SmartBox
®
4 LAN / SmartBox
®
4 LAN PRO
part no. 28 410 57 a
11 / 28
Quitting the
setup mode:
You can quit the setup mode at any time.
Select “Exit“ and press [ENTER]
to go back to the standard display mode.
Menu
Input function
Input value
Tank: 1
SmartBox 4
LAN PRO
Select the tank (tank: 1 to tank: 4) to enter the
corresponding values. (This step is not displayed if only
one probe is connected to SmartBox
®
4 LAN PRO.)
Tank:_______
0.Exit
Press [ENTER] to return to display mode
1.Probe
Select probe measuring range
see type label of the
probe
-
default setting
250 mbar
________mbar
Standard probe
max. tank height for
fuel oil
water
100mbar
1.20 m
1.00 m
150mbar
1.80 m
1.50 m
160mbar
1.90 m
1.60 m
200mbar
2.40 m
2.00 m
250mbar
2.90 m
2.50 m
400mbar
4.70 m
4.00 m
500mbar
6.00 m
5.00 m
1.000mbar
12.00 m
10.00 m
2.000mbar
24.00 m
20.00 m
3.000mbar
36.00 m
30.00 m
5.000mbar
60.00 m
50.00 m
Set mbar
2.Liquid
Select the
medium
_______kg/m³
Medium
Density value kg/m³ (15 °C)
Fuel oil
845 kg/m³ -
default setting
Water
999 kg/m³
Diesel
830 kg/m³
Biodiesel
880 kg/m³
RME, FAME
880 kg/m³
Rape oil
915 kg/m³
Palm oil
910 kg/m³
Motor oil
865 kg/m³
AdBlue
1090 kg/m³
Regular
petrol
743 kg/m³
Premium
petrol
750 kg/m³
Density value
Enter a special density value
with different measuring range
If the density of the stored medium is unknown, the reference height can be entered in menu
item “10.Trim height”