All furnaces ship as high speed for cooling.  Installer must adjust blower speed as needed.

• 

For most jobs, about 400 CFM per ton when cooling is desirable.

• 

INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE

.

Airflow Data — GMEC960302BN

COOLING

Dipswitch Setting:

Switch Bank 2

Switch 1 2 3

Static

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

G

870

658

548

469

413

349

293

N/A

**OFF OFF OFF

Ylo

874

697

612

533

470

414

361

303

1146

1097

1049

1002

941

895

846

787

ON OFF OFF

Ylo

874

697

612

533

470

414

361

303

928

868

810

743

670

614

560

505

ON ON OFF

Ylo

928

868

810

743

670

614

560

505

1146

1097

1049

1002

941

895

846

787

OFF ON ON

Ylo

874

697

612

533

470

414

361

303

1146

1097

1049

1002

941

895

846

787

ON OFF ON

Ylo

885

821

755

684

621

557

508

461

1146

1097

1049

1002

941

895

846

787

ON ON ON 

Ylo

885

821

755

684

621

557

508

461

874

697

612

533

470

414

361

303

**  Factory Default

HEATING

Dipswitch Setting:

Switch Bank 3

Switch 1 2

Static

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

Rise

CFM

CFM

CFM

**OFF OFF

W1

870

21

658

28

548

34

469

40

413

45

349

293

N/A

W2

885

30

821

32

755

35

684

39

621

43

557

508

461

ON OFF

W1

874

21

697

27

612

31

533

35

470

40

414

361

303

W2

885

30

821

32

755

35

684

39

621

43

557

508

461

ON ON

W1

874

21

697

27

612

31

533

35

470

40

414

361

303

W2

928

29

868

31

810

33

743

36

670

40

614

560

505

OFF ON

W1

928

20

868

22

810

23

743

25

670

28

614

560

505

W2

1146

23

1097

24

1049

25

1002

27

941

28

895

846

787

**  Factory Default

Downloaded from 

ManualsNet.com

 search engine

Summary of Contents for GMEC96

Page 1: ...eating Durable Silicon Nitride igniter Quiet two speed induced draft blower Self diagnostic control board with constant memory fault code history output to a LED Color coded low voltage terminals with...

Page 2: ...M Upflow Horizontal N Low NOx C Downflow Horizontal Cabinet Width Motor A 14 C 21 V Variable Speed ECM ComfortNet B 17 D 24 E Multi Speed ECM S Single Speed Maximum CFM 2 800 CFM 4 1600 CFM Gas Valve...

Page 3: ...6 8 8 8 8 11 6 13 3 13 3 13 3 Max Overcurrent amps 15 15 15 15 15 15 15 15 15 15 15 Shipping Weight lbs 106 106 110 111 112 115 118 123 140 140 154 Natural Gas BTU h DOE AFUE based upon Isolated Combu...

Page 4: ...ustible floor the floor MUST be wood ONLY 5 9 19 34 19 B C 23 2 1 2 2 6 5 9 19 23 24 31 A 21 2 14 23 1 1 28 2 1 2 2 2 6 1 26 23 Folded Flanges 22 Unfolded Flanges D Unfolded Flanges E Folded Flanges A...

Page 5: ...623 506 451 393 343 293 N A N A OFF OFF OFF Ylo 914 874 841 805 772 732 696 657 Y 1070 1040 1005 975 942 915 883 849 ON OFF OFF Ylo 653 597 552 507 460 410 366 326 Y 914 874 841 805 772 732 696 657 ON...

Page 6: ...91 1168 1135 1112 1081 1055 1024 998 OFF ON ON Ylo 653 597 552 507 460 410 366 326 Y 721 679 635 591 552 505 463 422 ON OFF ON Ylo 1191 1168 1135 1112 1081 1055 1024 998 Y 1091 1061 1026 996 962 936 9...

Page 7: ...1026 991 961 929 894 864 829 OFF OFF ON Ylo 880 838 794 763 722 689 644 606 Y 1330 1301 1274 1244 1227 1191 1163 1132 OFF ON ON Ylo 697 654 600 557 508 460 419 371 Y 1254 1230 1199 1171 1139 1115 1086...

Page 8: ...895 846 787 OFF ON ON Ylo 874 697 612 533 470 414 361 303 Y 1146 1097 1049 1002 941 895 846 787 ON OFF ON Ylo 885 821 755 684 621 557 508 461 Y 1146 1097 1049 1002 941 895 846 787 ON ON ON Ylo 885 82...

Page 9: ...90 834 778 OFF OFF ON Ylo 960 898 840 780 711 659 596 547 Y 989 932 882 819 773 695 650 586 OFF ON ON Ylo 856 667 546 466 413 357 302 N A Y 1143 1095 1046 996 946 890 834 778 ON OFF ON Ylo 989 932 882...

Page 10: ...N A Y 1236 1189 1149 1101 1066 1017 969 928 OFF OFF ON Ylo 1328 1287 1249 1215 1170 1131 1085 1046 Y 1163 1115 1065 1018 979 928 878 832 OFF ON ON Ylo 782 629 547 469 396 333 N A N A Y 947 899 842 786...

Page 11: ...94 842 784 726 682 618 562 519 Y 1221 1172 1128 1087 1049 1005 959 922 OFF OFF ON Ylo 894 842 784 726 682 618 562 519 Y 1311 1293 1249 1203 1172 1122 1088 1041 OFF ON ON Ylo 750 644 569 507 442 388 32...

Page 12: ...152 1096 1031 978 914 856 OFF OFF ON Ylo 1185 1121 1058 992 933 868 808 750 Y 1839 1790 1757 1699 1665 1615 1568 1527 OFF ON ON Ylo 1408 1337 1279 1218 1167 1112 1062 999 Y 1727 1691 1642 1600 1545 15...

Page 13: ...y Default HEATING Dipswitch Setting Switch Bank 3 Switch 1 2 Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM CFM CFM OFF OFF W1 1522 40 1464 42 1402 44 1338 46...

Page 14: ...tch Bank 3 Switch 1 2 Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM CFM CFM OFF OFF W1 1283 48 1219 51 1162 53 1101 56 1036 59 974 917 864 W2 1811 49 1772 50...

Page 15: ...ory Default HEATING Dipswitch Setting Switch Bank 3 Switch 1 2 Static 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM CFM CFM OFF OFF W1 1796 41 1753 42 1697 44 1645 4...

Page 16: ...UT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULAS BTU OUTPUT CFM x 1 08 x RISE RISE BTU OUTPUT 1 08 CFM 800 Temperature Rise Outpu...

Page 17: ...SIS GROUND 2 3 IGNITER SURFACE HOT 2 YL PU C 2 C BLOWER DRAFT INDUCED BK PM BK BLOWER COMPARTMENT 115 VAC 1 OVERCURRENT BK HARNESS ECM MTR HI TERMINAL OR POWER BEFORE IGNITER RD BK TO RD POWER SUPPLY...

Page 18: ...it N A TBD TBD N A HASFK 1 HASFK 1 HASFK 2 HASFK High Altitude LP Gas Kit N A TBD TBD N A HASFK 1 HASFK 1 HASFK 2 0270F05404 Horizontal Drain Tubing Kit LPLP03 Low LP Gas Pressure Switch LPM 08 LP Con...

Reviews: