background image

3

Electrical Supply Wire and MOP

HIGH VOLTAGE
To avoid the risk of fire or equipment
damage, use only copper conductors.
Disconnect ALL power before servicing or
installing this unit.  Multiple power sources may
be present.  The electrical power to this unit
MUST be in the OFF position and all power supplies
disconnected.  Failure to do so may cause property
damage, personal injury or death.

The unit MUST have an uninterrupted, unbroken
electrical ground to minimize the possibility of
personal injury if an electrical fault should occur. The
electrical ground circuit may consist of an appropri-
ately sized electrical wire connecting the ground lug
in the unit and control box wire to the building’s
electrical service panel. Other methods of grounding
are permitted if performed in accordance with the
“National Electric Code” (NEC)/”American National
Standards Institute” (ANSI)/”National Fire Protection
Association” (NFPA) 70 and local/state codes. In
Canada, electrical grounding is to be in accordance
with the Canadian Electric Code CSA C22.1. Failure
to observe this warning can result in electrical shock
that can cause personal injury or death.

Inspection of the Building Electrical Service

This unit is designed for single-phase electrical supply.  DO
NOT OPERATE ON A THREE-PHASE POWER SUPPLY.
Measure the power supply to the unit.  The supply voltage

must

 be in agreement with the unit nameplate power require-

ments and within the range shown in 

Table 1

.

Nominal Input

Minimum Voltage

Maximum Voltage

208/230

187

253

Table 1

Wire Sizing

Wire size is important to the operation of your equipment.  Use
the following check list when selecting the appropriate wire
size for your unit.

Wire size must carry the Minimum Circuit Ampacity
(MCA).

Wire size allows for no more than a 2% voltage drop
from the building breaker/fuse panel to the unit.

Refer to the latest edition of the National Electric Code or in
Canada the Canadian Electric Code when determining the cor-
rect wire size.  The following table shows the current carrying
capabilities for copper conductors rated at 75

o

C with a 2%

voltage drop.  Use  

Table 2

  to determine the voltage drop per

foot of various conductors.

10

15

20

25

30

35

40

45

14

75

50

37

NR

NR

NR

NR

NR

12

118

79

59

47

NR

NR

NR

NR

10

188

125

95

75

63

54

NR

NR

8

301

201

150

120

100

86

75

68

6

471

314

235

188

157

134

118

110

*Based on NEC 1996

Maximum Allowable Length in Feet

to Limit Voltage Drop to 2%*

Minimum Circuit Ampacity (MCA) 

Wire Size

(AWG)

Table 2

Maximum Overcurrent Protection (MOP)

Every installation must include an NEC (USA) or CEC (Canada)
approved overcurrent protection device.  Also, check with local
or state codes for any special regional requirements.

Protection can be in the form of fusing or HACR style circuit
breakers.  The Series and Rating Plate can be used as a guide
for selecting the MAXIMUM overcurrent device.

NOTE:

Fuses or circuit breakers are to be sized larger than

the equipment MCA but not to exceed the MOP.

IMPORTANT NOTE: 

Torch heat required to braze tubes of

various sizes is proportional to the size of the tube. Tubes of
smaller size require less heat to bring the tube to brazing
temperature before adding brazing alloy. Applying too much
heat to any tube can melt the tube. Service personnel must use
the appropriate heat level for the size of the tube being brazed.

NOTE: 

The use of a heat shield when brazing is recommended

to avoid burning the serial plate or the finish on the unit. Heat
trap or wet rags should be used to protect heat sensitive
components such as service valves and TXV valves.

Electrical Connections – Supply Voltage

USE COPPER CONDUCTORS ONLY.

A knockout is provided on the air handler top panel or side to
allow for the entry of the supply voltage conductors. If the knock-
outs on the cabinet sides are used for electrical conduit, an
adapter ring must be used in order to meet UL1995 safety
requirements.  An NEC or CEC approved strain relief is to be
used at this entry point.  The wire is to be sized in accordance
with the “Electrical Wire and MOP” section of this manual.
Some areas require the supply wire to be enclosed in conduit.
Consult your local codes.

Summary of Contents for AWUF18

Page 1: ...operating in any mode CO can cause serious illness including permanent brain damage or death B10259 216 VERTICAL MOUNT AIR HANDLERS INSTALLATION INSTRUCTIONS 2005 2009 Goodman Manufacturing Company L...

Page 2: ...located in this same section Before using this manual check the serial plate for proper model identification The installation and servicing of this equipment must be per formed by qualified experienc...

Page 3: ...ing the cor rect wire size The following table shows the current carrying capabilities for copper conductors rated at 75o C with a 2 voltage drop Use Table 2 to determine the voltage drop per foot of...

Page 4: ...piston See piston kit chart in instructions 5 Unsweat the cap on the suction line 6 Slide the 13 16 flare nut over the tailpiece 7 Braze tailpiece to the lineset liquid tube 8 Insert the suction line...

Page 5: ...M OF THE UNIT 3 4 NPT FEMALE CONNECTION NOTE HAND TIGHTEN ONLY SUCTION LINE FRONT ACCESS PANEL SMALL CHASSIS REMOVABLE SERVICE DOOR LIQUID LINE LARGE CHASSIS 2 5 3 0 TON SMALL CHASSIS 1 5 2 0 TON A 36...

Page 6: ...etting is 0 2 NOTE Connect appropriate speed tap Pink Purple Yellow to T1 Refer to table below for speed tap selection WIRE COLOR BTUH NOMINAL CFM PURPLE 18 000 600 PINK 24 000 800 YELLOW 30 000 950 W...

Page 7: ...T1 645 615 550 500 445 T5 1090 1065 1040 1015 985 T4 1005 975 945 920 890 T3 840 795 785 745 700 T2 645 615 550 500 445 T1 645 615 550 500 445 High 1280 1190 1110 1010 930 Low 1170 1100 1030 950 890 H...

Page 8: ...8 THISPAGELEFTINTENTIONALLYBLANK 2005 2009 Goodman Manufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com or www amana hac com...

Reviews: