p
rodUCt
s
peCifiCations
p
rodUCt
s
peCifiCations
4 www.goodmanmfg.com
SS-CPC36-72
p
rodUCt
s
peCifiCations
— CpC048
CPC048
XXX1DXXXB
CPC048
XXX3DXXXB
CPC048
XXX3BXXXB
CPC048
XXX4BXXXB
CPC048
XXX7BXXXB
Cooling Capacity
Total BTU/h
45,500
45,500
45,500
45,500
45,500
Sensible BTU/h
35,000
35,000
35,000
35,000
35,000
SEER / EER
13.0 / 11.3
13.0 / 11.3
13.0 / 11.3
13.0 / 11.3
13.0 / 11.3
Decibels
78
78
78
78
78
ARI Reference #s
4385053
4385054
4385054
4385055
4397605
Evaporator Motor / Coil
Motor Type
Direct Drive
Direct Drive
Belt Drive
Belt Drive
Belt Drive
Indoor Nominal CFM
1,600
1,600
1,600
1,600
1,600
Motor Speed Tap (Cooling)
Medium
Medium
--
--
--
Indoor Motor FLA (Cooling)
2.87
2.87
3.8
1.9
2.3
Horsepower - RPM
½ -1,000
½ -1,000
1.0 - 1,725
1.0 - 1,725
1.5 - 1,725
Piston Size (Cooling)
0.076
0.076
0.076
0.076
0.076
Filter Size (Qty)
(4) 14" x 20" x 2"
(4) 14" x 20" x 2"
(4) 14" x 20" x 2"
(4) 14" x 20" x 2"
(4) 14" x 20" x 2"
Drain Size (NPT)
¾"
¾"
¾"
¾"
¾"
R-410A Refrigerant Charge (oz.)
103
103
103
103
105
Evaporator Coil Face Area (ft²)
7.0
7.0
7.0
7.0
7.0
Rows Deep / Fins per Inch
4 / 16
4 / 16
4 / 16
4 / 16
4 / 16
Belt Drive Evap Fan Data
# of Wheels (D x W)
---
---
1 (11" x 10")
1 (11" x 10")
1 (11" x 10")
Motor Sheave
---
---
VL44 X 5/8
VL44 X 5/8
VL44 X 5/8
Blower Sheave / Belt
---
---
AK66 x 1 / AX55
AK66 X 1
AK66 X 1
Condenser Fan / Coil
Quantity of Condenser Fan Motors
1
1
1
1
1
Horsepower - RPM
¼ - 1,090
¼ - 1,090
¼ - 1,090
¼ - 1,090
¼ - 1,075
Fan Diameter / # Fan Blades
22 / 4
22 / 4
22 / 4
22 / 4
22 / 4
Outdoor Nominal CFM
3,800
3,800
3,800
3,800
3,800
Face Area (ft²)
17
17
17
17
17
Rows Deep / Fins per Inch
1 / 24
1 / 24
1 / 24
1 / 24
1 / 24
Compressor
Quantity / Stage
1 / Single
1 / Single
1 / Single
1 / Single
1 / Single
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Compressor RLA / LRA
20 / 109
13.1/ 83.1
13.1/ 83.1
6.1/ 41
4.4/ 33
Electrical Data
Voltage-Phase-Frequency
208/230-1-60
208/230-3-60
208/230-3-60
460-3-60
575-3-60
Outdoor Fan FLA
1.40
1.40
1.40
0.80
0.60
Total Unit Amps
24.1
17.4
18.3
8.8
7.3
Min. Circuit Ampacity¹
29
21
22
10
8
Max. Overcurrent Protection (amps)²
45
30
30
15
15
Power Supply Conduit Hole
1.125"
1.125"
1.125"
1.125"
1.125"
Low-Voltage Conduit Hole
½"
½"
½"
½"
½"
Operating Weight (lbs)
535
535
535
535
535
Ship Weight (lbs)
560
560
560
560
560
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.