Mitteldruckregler Typ VSR 0126
Artikel-Nr. 01 267 50 d
17 / 64
OPERATION
Lock-in device on handwheel with adjustable version
1. Loosen handwheel: Unscrew the set
screw of the handwheel slightly using an
Allen key.
2. Adjust the outlet pressure: Adjust the
required outlet pressure by turning the
handwheel (turning clockwise =
increases the outlet pressure).
The outlet pressure can be seen
on the pressure gauge.
3. Lock the handwheel: Tighten the set
screw in the groove on the housing of the
handwheel with an Allen key.
TROUBLESHOOTING
Fault cause
Action
Gas smell
Leaking LPG is extremely
flammable.
Can cause explosions.
Close the gas supply.
Do not use any electric switches.
Do not use a phone in the building.
Ventilate rooms well.
Shut down the LPG system.
Contact a specialised company.
No gas flow.
Open the gas cylinder valve or the shut-off fittings.
Pressure regulator is damaged, replace.
Pressure gauge indicates
incorrect values or is not
working at all.
Pressure gauge is defective.
REPLACEMENT must be carried out by a
specialised
company
.
Abnormal flame pattern of
non-adjustable pressure
regulator
Compare the nominal outlet pressure of the pressure
regulator with the nominal inlet pressure of the connected
consuming device:
if they do not correspond, replace the pressure regulator
or the gas appliance.
Abnormal flame pattern
of adjustable pressure
regulator
Compare the nominal outlet pressure of the pressure
regulator with that of the connected device:
if they do not match, adjust the pressure regulator to the
nominal connection pressure.
Measure the outlet pressure of the pressure regulator;
outlet pressure is not within the specified limits.
check the system configuration,