Goodman ASASD-10 Installation, Operation And Service Instructions Download Page 8

 

 

3.  Push the light out through front of power box. 
4.  Push the new light into the power box. 
5.  Connect the wiring to the LED terminals on the power 

board. P3 - red; P4 - black. Route the wires away 
from the high voltage wires or contacts. 

6. Replace 

cover. 

7.  Return power to Air Cleaner. Test light. 

 

Replacing A Power Board 

Before replacing the power board, turn 

OFF

 power to 

the Air Cleaner at the source or remove the plug. 
1.  Remove the power box cover. 
2.  Disconnect wiring from the  LED, HV1, HV2 and 24 V 

terminals. Make note of position of wires. 

3.  Remove the three hex nuts from the power board. 
4.  Remove the power board from the studs. 
5.  Place the new board onto studs with the 24 volt input 

close to the transformer. 

6.  Replace the hex nuts removed in Step 3. Ensure the 

star washer is in place over the steel spacer at the 
ground location on the power board. For proper 
grounding the washer must be located on the top of 
the steel spacer, under the power board. 

7.  Reconnect wiring to LED, HV1, HV2, and 24 V 

terminals on the new power board. See Fig. 5. 

8.  Return power to Air Cleaner. Test power board. 
9.  Replace power box cover. 

Note:

  The power board has been set before shipping. It 

is not usually necessary to reset the voltage to the new 
load. If you do need to adjust the voltage refer to Setting 
Voltage of Power Board section for more information.

 

 

Testing Air Proving Switch (APS) 

The APS sensor must sit in the plastic bushing to 

operate correctly.

 

The sensor is very sensitive and 

operation may be affected by cold ambient temperatures, 
an air exchanger, or a fresh air duct connected to the 
return air duct just upstream of the Air Cleaner. 

The APS uses a Triac in its output circuit, which 

affects the voltage sine wave. Using a regular digital 
voltmeter may give a false reading. To check the output 
from the APS, use a true RMS (root mean square) meter 
to measure the output at terminals 1 and 4 of the APS. 
The output should be between 105 and 115 VAC, 
depending on the airflow across the sensor. 

A 125 volt neon lamp may be used to test the output 

of the APS. Place the leads of the lamp across terminals 
1 and 4 of the APS. If the lamp lights, the voltage is 
sufficient for operation. 

Do not use performance light.

 

When the Air Cleaner is turned on without airflow, the 

APS sensor heats up, and after 20-30 seconds opens the 
circuit to turn off the power board. When the fan starts up 
(the sensor is cooled), the circuit will close, the power 
board is turned on, and the performance light will come 
on. 

The light on the power switch will be lit even when 

the APS is open. 

If the power board fails to come on with the fan on, 

check that the sensor is properly set down, to the bottom 
of the plastic bushing, in the front of the power box. To 
check the APS for proper operation remove the collecting 
cells, turn the unit 

ON

 without the fan on. The power 

board should come on immediately, and then turn off in 
20-30 seconds as the sensor heats up. To check sensor, 
blow directly on it lightly. This should activate the power 
board within 10 seconds. Service the sensor carefully. 
The sensor leads are 120 V. If the APS does not turn the 
power board and performance indicator on, by-pass the 
APS by placing a jumper between wires 3 & 4 on the 
APS. This removes the APS from the circuit. 
See Troubleshooting Guide for more information. 

Note:

 If the air flow through the Air Cleaner is less than 

360 CFM the APS sensor may not have enough air flow 
to activate the Air Cleaner. See Wiring for information 
how to wire the Air Cleaner to the EAC module of the 
system. In very low air applications the Air Cleaner may 
need to be wired through the EAC contacts and the APS 
disabled by connecting wires 3 & 4 together. 
If there is no EAC module or it is not powered on low 
speed then a relay will have to be installed to activate the 
Air Cleaner when the fan starts. The APS will have to be 
disabled. 
 

Replacing An Air Proving Switch (APS) 

Before replacing the APS, turn 

OFF

 the power to the 

Air Cleaner at the source.  
1.  Disconnect wiring from terminals 1, 2, 3, and 4 on the 

APS. See Fig. 5. 

2.  Remove the circuit board from the studs by removing 

the two nuts. Do not remove the spacers. 

3.  Install the new APS on the studs and secure with the 

nuts. Ensure sensor protrudes only to the bottom of  
the plastic bushing. 

4.  Connect wiring to terminals on APS. See Fig. 5. 

Wiring from the power switch is connected to 
terminals 2 and 3. Wiring to the transformer is 
connected to terminals 1 and 4. 

5.  Test the new APS. 

 

Testing The 24 V Transformer 

1.  Remove power box cover. 
2.  Disconnect the leads of the 24 V transformer from 

the power board. See Fig. 5. Do not short leads. 

3.  The Air Cleaner should be 

ON

. The system fan 

should be running on high speed. The access door 
should be closed. 

4.  Measure voltage across the leads with a voltmeter. 

Voltage should read 25 - 28 VAC. 

5.  If no voltage is present, check operation of the APS. 
6.  Reconnect leads to the power board. 
7.  Replace power box cover. 

 

Replacing The 24 V Transformer 

Before replacing the transformer, check the 

resistance across the power board 24 V input terminals, 

Summary of Contents for ASASD-10

Page 1: ...ruses and more down to 0 01 micron Dual Voltage Aluminum Collecting Cells are durable and easy to maintain Cell Guide ensures proper placement of collecting cells Activated Carbon Filters remove unple...

Page 2: ...of electrostatic precipitation Millions of airborne pollutants are carried through the return air ducts of the heating cooling system and treated through four stages of filtration The prefilters 2 re...

Page 3: ...oss the Air Cleaner will vary with CFM and whether the optional carbon filters have been installed in the unit Location The Air Cleaner must only be installed in the return air duct as close to the fa...

Page 4: ...pe humidifier must be installed as far from the Air Cleaner as possible 2 Collecting cells must be washed frequently to prevent a mineral deposit build up Installation Location With Air Conditioner Wh...

Page 5: ...ent direction than the left to right set up The handle should face the door Close access door Wiring Wiring should only be performed by qualified personnel only All wiring must comply with all applica...

Page 6: ...non chlorine non corrosive non abrasive liquid household detergent Allow detergent to run down both sides of plates and ionizing wires Let stand for 5 minutes or fill up laundry tub with water and DAX...

Page 7: ...from the power board Measuring High Voltage At Power Board A high voltage meter capable of measuring up to 10 000 VDC is required to test the voltage 1 The Air Cleaner should be ON with the cells ins...

Page 8: ...oard is turned on and the performance light will come on The light on the power switch will be lit even when the APS is open If the power board fails to come on with the fan on check that the sensor i...

Page 9: ...voltage meter 9 Replace the power box cover 10 Turn ON the Air Cleaner Setting Approximate Voltage Without High Voltage Meter A high voltage meter should be used to set the high voltage If one is not...

Page 10: ...ve it from the cabinet 6 If you are removing the power box for any length of time tape a cover over the top opening to prevent air from entering into the system Replacing A Tungsten Ionizing Wire Repl...

Page 11: ...09 D0 0509 D1 0509 11 Power Box Complete No Cover 12 Carbon Filters Set of 3 1156 3 1156 3 1856 3 1856 3 13 Prefilter R0 0855 R1 0855 R2 0855 R8 0855 14 Cell Guide Plastic R1 0603 R1 0603 R1 0603 R1 0...

Page 12: ...vely power light and per formance indicator light ON or flashing Cells wet from washing Allow cells to dry completely Particles lodged in cell or broken ionizing wire Wash cell Shake particle out of c...

Page 13: ...basis for the Air Cleaner to function at its peak efficiency The frequency of cleaning will vary from one house to another On average the cells should be cleaned every 3 months Use the chart below to...

Page 14: ...NOTES 14...

Reviews: