Specifications
GMEC80
0403A*
GMEC80
0603A*
GMEC80
0603B*
GMEC80
0803B*
GMEC80
0804B*
GMEC80
0804C*
GMEC80
0805C*
GMEC80
0805D*
GMEC80
1004C*
GMEC80
1005C*
GMEC80
1205D*
Heating Capacity
High Fire Input (BTU/h)¹
40,000
60,000
60,000
80,000
80,000
80,000
80,000
80,000
100,000
100,000
120,000
High Fire Output (BTU/h)¹ :
Natural Gas
32,000
48,000
48,000
64,000
64,000
64,000
64,000
64,000
80,000
80,000
96,000
LP Gas
32,000
48,000
48,000
64,000
64,000
64,000
64,000
64,000
80,000
80,000
96,000
Low Fire Input (BTU/h)¹
28,000
42,000
42,000
56,000
56,000
56,000
56,000
56,000
70,000
70,000
84,000
Low Fire Output (BTU/h)¹ :
Natural Gas
22,400
33,600
33,600
44,800
44,800
44,800
44,800
44,800
56,000
56,000
67,200
LP Gas
22,400
33,600
33,600
44,800
44,800
44,800
44,800
44,800
56,000
56,000
67,200
AFUE²
80
80
80
80
80
80
80
80
80
80
80
Available AC @ 0.5” ESP
1.5 - 3.0
1.5 - 4.0
1.5 - 4.0
3.0 - 4.0
2.0 - 5.0
2.5 - 5.0
2.5 - 5.0
2.5 - 5.0
2.0 - 5.0
2.0 - 5.0
2.0 - 5.0
Temperature Rise Range (° F)
15-45/
15-45
20-50/
20-50
15-45/
15-45
30-60/
30-60
30-60/
30-60
25-55/
25-55
25-55/
25-55
20-50/
20-50
25-55/
25-55
20-50/
20-50
40-70/
40-70
Circulator Blower
Size (D x W)
10” x 6”
10” x 6”
10” x 8”
10" x 8"
10” x 10”
10" x 10"
10" x 10"
11" x 10"
10” x 10”
10” x 10”
11” x 10”
Horsepower - RPM
1/2
1/2
1/2
1/2
3/4
3/4
3/4
3/4
3/4
1
1
Speed
5
5
5
5
5
5
5
5
5
5
5
Vent Diameter¹
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
4”
No. of Burners
3
3
3
4
4
4
4
4
5
5
6
Electrical Data
Min. Circuit Ampacity
³
8.7
8.7
8.7
8.7
12.45
12.45
15.32
15.32
12.45
15.32
15.32
Max. Overcurrent Device (amps)
4
15
15
15
15
15
15
20
20
15
20
20
Ship Weight (lbs)
105
107
107
118
121
129
129
129
124
124
124
¹ Natural Gas BTU/h; for altitudes 0-4500’ above sea level, reduce input rating by 4% for each 1000’ above 4500’ altitude.
² DOE AFUE based upon Isolated Combustion System (ICS)
³ Minimum Circuit Ampacity = (1.25 x Circulator Blower Amps) + ID Blower amps. Wire size should be determined in accordance with National Electrical Codes. Extensive wire
runs will require larger wire sizes.
⁴
Maximum Overcurrent Protection Device refers to maximum recommended fuse or circuit breaker size. May use fuses or HACR-type circuit breakers of the same size as noted.
Notes
•
All furnaces are manufactured for use on 115 VAC, 60 Hz, single-phase electrical supply.
•
Gas Service Connection ½” FPT
•
Important: Size fuses and wires properly and make electrical connections in accordance with the National Electrical Code and/or all
existing local codes.
Downloaded from