background image

7

For the 7-1/2 ton unit starting charge should be 15 lb of R-22
and 18 lbs for the 10 ton unit. The length of line set, indoor unit
airflow, condensing unit location and number of tubing fittings
will have an impact on final unit charge amount. Turn the elec-
trical power on, and let the system run. Wait for the refrigerant
pressures to stabilize.

Charge Verification

REFRIGERANT UNDER PRESSURE!

 

• Do not overcharge system with refrigerant.
• Do not operate unit in a vacuum or at negative pres-
  sure.
Failure to follow proper procedures may cause 
property damage, personal injury or death.

WARNING

Use refrigerant certified to AHRI standards. Use of used 
refrigerant may cause compressor damage that is not 
covered under warranty.  Most portable machines cannot 
clean used refrigerant to meet AHRI standards.

CAUTION

NOTICE

Violation of EPA regulations may result in fines or other
penalties.

Operating the compressor with the suction valve closed 
may cause serious compressor damage.

CAUTION

Final Charge Adjustment

The outdoor temperature must be 60°F or higher. Set the room
thermostat to COOL, fan switch to AUTO, and set the tem-
perature control well below room temperature.

After system has stabilized per startup instructions, check
subcooling and superheat as detailed in the following section.

Expansion Valve System

1. Purge gauge lines. Connect service gauge manifold

tobase-valve service ports. Run system at least 10 min-
utes to allow pressure to stabilize.

2. Temporarily install thermometer on liquid (small) line near

liquid line service valve with adequate contact and insu-
late for best possible reading.

3. Check subcooling and superheat. Systems with TXV ap-

plication should have a subcooling of 11 ± 2 ºF and su-
perheat of 9 ± 1 ºF.

a.

If subcooling and superheat are low, 

adjust

 TXV

to 9 ± 1 ºF superheat, then check subcooling.

NOTE:

 To adjust superheat, turn the valve stem clock-

wise to increase and counter clockwise to decrease.

b.

If subcooling is low and superheat is high, 

add

charge to raise subcooling to 11 ± 2ºF then check
superheat.

c.

If subcooling and superheat are high, 

adjust

 TXV

valve to 9 ± 1 ºF superheat, then check subcooling.

d.

If subcooling is high and superheat is low, 

adjust

TXV valve to 9 ± 1 ºF superheat and 

remove 

charge

to lower the subcooling to 11 ± 2ºF.

NOTE:

 Do 

NOT 

adjust the charge based on suction pres-

sure unless there is a gross undercharge.

4. Disconnect manifold set, installation is complete.

Subcooling Formula = Sat. Liquid Temp. - Liquid Line Temp.

NOTE

: Check the Schrader ports for leaks and tighten valve

cores if necessary. Install caps finger-tight.

NOTE:  

Subsequent opening and replace of the cap will require

only 1/2 to 1 hex flat. See the table below for the torque required
for an effective seal on the valve bonnet (1/6 turn past finger
tight.

TUBING SIZE

TORQUE

(ft-lbs)

5/8

14

1 3/8

16

After closing the valve bonnet, perform a final refrigerant leak
test on the valves and sweat connections.  Return the room
thermostat to the desired settings.

Troubleshooting

Qualified Installer/Servicer Only

When troubleshooting, the first step should always be to check
for clean coils, clean filter(s), and proper airflow. Indoor airflow
should be 375 to 425 CFM per ton of cooling based on the size
of the outdoor unit. The most common way of establishing
indoor airflow is heating temperature rise. Indoor airflow will
then be (Heating output of equipment) / (1.1 x temp. rise). In
other cases, measurement of external static pressure is help-
ful. For details, see the Installation Instructions for your indoor
unit.

Summary of Contents for CONDENSING AC UNIT

Page 1: ...s no responsibility for equip ment installed in violation of any codes or regulations The United States Environmental Protection Agency EPA has issued various regulations regarding the introduc tion and disposal of refrigerants Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines Should you have any questions please contact the local offi...

Page 2: ...rant used Store cylinders in a cool dry place Never use a cy linder as a platform or a roller Another important consideration in selecting a location for the unit s is the angle to obstructions Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clearance Corner installations are strongly discouraged 12 12 60 24 Thi...

Page 3: ... type hanger Keep both lines separate and always insulate the suction line Suct Liq Suct Liq Suct Liq 7 1 2 1 1 8 5 8 1 3 8 5 8 1 3 8 5 8 10 1 3 8 5 8 1 5 8 5 8 1 5 8 5 8 Cond Unit Tons REFRIGERANT LINE LENGTH ft 0 24 25 49 50 74 Line Diameter In OD Full rating line size Lines greater than 74 feet in length or vertical elevation changes more than 50 feet refer to the Remote Cooling Service Manual ...

Page 4: ...isk of fire or explosion never use oxygen high pressure air or flammable gases for leak testing of a refrigeration system WARNING To avoid possible explosion the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve The pressure relief valve must be set to open at no more than 150 psig WARNING Pressure test the system using dry nitrogen and soapy water to lo...

Page 5: ... NOTICE Units with reciprocating compressors and non bleed TXV s require a Hard Start Kit This unit is designed for three phase operation DO NOT OP ERATE ON A SINGLE PHASE POWER SUPPLY Measure the power supply to the unit The supply voltage must be in agreement with the unit rating plate power requirements RATED VOLTAGE MINIMUM SUPPLY VOLTAGE MAXIMUM SUPPLY VOLTAGE 208 230V 197 253 460V 414 506 Th...

Page 6: ...e Compressor Rotation Use care when handling scroll compressors Dome temp eratures could be hot CAUTION Three phase scrolls are power phase dependent and can com press in more than one direction Verify proper rotation for three phase compressors by ensuring the suction pressure drops and discharge pressure rises when the compressor is energized NOTE When operated in re verse a three phase scroll c...

Page 7: ...p plication should have a subcooling of 11 2 ºF and su perheat of 9 1 ºF a If subcooling and superheat are low adjust TXV to 9 1 ºF superheat then check subcooling NOTE To adjust superheat turn the valve stem clock wise to increase and counter clockwise to decrease b If subcooling is low and superheat is high add charge to raise subcooling to 11 2ºF then check superheat c If subcooling and superhe...

Page 8: ...oil Clean or replace filters 7 Flash gas in the liquid line 7 Excessive liquid line drop Check liquid line size 8 Quantity of air through evaporator not adequate 8 Increase the blower speed 1 Expansion valve stuck open 1 Correct valve action or replace the valve 2 Expansion valve bulb not in contact with 2 Fasten bulb securely to suction line suction line 3 Suction and or discharge valve leaking o...

Reviews: