background image

7. The air sensor must be installed if the freeze protection feature is enabled for the filter, valves or aux

outputs or if the chlorinator is enabled.

Turbo Cell 

(supplied with AQL-CL chlorination kit)

The Turbo Cell (used for chlorine generation) should be plumbed AFTER the filter and heater.  If installed
on a pool/spa combination system, the cell should be plumbed BEFORE the pool/spa return valve in order
to allow proper chlorination of both the pool and the spa.  Refer to plumbing diagram below:

The cell may be mounted vertically or horizontally, and water can move in either direction through the cell.
Install using the 2" unions provided.  Tighten unions 

BY HAND

 for a watertight seal.  For systems with

1½“ plumbing use adaptors (provided by installer).

Flow Switch 

(supplied with AQL-CL chlorination kit)

The flow switch must be plumbed in the same section of plumbing as the Turbo Cell. The flow switch is a
safety device that ensures that water is flowing through the cell before the Pro Logic starts to generate
chlorine.  Failure to properly install the flow switch can result in explosive gases accumulating in the pool
plumbing system.

!

  IMPORTANT: There must be at least a 12" (30cm) straight pipe run before (upstream)

the flow switch.  If the switch is plumbed after the cell, the cell can by counted as the 12" (30cm)
of straight pipe.

!

  IMPORTANT:  To ensure proper operation, verify that the arrow on the flow switch points

in the direction of water flow.

10

21

5.  Configuration Setup

After plumbing and wiring are complete, the Pro Logic MUST BE CONFIGURED before attempting to
operate.  Configuration information is entered at the keypad and “tells” the Pro Logic what equipment is
connected and how each should be controlled.

Accessing the Configuration Menus

Configuring the Pro Logic requires that you navigate through the Configuration Menu and input various
information.  For more detailed information about using the Pro Logic menu system, refer to the Operation
Manual.

To access the Configuration Menu

Configuration

Menu-Unlocked

Configuration

Menu-Locked

Press repeatedly until “Configuration Menu” is displayed

 

Move to configuration menu items

Press BOTH buttons SIMULTANEOUSLY for 5 seconds to unlock

NOTE: The configuration menu automatically “locks” after 2 minutes of no buttons being
pressed to prevent unauthorized people from changing the control logic inadvertently and
possibly damaging the pool equipment or causing a “call back” to fix the configuration.

Configuration Menu Items

Each item needs to be programmed and may contain additional sub-menu items.  Refer to the following
pages for information on programming.

Cell Type

T-CELL-15

Toggle between T-CELL-5 and T-CELL-15
Move to next menu item

Move to next menu item

Chlorinator

Enabled

Display

Salt

Chlor. Config.

+ to view/change

Toggle between Display Salt (default) and Minerals 

Toggle between Chlorinator Enabled (default) and Disabled

Move to previous/next configuration menu

Move to next configuration menu

Push to access Chlorinator option

Chlorinator

If the chlorinator is enabled (requires the use of the AQL-CL chlorination kit), then the cell
and flow switch must also be installed and the Pro Logic will automatically chlorinate both
the pool and spa according to the desired output setting (see Settings Menu in the Operation
manual).  If disabled (default), then neither the cell nor flow switch need to be installed and
all displays relating to the chlorinator will be suppressed.

When the chlorinator is enabled, the Pro Logic will automatically detect and control any
Aqua Rite(s) that is installed in the system (see page 20).

Display

Allows for the display of salt (default) or mineral values.

Cell Type Selection

The Cell Type Menu appears after “Display Salt/Minerals” in the Chlorinator Configuration
Menu.  The options are T-CELL-5 or T-CELL-15 (default).  Make the proper selection based
on the electrolytic cell that is used in your system.  For pools up to 20,000 gallons, the T-
CELL-5 is typically used.  The T-CELL-15 is for pools up to 40,000 gallons.

12”

min

Flow switch before cell

Flow switch after cell

Summary of Contents for Pro Logic PL-P-4

Page 1: ...www goldlinecontrols com Automation and Chlorination Installation Manual for model PL P 4 LD C G LINE ON TROLS...

Page 2: ...nal must be connected to the grounding means provided in the electric supply service panel with a continuous copper wire equivalent in size to the circuit conductors supplying the equipment One bondin...

Page 3: ...al Remote Controls 7 Optional Base Station 8 Optional ValveActuators 8 3 Plumbing Pool Spa Configuration 9 Turbo Cell 10 Flow Switch 10 4 Electrical Main Service 11 Wiring Grounding and Bonding 11 Cir...

Page 4: ...roofcover formountingonsideofProLogic Mounting hardware screws etc for mounting Pro Logic and remote display keypad Valves use standard Hayward Pentair Compool or Jandy valves Additionalvalveactuators...

Page 5: ...raturesensors Remotedisplay keypad optional Valve actuators if applicable 3 Plumbing page 9 GeneralPoolEquipment Turbo Cell Flow Switch 4 ElectricalWiring page 11 Main service Groundingandbonding Circ...

Page 6: ...ou are using the chlorinator features on the Pro Logic Control If you are NOT using the chlorinator it is recommended that you follow all of the other chemistry recommendations be sides salt Refer to...

Page 7: ...100 45 110 160 50 73 120 170 55 77 130 180 59 81 140 190 64 86 150 200 68 90 93 42 107 48 120 55 133 61 147 213 67 98 160 227 73 104 173 240 79 110 187 253 85 117 200 267 91 123 2200 3000 2800 2400 32...

Page 8: ...h x 893 Length x Width x Average Depth x 1000 POUNDS and Kg OF STABILIZER CYANURIC ACID NEEDED FOR 80 PPM Gallons and Liters of Pool Spa water Current Stabilizer Level ppm 0 ppm 20 ppm 60 ppm 30 ppm 4...

Page 9: ...l O ring makes an adequate seal Do not overtighten 4 For maximum temperature accuracy cover the sensor and 3 6cm of pipe on either side with insulationandwhitepaint Air Sensor Mount the air sensor out...

Page 10: ...sulated waterproof device which is intended for installation at the water s edge Theremotecontrolcomeswithanattached150 cableandistypicallyinstalledatthetile lineofthe spa wall or in the deck within a...

Page 11: ...emote control is used To installthebasestation removetheknockoutontheupperleftsideoftheProLogicmaincontrolunit insert the base station and then tighten the nut from the inside Also refer to the Base S...

Page 12: ...mps operate only when the filterpumpisonandthesystemisinthe poolonly operatingmode 6 The plumbing diagram above is intended to be used as a general guideline and is not a complete plumbingschematicfor...

Page 13: ...for a watertight seal For systems with 1 plumbinguseadaptors providedbyinstaller Flow Switch supplied withAQL CLchlorination kit TheflowswitchmustbeplumbedinthesamesectionofplumbingastheTurboCell The...

Page 14: ...ical panel to the Pro Logic ground bus bar Also ground each piece of high voltage 120 or 240VAC equipment that is connected to the Pro Logic control relays or circuit breakers The Pro Logic should als...

Page 15: ...heProLogicrequires120VAC 2A powertooperatethecontrollogiccircuitsandthechlorinator This power should be connected to one of the circuit breakers WARNING 120VAC only permanent damage if connected to 24...

Page 16: ...externaltransformer Forlightingsystemsthathavebothalightsource and color wheel connect the light source to the Lights relay and then connect the color wheel to one of theAUXoutputs Hayward Variable Sp...

Page 17: ...red by a GFCB Low Voltage Wiring ValveActuators The Pro Logic can control up to three automatic valve actuators Two of the valve outputs are dedicated to the pool spa suction Valve2 and return Valve1...

Page 18: ...raturerating for wires If no guidance is given use 105 C rated wire 3 Set any ON OFF switch on the heater to ON 4 Set the thermostat s on the heater to the maximum hottest setting Laars Heaters 1 Turn...

Page 19: ...aterwillfirewheneverProLogicrequests whenProLogic Heater LEDisilluminated Pentair Purex MiniMax 1 Turn power off to heater 2 Removefactoryinstalledjumperfromthe ExtSwitch connector 3 Wire the Pro Logi...

Page 20: ...L or SPA which then disables the remote control by the Pro Logic To prevent this Remove the heater touch pad connector P5 which will disable the touchpad STA RITE Heater 1 Turn power off to heater 2 R...

Page 21: ...d VSC power connections if possible VSCPumpAddressSetting For proper communications a pump address must be set for each VSC used in the system For single pumpsystems theVSCaddressshouldbesetto001 When...

Page 22: ...isplay keypads are installed Never connect more than 2 wires to any terminal block Two remotes can be wired back to the Pro Logic main unit or the second display keypad and third ifapplicable canbe da...

Page 23: ...lineAqua Rite Chlorinator TheProLogiccancontroloneormoreGoldlineAquaRitechlorinatorswhenadditionalsanitizingcapacity is required A4 wire connection is used to communicate to theAqua Rite and can be wi...

Page 24: ...gle between T CELL 5 and T CELL 15 Move to next menu item Move to next menu item Chlorinator Enabled Display Salt Chlor Config to view change Toggle between Display Salt default and Minerals Toggle be...

Page 25: ...d Disabled default if Pool Only or Spa Only is selected Move to previous next configuration menu Filter Off Valve Change Enabled Toggle between Enabled and Disabled default if Pool and Spa is selected...

Page 26: ...ter Cooldown mode Filter Config to view change Filter Pump 1 Speed Freeze Protect Enabled Lowest Speed 10 Highest Speed 100 Push to access pump options Rotates between 1 speed default 2 speed and vari...

Page 27: ...erature to be used for freeze protection Temperature is adjustable from 33 F 42 F 1 C 6 C 38 F 3 C is default This threshold will be used for all outputs that have freeze protection enabled Heater1 Co...

Page 28: ...enu item if Solar is enabled if Solar is enabled Allow Low Speed Disabled Toggle between Enabled and Disabled default Move to next menu item or previous next configuration menu if Solar is enabled and...

Page 29: ...hts Function Although designated as the Lights output the function of the lights relay is similar to the aux1 and aux2 relays If pool lights are wired to the lights relay some options including Solar...

Page 30: ...c will energize the lights relay IMPORTANT this only enables operation of the lights relay during freeze see the Filter Pump Config menu to enable freeze protection for the main circulation system NOT...

Page 31: ...ntdown Timer Timeclock selected above and turn the aux1 off when filter pump is off first 3 minutes of filter pump operation allows the pump to prime and get water flowing when the pool spa suction re...

Page 32: ...re threshold the Pro Logic will turn on the valve to allow circulation of the water IMPORTANT this only enables operation of the valve3 output during freeze see the Filter Pump Config menu to enable f...

Page 33: ...ion parameters Move to previous next configuration menu config not reset Move to previous next menu config not reset Move to previous next configuration menu Use this function to erase all previous sy...

Page 34: ...ng is set as high as possible usually 104 F 40 C Also note that some heat pumps actually have be set to the lowest possible temperature 3 Once the heater is running you can verify the heater cooldown...

Page 35: ...itecap Drive North Kingstown RI 02852 for warranty service The costs incurred in removal and or reinstallation of the product are NOT covered under this warranty Some states do not allow limitations o...

Page 36: ...pool high low speed day and time backlit display light beeper teach wireless remote wireless channel maintenance menu pH calibration wizard clean probe wizard timers menu pool filter pump1 or hi spee...

Reviews: