32 www.goodmanmfg.com
SS-CPG36-72
w
irinG
d
iaGram
—
CPG060*3d (t
hree
-P
hase
, d
ireCt
d
rive
)
Wiring
is
subject
to
change.
Al
wa
ys
refer
to
the
wiring
diag
ram
or
the
unit
for
the
most
up-to-da
te
wiring
.
⚠
w
arnin
G
High
Voltage:
Disconnect
all
power
bef
or
e
ser
vicing
or
installing
this
unit.
Multiple
power
sour
ces
ma
y
be
pr
esent.
F
ailur
e
to
do
so
ma
y
cause
pr
operty
damage,
per
sonal
injur
y,
or
dea
th.
⚡
IIC
FC
RD
RD
FS
BR
NOTE 6
SEE
COOL
DI
L1
HEA
T
UN
US
ED
L2
BL
WH
RD
PU
WH
GR
BL
BL
BL
GAS VALVE
MV
2
1
4
5
YL
BL
W. R.
GAS VALVE
PU
(ALT.) HONEYW ELL
3
6
YL
BL
YL
PU
WH
BR
R
G
Y1
W
OR
RD
TO THERMOSTAT
C
MV
FS
IGN
VM
BL
BL
YL
WH
BR
BL
BK
GV
GV
SMOKE/FIRE
DETECTOR
REPLACE
JUMPER
TB1
PU
BL
YL
LPS
HPS
YL/PK
BL/PK
BL
RD
Y2
YL
BR
W2
BR
NOTE 8
SEE
WH
GND
YL
BK
BK
POWER SUPPLY
240/3/60
RD
YL
RD
WH
BL
BRE
AK
FO
R
TW
O
ST
AGE
T2
COMP
RES
SOR
RD
L2
C
T2
T3
L3
L1
T1
BK
BK
PU
YL
T3 T2 T1
COMP
BK
PU
CM
BR
PK
VMR
C2
2
OR
SP
EED
-UP
MO
UNT
T1
P2
RE
QUIRED
SCR
EW
P3
13
5
12
0
15
0
FU
SE3
AMP
MAX
F1
WH
YL
RD
11
8
12
9
7
10
4
2
5
6
3
1
RD
YL
YL
PU
RD
BL
P1
EC
ON
RD
ALS
GR
PS
RS
PLF
YL
YL
NOTE 4
BR
WH
PU
PU
BK
FOR
TB1
YL
GR
TB1
WH
YL
NOTE 3 & 7
WH
YL
BR
PU
OR
1
5
S1
S2
3
2
1
RD
RD
LS
208
TR
BL
24V
C
BL
PK
240
BK
RD
BK
BL
NOTE 2
RD
BL
G
T4
EM
L
T3
T2
T1
C
GR
RD
BK
N
T5
GR
WH
YL
BR
PU
OR
3
1
2
OR
OR
SEE NOTE 5
230/3/60
0140L00980
REV B
COOLING SPEED (YELLOW WIRE)
USE
NEC CLASS 2 WIRE.
5. USE COPPER CONDUCTORS ONLY.
6. L1 AND L2 ON ICC CONTROL IS 24V INPUT.
7. SPEED TAP TERMINATIONS SHOWN ON
DIAGRAM ARE REPRESENTATIVE, BUT
ACTUAL FACTORY SETTINGS MAY BE
DIFFERENT BASED ON THE HEATING VALUE
OF THE UNIT.
3. FOR DIFFERENT THAN FACTOR Y SPEED TAP.
CHANGE COOLING SPEED AT MOTOR T3 AND
T4 TERMINALS. CHANGE HEATING SPEED AT
MOTOR T1. T2, AND T5 TERMINALS
4. ACCESSORY ECONOMIZER PLUG ADJACENT
TO BLOWER HOUSING IN RETURN AIR
COMPARTMENT. REMOVE MALE PLUG AND
ATTACH FEMALE PLUG TO ECONOMIZER
ACCESSORY.
1. REPLACEMENT WIRE MUST BE THE SAME
SIZE AND TYPE OF INSULATION AS ORIGINAL.
(USE COPPER CONDUCTOR ONLY).
AUXILIAR Y LIMIT SWITCH
FEMALE PLUG/CONNECTOR
INTEGRATED IGNITION CONTROL
LS
4
INSTALLER/SERVICEMAN
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO
STATUS LIGHT
3 BLINKS
6 BLINKS
2 BLINKS
4 BLINKS
5 BLINKS
OFF
ON
1 BLINK
OPEN AUX. LIMIT
FALSE FLAME SENSED
OUTPUT DELAY
OPEN LIMIT SWITCH
COMPRESSOR
WITHOUT INDUCER ON
PRESSURE SWITCH CLOSED
PRESSURE SWITCH
SWITCH
OPEN
OPEN ROLLOUT
SWITCH
IGNITION FAILURE
NORMAL OPERATION
NO POWER OR
INTERNAL CONTROL
EQUIP. STATUS
OR
OR
FAULT
TO THERMOSTAT
TERMINAL BLOCK
G
R
5
7
9
ECON
IIC
Y1
W
Y2
3
6
12
10
8
11
RS
ALS
PS
BAD SWITCH
AUX. LIMIT OPEN
ANTI-CYCLE TIMER
MAIN LIMIT OPEN
STICKING GAS VALVE
BAD SWITCH
3 MIN. COMP.
PRESSURE SWITCH
PRESSURE SWITCH
CHECK
CHECK
GAS PRESSURE
FLAME ROLLOUT
FLAME SENSOR
GAS VALVE
CHECK FUSE ON CONTROL
CHECK INPUT POWER
REPLACE CONTROL
GAS FLOW
CHECK
-
PLF
C
NOTE 4
4
3
2
1
5
6
GV
C
T3 - LOW SPEED
T4 - HIGH SPEED
IGN
NOTE 6
L1
F
D1
FS
TR
L1
240/3/60
SUPPLY VOLTAGE
CM
CONDENSER MOTOR
NOTE 6
FS
IIC
L2
VM
1
VMR
L3
LS
LIMIT SWITCH
VENT MOTOR RELAY
VENT MOTOR
PRESSURE SWITCH
TERMINAL BLOCK (24V SIGNAL)
ROLLOUT SWITCH
VMR
VM
PS
PLF
TB1
RS
NOTES
FAN CAPACITOR
CONTACTOR
GAS VALVE
IGNITOR
EQUIPMENT GROUND
FLAME SENSOR
EVAPORATOR MOTOR
FC
FUSE
F
C
GV
FS
GND
IGN
IIC
EM
L2
L3
COMPRESSOR
COMPONENT LEGEND
COMP
ALS
HEATING SPEED (WHITE WIRE)
T5 - HIGH SPEED (140)
T2 - MED. SPEED
T1 - LOW SPEED (070)
TB1
TB1
TR
TRANSFORMER
EM
L
3
1
2
N
SEE NOTE 2
L2
C
CM
T3
COMP
T3
T2
FC
L1
C
T1
T1
C
T2
230/3/60
0140L00980
REV B
HPS
LPS
LPS
LOW PRESSURE SWITCH
HPS
HIGH PRESSURE SWITCH
VMR
TB1
5
4
EM
1
3
2
C
C
H
NOTE 3
HIGH VOLTAGE
FACTORY WIRING
OPTIONAL
HIGH VOLTAGE
LOW VOLTAGE
FIELD WIRING
LINE VOLTAGE
LOW VOLTAGE
BL
RD
Y1
Y/Y2
YL
W
Y/Y2
BL
G
R
W
NO ECONOMIZER
G
YL
RD
Y/Y2
Y1
PK
WH
W
R
RD
WH
GR
C
R
YL
GR
Y1
G
WH
WITH ECONOMIZER OPTION
C
GR
THERMOSTAT
FIELD WIRING
BL
C
2 STAGE COOLING
TB1
G
R
W
Y
C
TB1
TB1
Y
W
R
G
C
W
Y2
G
R
C
Y1
STAT
STAT
STAT
BL/PK
BLUE WITH PINK STRIP
YL/PK
YELLOW WITH PINK STRIP
GR
GREEN
WIRE CODE
BL
BLUE
PU
PURPLE
PK
PINK
WH
WHITE
BK
BLACK
RD
RED
BR
BROWN
OR
ORANGE
YL
YELLOW
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER
CURRENT PROTECTION
8. FOR LOW STAGE OPERATI ON ONLY, REMOVE
WHITE JUMPER. FOR 2 STAGE OPERAT ION,
REMOVE JUMPER AND CONNECT W2 TO W2
ON THERMOSTAT.
W2
3
2. FOR 208 VOLT TRANSFORMER OPERATI ON
MOVE BLACK WIRES FROM TERMINAL
3
TO
TERMINAL
2
ON TRANSFORMER.