Goodman AVPTC24B14 series Installation & Operating Instructions Manual Download Page 20

20

maximum airflow capability. If the thermostat provides four continuous fan speeds then a 100% airflow option is added. During
continuous fan operation, the thermostat sends a fan request along with the continuous fan demand to the air handler. The
air handler, in turn, sends the demand to the ECM motor. The ECM motor delivers the requested continuous fan airflow.

20.2 CTK0* Thermostat Wiring

NOTE:

Refer to section Electrical Connections for 208/230 volt line connections to the air handler

.

NOTE:

A removable plug connector is provided with the control to make thermostat wire connections.  This plug may be

removed, wire connections made to the plug, and replaced.  

It is 

STRONGLY

 recommended that you do not connect

multiple wires into a single terminal.  Wire nuts are recommended to ensure one wire is used for each terminal.

Failure to do so may result in intermittent operation.

Typical 18 AWG thermostat wire may be used to wire the system components.  One hundred (100) feet is the maximum
length of wire between indoor unit and outdoor unit, or between indoor unit and thermostat.

20.3 Four-Wire Indoor and Outdoor Wiring

Typical wiring will consist of four wires between the indoor unit and
outdoor unit and between the indoor unit and thermostat.  The required
wires are: (a) data lines, 1 and 2; (b) thermostat “R” (24 VAC hot) and
“C” (24 VAC common).

20.4 Two-Wire Outdoor, Four-Wire Indoor Wiring

Two wires only may be utilized between the indoor and out-
door units.  For this wiring scheme, only the data lines, 1 and
2, are required between the indoor and outdoor units.  A
40VA, 208/230 VAC to 24 VAC transformer must be installed
in the outdoor unit to provide 24 VAC power to the outdoor
unit’s electronic control.  See kit instructions for mounting and
wiring instructions.  Four wires are required between the in-
door unit and thermostat.

20.5 ComfortNet™ System Advanced Features

The ComfortNet system permits access to additional system information, advanced set-up features, and advanced diagnos-
tic/troubleshooting features.  These advanced features are organized into a menu structure.  See the AIR HANDLER AD-
VANCED FEATURES MENU section for layout of menu shortcuts.

20.6 Diagnostics

Accessing the air handler’s diagnostics menu provides ready access to the last six faults detected by the air handler.  Faults
are stored most recent to least recent.  Any consecutively repeated fault is stored a maximum of three times.  Example: A
clogged return air filter causes the air handler’s motor to repeatedly enter a limiting condition. The control will only store this
fault the first three 

consecutive

 times the fault occurs.

NOTE:

 It is highly recommended that the fault history be cleared after performing maintenance or servicing the air handler

.

20.7 Network Troubleshooting

The ComfortNet system is a fully communicating system, and thus, constitutes a network.  Occasionally the need to trouble-
shoot the network may arise.  The integrated air handler control has some on-board tools that may be used to troubleshoot
the network.  These tools are: red communications LED, green receive (Rx) LED, and learn button.  Refer to the 

Communi-

cations Troubleshooting Chart

 at the end of this manual for error codes, possible causes and corrective actions

Red communications LED – Indicates the status of the network.  The table below indicates the LED status and the
corresponding potential problem.

1

2

R

C

1

2

R

C

CTK0*
Thermostat

CT™ Compatible
Air Handler Blower
Integrated Control Module

CT™ Compatible AC/HP
Integrated Control Module

1

2

R C

System Wiring Using Four-Wires

Figure 33

1

2

R C

1

2

R C

CTK0*
Thermostat

CT™ Compatible
Air Handler Blower
Integrated Control 
Module

CT™ Compatible
AC/HP Integrated
Control Module

40VA Transformer

208/230 VAC

24 VAC

1

2

R C

System Wiring using Two-Wires between Air Handler and AC/

HP and Four-Wires between Air Handler and Thermostat

Figure 24

Summary of Contents for AVPTC24B14 series

Page 1: ...c Heat 9 12 Electrical and Control Wiring 10 13 Achieving 2 Low Leakage Rate 11 14 24 Volt Wiring 11 15 Auxiliary Alarm Switch 13 16 AVPTC Motor Orientation 13 17 Circulator Blower 14 18 Heat Kit Sele...

Page 2: ...if performed in accordance with the National Electric Code NEC American National Standards Institute ANSI National Fire Protection Association NFPA 70 and local state codes In Canada electrical ground...

Page 3: ...e any questions please contact the local office of the EPA and or refer to EPA s website www epa gov 4 Replacement Parts When reporting shortages or damages or ordering repair parts give the complete...

Page 4: ...ets may now be re moved The bottom left drain connection is the primary drain for this application and condensate drain line must be attached to this drain connection The top connection of the three d...

Page 5: ...RESULT IN BRAZE JOINT DAMAGE AND LEAKS 3 Removal of the center support is required on units with 21 wide cabinet Remove and retain the two 2 screws that secure the center support to the cabinet Remov...

Page 6: ...nel Thumb Screw EXTERNAL PART TERMINOLOGY Figure 7 Downflow Bracket Center Support Filter Bracket Control Deck Upper Tie Plate Filter Access Panel INTERNAL PART TERMINOLOGY Figure 6 Coil Slides on the...

Page 7: ...ags must be used to protect heat sensitive components such as service valves and TXV valves sensing bulb 7 3 Tubing Connections for TXV Models TXV models come with factory installed TXV with the bulb...

Page 8: ...ondensate from draining and if connected to a sewer line to pre vent sewer gases from being drawn into the airstream during blower operation Field experience has shown condensate drain traps with an o...

Page 9: ...ured Airflow VC Voltage Correction NOTE The Temperature Rise Tables can also be used to estimate the air handler airflow delivery When using these tables for this purpose set the room thermostat to ma...

Page 10: ...d overcurrent protection device Also check with local or state codes for any special regional requirements Protection can be in the form of fusing or HACR style circuit breakers The Series and Rating...

Page 11: ...access panels and between the coil access and filter access panels Ensure upon installation that the plastic breaker cover is sitting flush on the blower access panel and all access panels are flush w...

Page 12: ...t be normally closed and open when the base pan s water level in the evaporator coil reaches a particular level The control will respond by turning off the outdoor compressor and Air Handler Integrate...

Page 13: ...wn in the AVPTC Mo tor Orientation figure below Be sure motor is oriented with the female connections on the casing down If the motor is not oriented with the connections down water could collect in t...

Page 14: ...low closest to 1000 CFM A cooling airflow of 1000 CFM can be attained by setting the cooling speed to C and the adjustment to 0 no adjustment 4 Locate the blower speed selection DIP switches on the in...

Page 15: ...airflow Thus the electric heater airflow is adjusted by the same amount This does not apply to sys tems setup with a communicating thermostat See Set Up section in the AIR HANDLER ADVANCED FEATURES ME...

Page 16: ...ler the control and the person at the same electrostatic potential these steps will help avoid exposing the integrated control module to electrostatic discharge This procedure is applicable to both in...

Page 17: ...Select model and installed electric heater size Set dip switches S9 S10 and S11 to the appropriate ON OFF positions 3 If airflow adjustment is required set Trim Enable Switch to S8 ON OFF 0 Trim and...

Page 18: ...18 THIS PAGE INTENTIONALL LEFT BLANK...

Page 19: ...the indoor unit This two way digital communications between the thermostat and subsystems indoor outdoor unit and between subsystems is the key to unlocking the benefits and features of the ComfortNet...

Page 20: ...5 ComfortNet System Advanced Features The ComfortNet system permits access to additional system information advanced set up features and advanced diagnos tic troubleshooting features These advanced f...

Page 21: ...d trapped and pitched to allow for drainage Low voltage wiring is connected Auxiliary drain is installed when necessary and pitched to allow for drainage Drain pan and drain tubing has been leak check...

Page 22: ...stalled as a legacy traditional system Check communications wiring data 1 data 2 wires Check wire connections at terminal block Verify air handler installation type legacy traditional or communicating...

Page 23: ...ES Selecting YES clears the fault history NOTE Consecutively repeated faults are shown a maximum of 3 times Submenu Item Model Number MOD NUM Displays the modular blower model number Serial Number SER...

Page 24: ...ed in shared data set HTR TOO SMALL EC x Heater kit selected via dipswitches is too small for heater kits in shared data set x Verify electric heat dipswitch settings x Verify the installed electric h...

Page 25: ...ge d0 x Data not yet on network NO NET DATA d0 x Air handler blower does not contain any shared data x Populate shared data set using memory card x Turn power OFF prior to repair x Use memory card for...

Page 26: ...otor horse power MOTOR MISMATCH b2 x Incorrect circulator blower motor in air handler blower x Incorrect shared data set in integrated control module x Verify circulator blower motor horse power is th...

Page 27: ...tures x Check power to air handler blower Verify line voltage to blower is within the range specified on the air handler blower rating plate x See Installation Instructions for installation requiremen...

Page 28: ...CE INTEGRATED CONTROL LOW VOLTAGE 24V FIELD SPLICE INTERNAL TO FIELD GRND OVERCURRENT BK BLACK OR ORANGE BL BLUE PK PINK GY GRAY RD RED WH WHITE PU PURPLE YL YELLOW BR BROWN COLOR CODES GN GREEN NOTES...

Page 29: ...ULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH WARNING Wiring is subject to change Always refer to the wiring diagram on the unit for the most...

Page 30: ...airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually c...

Page 31: ...P OR LOST ROTOR b5 BLOWER MOTOR ROTOR LOCKED b6 OVER UNDER VOLTAGE TRIP OR OVER TEMPERATURE TRIP b7 INCOMPLETE PARAMETER SENT TO MOTOR b9 LOW INDOOR AIRFLOW C1 LOW STAGE COOL LEGACY MODE ONLY C2 HIGH...

Page 32: ...ufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com or www amana hac com is a registered trademark of Maytag Corporation or its related entities and is used under lice...

Reviews: