Go Power! Modified Sine Wave Inverter 

Owner’s Manual 

 

 

5.  Connect the cable from the negative terminal of the inverter to the negative terminal 

of the battery. Make a secure connection. 

 

Loose connections result in excessive voltage drop and may cause 
overheated wires and melted insulation. Ensure connections are tight. 

6.  Before proceeding further, carefully check that the cable you have just connected is 

going from the negative terminal of inverter to the negative output terminal of the 
power source (battery). 

7.  Install the inverter fuse into the positive lead. Fuse 

should be located within 12” 

(31 cm) of battery. Ensure all connections are tight and secure. 

8.  Connect the cable from the positive terminal of inverter to the positive terminal of the 

battery. Make a secure connection. Check your polarity. 

 

This inverter cannot supply power to any AC distribution wiring or AC 
loads in which the neutral and ground are connected (bonded). Doing so 
will destroy the unit and void the warranty. If you do not understand 
neutral to ground bonding then please have a professional install your 
system for you. See “Grounding” for more information. 

9.  Set the power switch to the ON position. Check the meters and indicators on the front 

panel of the inverter. The voltage bar graph should indicate 11 to 14 V depending on 
the voltage of the power source. If it is does not, check your battery bank and the 
connections to the inverter. The other indicators should be OFF. 

10.  Set the power inverter switch to the OFF position. The indicator lights may blink and 

the internal alarm may sound momentarily. This is normal. Plug the test load into the 
AC receptacle on the front panel of the inverter. 

11.  Set the power inverter switch to the ON position and turn the test load on; the inverter 

should supply power to the load. If you plan to measure the output voltage of the 
inverter, a true RMS meter must be used for accurate readings. 

4.3 

DC Install Kits 

Go Power! DC Installation Kits include everything you will need to properly connect your 
Go Power! Inverter to the batteries. 

GP-1750 

– GP Install Kit 3 

GP-3000 

– GP Install Kit 5 

Summary of Contents for GP-1750

Page 1: ...Go Power Manual GP 1750 Inverter GP 3000 Inverter ...

Page 2: ...ower Inverters can be used in a wide range of applications including RVs boats and light and heavy duty truck applications It will operate most televisions DVD players computers and small appliances including drills sanders grinders mixers blenders and microwaves To get the most out of your power inverter it must be installed and used properly Please read the instructions in this manual before ins...

Page 3: ...erload over temperature over voltage low voltage Low Battery Alarm 10 5 0 5 V DC Low Battery Shut Down 10 0 5 V DC Overvoltage Shut Down 16 5 1 V DC Thermal Shut Down 150 F 66 C Operating Temperature Range 32 104 F 0 40 C Storage Temperature Range 22 158 F 30 70 C Cooling Thermostatically controlled fan AC Receptical North American standard x4 Dimensions L x W x H 19 x 9 4 x 3 3 482 x 240 x 83 mm ...

Page 4: ... temperature over voltage low voltage Low Battery Alarm 10 5 0 5 V DC Low Battery Shut Down 10 0 5 V DC Overvoltage Shut Down 16 5 1 V DC Thermal Shut Down 150 F 66 C Operating Temperature Range 32 104 F 0 40 C Storage Temperature Range 22 158 F 30 70 C Cooling Thermostatically controlled fan AC Receptical North American standard x4 Dimensions L x W x H 14 4 x 9 1 x 6 2 365 x 230 x 158 mm Weight 1...

Page 5: ...tage or current in the red zone will result in protective shutdown of the inverter c Overload indicator Lights up when inverter shuts down due to overloading Turn inverter OFF remove cause of overload and turn inverter ON to reset d Over temp indicator Lights up when inverter protects itself against overheating Inverter shuts down while indicator is on Inverter will restart automatically and indic...

Page 6: ...t least 1 inch 2 54 cm for air flow b DC Power input terminal Black Negative c DC Power input terminal Red Positive d Chassis ground lug Connect the chassis ground to an earth ground or to vehicle chassis using 8 AWG wire The minimum inverter DC cable and DC inverter fuse sizes are listed in sections 4 3 and 4 4 ...

Page 7: ...eration The inverter will operate for several minutes when the current is in the yellow zone Operation with battery voltage or current in the red zone will result in protective shutdown of the inverter c AC outlet Outlet sockets available North America d ON OFF switch Power ON OFF switch leave in the OFF position during installation e Power LED The LED display indicates the power status of the inv...

Page 8: ...0 a DC Power input terminal Red Positive Suggested Hardware 5 16 b DC Power input terminal Black Negative Suggested Hardware 5 16 c Cooling fan Do not obstruct allow at least 1 inch 2 54 cm for air flow d Chassis ground lug Connect the chassis ground to an earth ground or to vehicle chassis using 8 AWG wire ...

Page 9: ...verse polarity connection will permanently damage the inverter Damage caused by reverse polarity connection is not covered by the warranty This inverter must only be connected to batteries with a nominal output voltage of 12 V Lower voltages will not operate the inverter properly and higher voltages could damage the inverter or the device being powered If more than one 12 V battery is used the bat...

Page 10: ...oy the unit and void the warranty If you do not understand neutral to ground bonding then please have a professional install your system for you See Grounding for more information 9 Set the power switch to the ON position Check the meters and indicators on the front panel of the inverter The voltage bar graph should indicate 11 to 14 V depending on the voltage of the power source If it is does not...

Page 11: ...power inverter has a lug on the rear panel Chassis Ground This is to connect the chassis of the power inverter to a grounding point The power inverter grounding point will vary depending on where the power inverter is installed In a vehicle connect the chassis ground to the chassis of the vehicle In a boat connect to the boat s grounding systems In a fixed location connect the chassis ground lug t...

Page 12: ...e Wave Inverter Owner s Manual Installation using two 12 V batteries in parallel Installation using two 6 V batteries in series Installation using two 6 V batteries Fuse GP Inverter _ GP Inverter Fuse _ 12 V 6 V 12 V 6 V _ ...

Page 13: ...r bottom of the graph the inverter may shut down 5 4 Battery current indicator The battery current bar graph indicates the current drawn from the battery by the power inverter It will not indicate current by other loads also connected to the battery For long term operation the current should be in the green area of the bar graph Short term operation is possible with current in the yellow area If t...

Page 14: ...e inverter Remove the hard wire cover and carefully pull out the three wires Do Not remove the hardwiring from the inverter while battery power is supplied to the inverter Remove the knockout on the hard wire cover Pull the three wires through the knockout opening and reattach the hard wire cover Install a cord grip or strain relief to protect the wires The ground wire output is yellow and green c...

Page 15: ... antenna and the television Move the television as far away from the power inverter as possible Keep the cables between the battery and the power inverter as short as possible and twist them together with about 2 to 3 twists per foot This minimizes radiated interference from the cables 6 2 Troubleshooting guide Problem and Symptoms Possible Cause Solution Low AC output voltage 95 105 VAC Using sta...

Page 16: ...on make sure ventilation openings in inverter are not obstructed Reduce ambient temperature No output voltage Error indicator on Short circuit or wiring error Check AC wiring for short circuit to ground or improper wiring 7 0 Maintenance Very little maintenance is required to keep your inverter operating properly Keep the exterior of the inverter clean and dry Unplug the inverter before cleaning P...

Page 17: ... when power is not required Installing the GP 1750 GP 3000 with an automatic transfer switch Battery inter connects should be a minimum of 4 gauge Ensure converter is turned Off when inverter is operating To avoid hidden loads turn inverter off when power is not required DC connections use appropriate GP DC Install Kit 12 V Batteries On Off Remote Optional Shore Power Cord Go Power Transfer Switch...

Reviews: