PRODUCT DESIGN

4

DSX18 models are available in 3, 4 and 5 ton sizes and
use R-410A refrigerant. They are designed for 208/230 volt
single phase applications.

The condenser air is pulled through the condenser coil by a
direct drive propeller fan. This condenser air is then dis-
charged out of the top of the cabinet.

These units are designed for free air discharge, so no addi-
tional resistance like duct work shall be attached.

The suction and liquid line connections on present models
are of the sweat type for field piping with refrigerant type cop-
per. Front seating valves are factory installed to accept the
field run copper. The total refrigerant charge for a normal in-
stallation is factory installed in the condensing unit. DSX units
are charged for the matching evaporator coil and a 15 foot
refrigerant line set.

Systems should be properly sized by heat gain and loss
calculations made according to methods of the Air Condi-
tioning Contractors Association (ACCA) or equivalent.  It is
the contractors responsibility to ensure the system has ad-
equate capacity to heat or cool the conditioned space.

DSX18 models use the Copeland Scroll "Ultratech" Series
compressors which are specifically designed for R-410A re-
frigerant.  There are a number of design characteristics which
are different from the traditional reciprocating and/or scroll
compressors.

"Ultratech" Series scroll compressors with Copeland

®

ComfortAlert diagnostics will not have a discharge thermo-
stat, some of the early model scroll compressors required
discharge thermostats.

"Ultratech" Series scroll compressors will not have a dis-
charge thermostat. Some of the early model scroll compres-
sors required discharge thermostats. Due to their design Scroll
compressors are inherently more tolerant of small quantities
of liquid refrigerant.

NOTE:  Even though the compressor section of a Scroll com-
pressor is more tolerant of liquid refrigerant, continued
floodback or flooded start conditions may wash oil from the
bearing surfaces causing premature bearing failure.

"Ultratech" Series scroll compressors use "POE" or
polyolester oil  which is 

NOT

 compatible with mineral oil based

lubricants like 3GS.  "POE"  oil must be used if additional oil
is required.

WARNING

To avoid possible injury, explosion or death, practice
safe handling of refrigerants.

Operating pressures and amp draws may differ from stan-
dard reciprocating and/or scroll compressors.  This informa-
tion may be found in the "Cooling Performance Data" sec-
tion.

This unit is for outdoor installation only. Refer to minimum
figure for clearances from the sides of the unit to full walls
and other objects.

NOTE:

 This unit cannot be completely enclosed. At least

one side must be unrestricted.

These clearances will help avoid air recirculation. If installing
two or more units at the same location, allow at least 24
inches between units. If only one side is restricted (for ex-
ample, against the outside wall of a house), the unit may be
placed as close as 8" to that one wall.

DO 

NOT

 locate the unit:

* Directly under a vent termination for a gas appliance.

* Within 3 feet of a clothes drier vent

* Where the refreezing of defrost water would create

a hazard

* Where water may rise into the unit.

OK!

OK!

AA

AA

A

A

C

C

C

C

OK!

OK!

OK!

OK!

NOT

RECOMMENDED

AA

AA

AA

AA

AA

B

B

B

B

Model Type

A

B

C

AA

Residential

10"

10"

18"

20"

Light Commercial

12"

12"

18"

24"

Minimum Airflow Clearance

Model

Dimensions - W x D x H

DSX180361A*

35½ x 35½ x 38¼

DSX180481A*

35½ x 35½ x 38¼

DSX180601A*

35½ x 35½ x 38¼

Summary of Contents for DSX18

Page 1: ...ber information See models on page 3 TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU TECHNICAL MANUAL AL AL AL AL RT6114007r1 August 2009 This manual is to be used by qualified professiona...

Page 2: ...all or repair this unit without such background may result in product damage personal injury or death Goodman will not be responsible for any injury or property damage arising from improper service or...

Page 3: ...office WARNING WARNING Do not connect or use any device that is not design certified by Goodman for use with this unit Serious property damage personal injury reduced unit performance and or hazardou...

Page 4: ...model scroll compres sors required discharge thermostats Due to their design Scroll compressors are inherently more tolerant of small quantities of liquid refrigerant NOTE Even though the compressor s...

Page 5: ...0 262 0 Power Supply 208 230 60 1 208 230 60 1 208 230 60 1 Minimum Circuit Ampacity 1 23 7 29 3 34 8 Maximum Overcurrent Device 2 40 50 60 Electrical Conduit Size Power Supply Inches 1 2 or 3 4 1 2...

Page 6: ...2 25 9 28 0 30 1 24 6 25 3 27 4 29 4 24 0 24 7 26 7 28 7 22 8 23 4 25 4 27 2 21 1 21 7 23 5 25 2 S T 0 86 0 77 0 58 0 38 0 89 0 80 0 60 0 39 0 92 0 82 0 62 0 40 0 95 0 85 0 64 0 41 0 98 0 88 0 66 0 43...

Page 7: ...7 3 7 1 7 2 7 5 7 8 7 5 7 7 7 9 8 2 HI PR 206 221 225 230 233 250 254 259 265 285 289 295 302 324 329 336 326 350 355 363 386 415 421 430 LO PR 122 125 137 146 125 129 141 150 129 133 146 155 133 137...

Page 8: ...4 38 3 41 1 33 5 34 5 37 4 40 1 32 7 33 7 36 4 39 1 31 1 32 0 34 6 37 2 28 8 29 6 32 1 34 4 S T 0 86 0 77 0 59 0 38 0 90 0 80 0 61 0 39 0 92 0 82 0 62 0 40 0 95 0 85 0 64 0 41 0 98 0 88 0 67 0 43 0 9...

Page 9: ...6 9 8 10 1 10 5 10 2 10 4 10 8 11 2 HI PR 212 227 231 236 239 257 261 267 272 292 297 303 310 333 338 345 348 375 380 388 390 420 426 435 LO PR 119 123 134 143 123 126 138 147 127 131 143 152 130 134...

Page 10: ...6 9 50 3 41 1 42 3 45 8 49 1 40 1 41 3 44 7 47 9 38 1 39 2 42 4 45 5 35 3 36 3 39 3 42 2 S T 0 83 0 74 0 56 0 36 0 86 0 77 0 58 0 37 0 88 0 79 0 59 0 38 0 91 0 81 0 61 0 39 0 94 0 84 0 64 0 41 0 95 0...

Page 11: ...7 14 0 14 5 15 1 14 5 14 8 15 4 16 0 HI PR 222 238 242 247 243 262 265 271 285 306 311 318 325 349 354 362 365 393 398 407 422 454 460 470 LO PR 116 119 130 139 119 123 134 143 123 127 138 147 126 130...

Page 12: ...43 6 35 6 36 7 39 7 42 6 34 7 35 8 38 7 41 5 33 0 34 0 36 8 39 5 30 6 31 5 34 1 36 6 S T 0 84 0 75 0 57 0 37 0 87 0 78 0 59 0 38 0 89 0 80 0 60 0 39 0 92 0 82 0 62 0 40 0 95 0 85 0 65 0 42 0 96 0 86...

Page 13: ...2 10 9 11 2 11 5 12 0 11 6 11 8 12 3 12 7 HI PR 216 232 235 241 244 262 266 272 278 298 303 309 316 340 345 352 341 367 372 380 405 435 441 451 LO PR 116 120 131 139 120 123 135 143 124 127 139 148 12...

Page 14: ...3 53 4 57 3 46 8 48 1 52 1 55 9 45 6 47 0 50 8 54 6 43 3 44 6 48 3 51 8 40 1 41 3 44 7 48 0 S T 0 87 0 78 0 59 0 38 0 90 0 81 0 61 0 39 0 92 0 83 0 63 0 40 0 95 0 85 0 65 0 42 0 99 0 89 0 67 0 43 1 00...

Page 15: ...0 13 6 13 9 14 4 15 0 14 4 14 8 15 3 15 9 HI PR 223 240 243 249 252 271 275 281 287 308 313 320 327 351 356 364 367 395 401 409 411 442 449 459 LO PR 118 122 133 142 122 125 137 146 126 130 142 151 12...

Page 16: ...8 64 8 69 5 56 7 58 4 63 2 67 8 55 3 57 0 61 7 66 2 52 6 54 1 58 6 62 9 48 7 50 1 54 3 58 3 S T 0 83 0 75 0 56 0 36 0 86 0 77 0 58 0 38 0 89 0 79 0 60 0 39 0 91 0 82 0 62 0 40 0 95 0 85 0 64 0 41 0 96...

Page 17: ...0 20 2 20 8 21 5 22 3 21 4 22 0 22 7 23 6 HI PR 236 254 258 263 259 279 283 289 304 327 331 339 346 372 377 386 389 419 424 434 450 484 490 501 LO PR 113 116 127 135 116 120 131 139 120 124 135 144 12...

Page 18: ...9 623 2 268 90 35 717 26 634 9 083 2 333 95 35 276 26 722 8 554 2 397 100 34 394 26 548 7 846 2 452 105 33 512 26 348 7 164 2 506 110 32 278 25 483 6 794 2 554 115 31 043 24 611 6 432 2 601 95 32 688...

Page 19: ...12 043 2 372 80 38 874 27 318 11 556 2 453 85 38 406 27 327 11 078 2 534 90 37 937 27 429 10 508 2 605 95 37 469 27 520 9 949 2 677 100 36 532 27 340 9 192 2 737 105 35 596 27 135 8 461 2 798 110 34 2...

Page 20: ...T CODE C CONTACTOR CADM COMFORT ALERT MODULE CM OUTDOOR FAN MOTOR COMP COMPRESSOR CS COMPRESSOR SOLENOID HPS HIGH PRESSURE SWITCH IO INTERNAL OVERLOAD LPS LOW PRESSURE SWITCH LVJB LOW VOLTAGE JUNCTION...

Reviews: