GNB Tubular LMX Installation And Operating Instructions Download Page 3

Page 3

TROUBLE SIGNS

Battery temperature averages more than 125°F.
Open circuit cell voltages vary by 0.15 volts or more and specific gravity varies by 0.020 or more during equalizing. 
The top of the battery is always wet or one cell requires excessive water.

8. MAINTENANCE CLEANING

The top of the battery should be kept clean and dry. Keep the vent caps in place during use and charging. Remove the vent cap only 
to observe electrolyte levels, make water additions, take temperatures, or take specific gravity readings with a hydrometer. If the 
battery requires cleaning, contact your local GNB Industrial Power servicing representative. The solution used to clean and neutralize 
the outside of the batteries should be disposed of in an environmentally safe manner. 

9. WATER ADDITIONS

Maintain electrolyte levels above the top of the separators, but no higher than 1/8” from the bottom of the vent well. Check 
the electrolyte level weekly, or as necessary depending on battery use prior to charging. If the level is not visible (below 
the top of the separators), add just enough water to cover it and then proceed with charging the battery. Otherwise, defer 
watering the battery until the end of the charging period when the battery is fully charged and the charger has tapered to its 
finish rate. At that time, add enough water to bring the electrolyte level to 1.2” of the top of the cover. Always use distilled 
water or water that is known to be free of abnormally high amounts of impurities. Contact your local GNB Industrial Power 
representative if you are not sure of your water quality.  
BATTERIES MUST BE VISUALLY INSPECTED PER THE ABOVE SCHEDULE EVEN WITH THE USE OF A WATERING SYSTEM.

10. SERVICE AND PARTS

Your local GNB Industrial Power sales representative has more information regarding the full range of maintenance and repair 
service available. GNB Industrial Power can also supply all of your battery, charger, and accessory device replacement part 
needs. For more information in the U.S.A. and Canada, call 1-888-563-6300. All others, please contact your local GNB Industrial 
Power battery sales representative. 

11. RECYCLING

U.S. Federal and State Regulations require that lead acid batteries be handled and disposed of in compliance with strict 
guidelines. GNB Industrial Power offers disposal service for lead acid batteries. Call 1-888-438-5865 to arrange a pick-up or to 
get additional information.

©2018 Exide Technologies Exide Technologies Milton, GA 30004. GB6001 06/18

JAR

HIGH

WATERING

LEVEL

LOW

WATERING

LEVEL

COVER

VENT WELL

POST

1.25”

2.0”

For alternate language versions of this document, visit www.gnb.com

GNB INDUSTRIAL POWER

USA – Tel:  877.462.4636  
Canada – Tel: 800.268.2698

www.gnb.com

Reviews: