Goodman GDH8 Technical Manual Download Page 4

4

PRODUCT DESIGN

NFPA 54/ANSI Z223.1 - latest edition. In Canada, the fur-
naces must be vented in accordance with the National Stan-
dard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2
- latest editions and amendments.

NOTE:

 The vertical height of the Category I venting system

must be at least as great as the horizontal length of the
venting system.

Accessibility  Clearances (Minimum)

Unobstructed front clearance of 24" 

for servicing

 is rec-

ommended.

SW

B

1

0

3

6

1

1

*    24" clearance for serviceability recommended.

MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS - INCHES

**  Single Wall Vent (SW) to be used only as a connector. 
     Refer to the venting tables outlined in the Installation Manual for
     additional  venting requirements.

Vent

Sides

Top

Rear

Front*

Note:  

In all cases accessibility clearance shall take prece-

dence over clearances from the enclosure where accessi-
bility clearances are greater.  All dimensions are given in
inches.

High Altitude Derate

IMPORTANT NOTE: 

The furnace as shipped requires no

change to run between 0 - 4500 feet. Do not attempt to
increase the firing rate by changing orifices or increasing
the manifold pressure below 4500 feet. This can cause poor
combustion and equipment failure.

High altitude installations above 4500 feet may require both
a pressure switch and an orifice change. These changes
are necessary to compensate for the natural reduction in
the density of both the gas fuel and the combustion air at
higher altitude.

For installations above 4500 feet, please refer to your dis-
tributor for required kit(s). Contact the distributor for a tabu-
lar listing of appropriate manufacturer’s kits for propane
gas and/or high altitude installations. The indicated kits must
be used to insure safe and proper furnace operation. All
conversions must be performed by a qualified installer, or
service agency.

General Operation

The GDH8 furnaces are equipped with an electronic ignition
device used to light the burners and an induced draft blower
to exhaust combustion products.

An interlock switch prevents furnace operation if the inner
blower door is not in place. Keep the blower access door in
place except for inspection and maintenance. 

(See illustra-

tion on page 5.)

This furnace is also equipped with a self-diagnosing elec-
tronic control module. In the event a furnace component is
not operating properly, the control module LED  will  flash on
and off in a factory-programmed sequence, depending on
the problem encountered. This light can be viewed through
the observation window in the blower access door. Refer to
the 

Troubleshooting Chart

 for further explanation of the LED

codes and 

Abnormal Operation - Integrated Ignition Control

section in the Service Instructions for an explanation of the
possible problem.

The rated heating capacity of the furnace should be greater
than or equal to the total heat loss of the area to be heated.
The total heat loss should be calculated by an approved
method or in accordance with “ASHRAE Guide” or “Manual
J-Load Calculations” published by the Air Conditioning Con-
tractors of America.

*Obtain from: American National Standards Institute 1430
Broadway New York, NY 10018

Location Considerations

The furnace should be as centralized as is practical
with respect to the air distribution system.

Do not install the furnace directly on carpeting, tile, or
combustible material other than wood flooring.

When installed in a residential garage, the furnace
must be positioned so the burners and ignition source
are located not less than 18 inches (457 mm) above
the floor and protected from physical damage by ve-
hicles.

Notes:

WARNING

T

O PREVENT POSSIBLE PERSONAL INJURY OR DEATH DUE TO ASPHYXIATION, 

THIS FURNACE MUST BE 

C

ATEGORY 

I

 VENTED.  

D

O NOT VENT USING

C

ATEGORY 

III

 VENTING.

Category I Venting is venting at a non-positive pressure.  A
furnace vented as Category I is considered a fan-assisted
appliance and the vent system does not have to be “gas
tight.”  

NOTE:

  Single stage gas furnaces with induced draft

blowers draw products of combustion through a heat ex-
changer allowing, in some instances, common venting with
natural draft appliances (i.e. water heaters). All installations
must be vented in accordance with National Fuel Gas Code

Summary of Contents for GDH8

Page 1: ...2013 Goodman Manufacturing Company L P This manual is to be used by qualified professionally trained HVAC technicians only Goodman does not assume any responsibility for property damage or personal in...

Page 2: ...erform service on this unit you assume responsibility for any personal injury or property damage which may result Many jurisdictions require a license to install or service heating and air conditionin...

Page 3: ...the imposition of substantial fines These regulations may vary by jurisdiction Should questions arise contact your local EPA office WARNING WARNING Do not connect or use any device thatisnotdesigncer...

Page 4: ...n interlock switch prevents furnace operation if the inner blower door is not in place Keep the blower access door in place except for inspection and maintenance See illustra tion on page 5 This furna...

Page 5: ...33 3 8 A B 28 High Voltage Electrical Low Voltage Electrical Gas Inlet MODEL A B NON COMBUSTIBLE FLOOR BASE GDH80403A GDH80603A 14 12 1 2 SBT14 GDH80804B 17 1 2 16 SBT17 GDH81005C 21 19 1 2 SBT21 All...

Page 6: ...B1370158 0 70 PRESSURE SWITCH Part Number 0130F00035 0130F00036 Open Setting F 220 180 GDH80403A A 1 GDH80603A A 1 GDH80804B A 1 GDH81005C A 1 PRIMARY LIMIT Part Number 10123529 Open Setting F 300 GD...

Page 7: ...Open Setting F 180 210 GDH80403A B 1 GDH80603A B 1 GDH80804B B 1 GDH81005C B 1 PRIMARY LIMIT Negative pressure readings are in inches of water column in w c Part Number 10123529 Open Setting F 300 GD...

Page 8: ...ights have an insulated Z bracket for use with one size smaller furnace All proper coil combinations are subject to being AHRI rated with a matched outdoor unit C A P F 1824 A 6 A PRODUCT TYPE C Indoo...

Page 9: ...h this furnace and must be provided by the installer The filters used must comply with UL900 or CAN ULCS111 standards Installing this furnace without filters will void the unit warranty FURNACE INPUT...

Page 10: ...dipswitches on the ignition control as follows Note This furnace is designed to be used with a single stage thermostat Modified Two Stage Fixed 5 Min Low Stage Auto Time 1 12 Min Low Stage Single Stag...

Page 11: ...onnections in accordance with the National Electrical Code and or all existing local codes 3 Vent and combustion air diameters may vary depending upon vent length Refer to the latest editions of the N...

Page 12: ...on vent length Refer to the latest editions of the National Fuel Gas Code NFPA 54 ANSI Z223 1 in the USA and the Canada National Standard of Canada CAN CSA B149 1 and CAN CSA B142 2 in Ca 3 Minimum Ci...

Page 13: ...1 116 1 099 Med 2 5 1 183 28 1 113 30 1 098 30 1 052 32 1 039 32 1 006 1 012 969 Med Lo 2 0 980 34 946 35 920 36 900 37 896 37 885 855 804 Low 1 5 778 43 762 44 738 45 746 45 738 45 717 696 678 High...

Page 14: ...49 26 1 116 1 116 1 099 Med 2 5 1 183 25 1 113 27 1 098 27 1 052 28 1 039 29 1 006 1 012 969 Med Lo 2 0 980 30 946 31 920 32 900 33 896 33 885 855 804 Low 1 5 778 38 762 39 738 40 746 40 738 40 717 69...

Page 15: ...0 120 100 130 140 150 100 90 80 70 60 50 40 30 20 10 OUTPUT BTU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULA...

Page 16: ...HERMOSTATAT0 7AMPS BLOWER PRIMARYLIMIT WH GR BK IGNITER SURFACE HOT PU RD 15PINPLUG C NO SWITCH PRESSURE BR SENSOR FLAME BK WH ROLLOUTLIMITS RAPIDFLASHES REVERSED115VACPOLARITY VERIFYGND SYSTEMLOCKOUT...

Page 17: ...e appropriate wiring diagram for the unit being serviced 0005 3M K4 K2 HI HEAT COOL PARK CIR NEU K5 GAS VALVE HIGH LIMIT AUX LIMIT PRESSURE SWITCH FLAME SENSOR PROBE IGNITOR FP IGN GND MV MLV PS HLO H...

Reviews: