Goodman ASAS-10ASC Installation, Operation And Service Instructions Download Page 7

Replacing An Air Proving Switch (APS) 

Before replacing the APS, turn off the power to the 

Air Cleaner at the source.  
1.  Disconnect wiring from terminals 1, 2, 3, and 4 on 

the APS. See Fig. 5 and 6. 

2.  Release circuit board from plastic spacers by 

pinching end of spacer and pulling board out. 

3.  Install new APS on plastic spacers. Ensure sensor 

protrudes slightly through plastic bushing. 

4.  Connect wiring to terminals on APS. Wiring from 

power source is connected to terminals 2 and 3. 
Wiring to power board is connected to terminals 1 
and 4. 

5.  Test the new APS. 

Testing For High Voltage At Power Board 

A high voltage meter capable of measuring up to 

10,000 VDC is required to test the voltage. 
1.  The Air Cleaner should be 

ON

 with the door 

closed. The unit fan should be running. The Air 
Cleaner should be on at least 5 minutes to allow 
voltage to stabilize. 

2.  Remove cover from power box. 
3.  Connect the ground of the high voltage meter to an 

unpainted surface in the power box. 

4.  Check terminals HV1 and HV2 (where applicable) 

on the power board to determine if voltage is 
present. 

5.  If no voltage present, remove both cells from the 

Air Cleaner and replace access door. 
a.  Check the voltage at HV1 and HV2 (where 

applicable) again. 

b.  If voltage is present, the problem is with one of 

the cells or the copper contact on the high 
voltage tray. 

c.  With a flashlight, look into the cabinet to check 

condition of the copper contacts. 

d.  If the contacts are not bent, replace one cell 

and retest voltage. If cell is OK, test the other 
cell. If the problem is with a cell, see 
Troubleshooting Guide. 

e.  Check the APS to make sure that it is 

functioning correctly. 

f.  Check the transformer to make sure power is 

being supplied to the Air Cleaner. 

6.  If there is voltage present, but the performance 

light does not come on, replace light. 

7.  High voltage can be adjusted with high voltage 

potentiometer if required. 

Replacing Performance Light 

Before replacing performance light, turn off power 

to the Air Cleaner at the source.  
1.  Remove the power box cover. 
2.  Disconnect the performance light wiring connected 

to the LED terminals on the power board. 

3.  Push the light out through the front of the power 

box. 

4.  Push the new light into the power box. 

5.  Connect the wiring to the LED terminals on the 

power board. See Fig. 5 and 6. 

6. Replace 

cover. 

7.  Return power to Air Cleaner. Test light. 

Replacing A Power Board 

Before replacing power board, turn off power to the 

Air Cleaner at the source. 
1.  Remove the power box cover. 
2.  Disconnect wiring from the LED, HV1 and 120 

VAC power board terminals (A/ GSAS-10 and A/
GSAS-11) or LED, HV1, HV2 and 24 V terminals 
(A/ GSAS-12 and A/ GSAS-18) and ground.  See 
Fig 5 & 6. 

3.  Remove the 2 hex nuts from the power board. 
4.  Release the power board from the 2 plastic board 

spacers, by pinching the end of the spacers and 
pulling the board out. 

5.  Push new board onto spacers. Make sure spacers 

click into place to hold down board. 

6.  Screw on 2 hex nuts saved from Step 3. Ensure 

the star washer is in place over the steel spacer for 
proper grounding. 

7.  Reconnect wiring to LED, HV1 and 120 VAC (A/

GSAS-10 and A/ GSAS-11) terminals or LED, 
HV1, HV2, and 24 V terminals (A/ GSAS-12 and A/
GSAS-18) and ground on the new power board. 

8.  Replace power box cover. 
9.  Return power to Air Cleaner. Test power board. 

Note:

  Although the power board has been set before 

shipping, it may be necessary to reset the voltage to 
the correct load for optimum efficiency. Refer to 
Testing Voltage At Power Board section for more 
information. 

Testing The 24 V Transformer 
(A/ GSAS-12 and A/ GSAS-18 Only) 

1.  The Air Cleaner should be 

ON

. The system fan 

should be running. The access door should be 
closed. 

2.  Remove power box cover. 
3.  Disconnect the leads of the 24 V transformer from 

the power board. See Fig. 6. 

4.  Measure voltage across leads with a voltmeter. 

Voltage should read 24 - 27 VAC. 

5.  If no voltage present, check the operation of the 

APS. 

6.  Before replacing transformer, check the resistance 

of the power board input. Input should read above 
40 Kohm. If resistance is below 40 Kohm, the 
power board may be the cause of the transformer 
failure. 

7.  Reconnect leads to power board. 
8.  Replace power box cover. 

Summary of Contents for ASAS-10ASC

Page 1: ...eria and more down to 0 01 micron Light Weight Aluminum Collecting Cells are durable and easy to maintain Cell Guides ensure proper placement of collecting cells Activated Carbon Filters remove unplea...

Page 2: ...precautions that may apply Follow all safety codes Wear safety glasses and work gloves WHAT THE ELECTRONIC AIR CLEANER DOES Your High Efficiency Electronic Air Cleaner has been designed to remove atmo...

Page 3: ...ng Installation Location With Humidifier A humidifier should be installed in the furnace warm air duct However it may be installed in the return duct without causing problems to the Air Cleaner Care m...

Page 4: ...air turbulence through Air Cleaner and to increase its efficiency There should not be more than 20 of expansion used on each side of transition fitting Do not reduce ductwork to a smaller Air Cleaner...

Page 5: ...irflow through the ducts The Air Cleaner will not run if the system fan is off For proper operation follow these simple steps 1 Run heating cooling system fan continuously and on low speed if availabl...

Page 6: ...low Replacement Carbon Filters A GSAS 10 A GSAS 11 Set of 3 Part 1156 3 A GSAS 12 A GSAS 18 Set of 3 Part 1856 3 SERVICE Testing Air Proving Switch APS The APS sensor must protrude through the plastic...

Page 7: ...aner at the source 1 Remove the power box cover 2 Disconnect the performance light wiring connected to the LED terminals on the power board 3 Push the light out through the front of the power box 4 Pu...

Page 8: ...se proximity to hydro towers or situated in remote farm land areas By adjusting the HV ADJ potentiometer the voltage can be set to optimum level A high voltage meter capable of measuring 10 000 VDC is...

Page 9: ...t Look along the top of the cell with the short still in place If there is a small arc between the cell top and copper contact then that is the bad contact Pull cell out and gently pull copper contact...

Page 10: ...4 Using needle nose pliers place spring hook in the hole of the ionizing bar near cell top 5 Place eyelet of wire over the S hook and place S hook into hole on ionizing bar on other side of cell Keep...

Page 11: ...icle out of cell Replace wire if necessary Ducts were not cleaned prior to installation of air cleaner Clean ducts Cell plate s are bent Remove cells and adjust to original spacing using needle nose p...

Page 12: ...BUT NOT LIMITED TO LOSSES TO PERSONS OR PROPERTY ARISING OUT OF THE FAILURE OF THIS EQUIPMENT TO OPERATE FOR ANY REASON WHATSOEVER ARE EXCLUDED THE EXPRESSED WARRANTIES MADE IN THIS WARRANTY ARE EXCLU...

Reviews: