induced draft blower BURNER ASSEMBLY Burners Manifold Orifices Gas Valve Igniter Flame sensor MISCELLANEOUS Wrapper Acces...

Page 3: ...e with the current CAN CGA B149 1 2 Gas Installation Codes local plumbing or waste water codes and other applicable codes Additional helpful publications available from the NFPA are NFPA 90A Installat...

Page 4: ...es equal to or less than 1 2 psig 3 5 kPa MIN CLEARANCES TO COMBUSTIBLE SURFACES Unobstructed front clearance of 24 for servicing is recommended RIGHT SIDE 1 VENT 0 REAR 0 LEFT SIDE 1 TOP OF PLENUM 1...

Page 5: ...in ANSI Z221 3 section 5 3 When installed as a non direct vent furnace in an area which is deemed as a confined area see ANSI Z223 1 section 1 7 Space Confined the requirements are as follows All Com...

Page 6: ...CTION BOOKLET THE VENT MUST TERMINATE OUTDOORS VENT COMBUSTION AIR SUPPLY PIPE LENGTHS Elbows must be long radius types Quarter bends or DWV The maximum length of the vent pipe and the combustion air...

Page 7: ...vent terminal within four 4 feet of an adjacent building DIRECT VENT INSTALLATION DO NOT locate the vent terminal within twelve 12 inches of an operable window or door NON DIRECT VENT INSTALLATION DO...

Page 8: ...nstructions Failure to follow these instructions can cause products of combustion including CARBON MONOXIDE to enter the building This appliance may be horizontally vented through an exterior wall See...

Page 9: ...ns are not available a condensate pump may be employed This condensate pump must be constructed of corrosion resistant materials It must also have an auxiliary switch that will shut down the furnace i...

Page 10: ...IO 231 6 03 10 DRAIN CONNECTIONS UPFLOW LEFT DOWNFLOW LEFT SIDE DOWNFLOW RIGHT SIDE UPFLOW RIGHT SIDE...

Page 11: ...diameters and length in ft 3 hr with a pressure drop of 0 3 W C and a specific gravity of 0 60 natural gas After the length of pipe has been determined select the pipe size which will provide the mini...

Page 12: ...NNECTIONS The electrical requirements are 115Volts 60 Hz 1 Ph A separate supply line with a current overload device and a manual switch where required must be installed Type T wire or equivalent with...

Page 13: ...0 Btu ft3 ALTITUDE NAT GAS ORIFICE SIZE 0 1 999 45 2 000 2 999 46 3 000 3 999 47 4 000 4 999 47 5 000 5 999 47 6 000 7 000 48 The input to the furnace must be checked AFTER reorificing For altitudes a...

Page 14: ...D CHECK OUT PROCEDURE General In most cases the safety controls are wired is series with the W leg It is imperative that these switches remain in the circuit Never jumper relocate unless as noted on t...

Page 15: ...s blocked or dirty filters Circulating air filters must be inspected monthly for dirt accumulation and replaced if necessary Failure to maintain clean filters can cause premature heat exchanger failur...

Page 16: ...78 68 1264 68 351 540 1058 68 1523 68 468 720 Norm 975 61 1404 61 1 5 390 600 Norm 1175 61 1692 61 2 0 520 800 1073 56 1544 56 429 660 1293 56 1861 56 572 880 945 63 1361 63 468 720 1058 68 1523 68 2...

Page 17: ...ollowing figure for switch positions and their corresponding taps Turn off power to furnace for a minimum of 10 sec onds allowing motor to reset and recognize new speed selection Turn on power to furn...

Page 18: ...will remain inoperable until this situation is corrected The venter blower is energized The vent pressure switch will close when it detects a pressure in excess of its setting If the pressure switch f...

Page 19: ...n the heat exchanger perform the following Adjust the room thermostat to its lowest setting Turn off the gas and electric supply to the furnace Remove the control access door Open the gas supply union...

Page 20: ...se any telephone in your Do not touch any electric switch Do not try to light any appliance WHAT TO DO IF YOU SMELL GAS the gas suppliers instructions Immediately call your supplier automatically ligh...

Page 21: ...SURFACE IGNITION RELAY COM HI BL R SO GV LS P P ROS Y YLO G W 2 R W 1 BLUE WIRE COLOR CODE ORANGE GREEN BROWN BLACK PVR2 POWER VENT RELAY HIGH FIRE PVR1 POWER VENT RELAY LOW FIRE ROS ROLLOUT SWITCH PV...

Page 22: ...ent causes of product failure They are simple to service and forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we kn...

Reviews: