GNB TUBULAR-LMX Installation And Operating Instructions Manual Download Page 7

Page 7

The BWT watering plug assembly – plug, float and gasket (see Figure 1) – is 

the heart of the system.  It controls the watering of each battery cell to the 

recommended shut-off level.  This is a minimum of 1/8“ below the vent well at 

the end of recharge.  

During watering, the rising electrolyte level causes the float to rise.  As the 

float rises, a self-contained mechanical linkage closes a poppet valve inside 

the plug.  Once closed, system pressure keeps the valve closed for the 

duration of the filling cycle.  The installed system is designed to bleed off this 

pressure gradually once the quick-disconnect is disconnected.

During  watering,  the  water  flows  from  the  filter/regulator  unit  or  tank  unit, 

through the visual flow indicator (water wheel), quick-disconnect coupler, in–

line filter, and in to the plugs.

SYSTEM REQUIREMENTS

a)  

Filtration:

 The supply water should be filtered to ensure proper long-term operation.   Experience 

has shown that municipal water supplies typically contain unacceptable amounts of particles 

and debris.  A 20-micron (or finer) filter is recommended. 

NOTE: This is in addition to the auxiliary 100-micron BWT filter pre-

packed with the system.

b)  

Pressure:

 Minimum height of water reservoir must be ten 

feet.  For municipal water supply lines, a pressure regulator 

is required.  Recomended static system pressure is 15 psi.  

Excessive pressure can cause plugs to snap shut prematurely.  

Insufficient pressure will cause the cells to fill more slowly.

c)  

Fill Time:

  The  filling  system  should  only  be  connected  long 

enough for the cells to fill (usually 1 to 3 minutes).  When the 

flow  indicator  stops  spinning,  the  cells  are  full  and  the  quick-

disconnect should be disconnected.

CAUTION: For systems where a timer control is used, BFS recommends 

filling for two minutes.

d)  

Float Clearance: 

Adequate clearance (T1), per Figure 2a/b/c is 

required for proper action.

e) 

Water Quality:

 Use only water that meets the following analysis:

 

Total solids   

 

 

less than 125 ppm

 

Fixed solids   

 

 

less than 75 ppm

 

Organic and volatile material 

less than 50 ppm

 Iron 

    less 

than 

ppm

Figure 1

Figure 2a

T1

Figure 2b

T2

Figure 2c

Top of separators
   or moss guard

Electrolyte level

clearance

5mm

Summary of Contents for TUBULAR-LMX

Page 1: ...ashbasins are required 1 5 Batteries produce hydrogen and oxygen gas during charge Keep open flames away Do not check electrolyte level with a cigarette lighter or match Use a flashlight or permanent lights Switch on off away from the top of the battery Do not smoke or create sparks 1 6 Lift batteries with a certified approved hoist crane lift truck or similar equipment Move batteries with trucks ...

Page 2: ...r with an I E I charging profile in order to achieve a minimum 45 day watering interval To achieve a minimum 90 day watering interval GNB requires the use of a GNB charger with a Tubular LMX charging profile Open the vent caps from each cell and check to see that the electrolyte level is above the plate separators If it is obvious that the electrolyte has spilled out of any cells replace it with e...

Page 3: ... lead acid batteries the electrolyte temperature must not exceed 110 F 43 C If the battery is continuously operated at or above this temperature the service life of the battery will be severely diminished Under normal operating conditions battery electrolyte temperature should be maintained between 60 100 F 15 38 C Following charging the battery should be allowed to cool down or rest approximately...

Page 4: ...d water at the end of the charging period when the battery is fully charged and the charger has tapered to its finish rate See Section 9 When using a GNB SCR200 charger with a Tubular LMX charging profile After each 90 calendar days of operation to 80 DOD at 5 days per week or when the specific gravity in the cells reaches 1 335 to 1 345 add water at the end of the charging period when the battery...

Page 5: ...ctrolyte levels above the plate separators but no higher than 1 8 from the bottom of the vent well Check the electrolyte level quarterly or as necessary depending on battery use prior to charging If the level is not visible below the plate separators add just enough water to cover them and then proceed with charging the battery Otherwise defer watering the battery until the end of the charging per...

Page 6: ...lls is needed Operation of the sensor and lead wire connections should be checked quarterly Sensor operation can easily be checked by lifting it out of the cell If the light goes OFF the sensor is functional and can be reinserted When the sensor is removed from the cell if the light continues to FLASH check the lead wire connections If after confirming the lead wire connections the light continues...

Page 7: ...nacceptable amounts of particles and debris A 20 micron or finer filter is recommended NOTE This is in addition to the auxiliary 100 micron BWT filter pre packed with the system b Pressure Minimum height of water reservoir must be ten feet For municipal water supply lines a pressure regulator is required Recomended static system pressure is 15 psi Excessive pressure can cause plugs to snap shut pr...

Page 8: ... of maintenance and repair service available GNB can also supply all of your battery charger and accessory device replacement part needs For more information in the U S A and Canada call 1 888 563 6300 All others please contact your local GNB battery sales representative 12 RECYCLING U S Federal and State Regulations require that lead acid batteries be handled and disposed of in compliance with st...

Reviews: