GNB 93.10G Installation And Operating Instructions Manual Download Page 5

4.3 TEMPERATURE 

A battery location having an ambient temperature of 25°C 
(77°F) will result in optimum battery life.  Batteries operated 
above this temperature will suffer reduced life, while batteries 
operated below this temperature may exhibit suppressed 
capacity. Though brief temperature excursions between 
0°C (32°F) and 40°C (104°F) can be tolerated, the normal 
operating temperature is between 16°C (60°F) and 32°C 
(90°F).

4.4 ELECTROLYTE LEVEL

During normal operation, the electrolyte level should be 
between the high and low marks on the battery container. 
Upon receipt of the battery, the electrolyte level may be a 
bit lower than this mark; after charging, it may be higher.  
The reason is that gas bubbles formed during charge will 
adhere to the battery plates, displacing and raising the 
electrolyte level.  Do not attempt to adjust the electrolyte 
either immediately upon receipt or immediately after the 
initial charge.

4.5 CELL POSITIONING

By now, it is assumed that the rack has been assembled.  
Determine the desired position of the positive and negative 
terminals.  Measure and mark the center of the rack. 
Determine the number of battery blocks that will fit on a step/
tier of the rack.  If that number is odd, position the centerline 
of the first battery block on the centerline of the rack step/tier.  
If the number is even, position the end of battery block on 
the centerline of the rack step/tier.  Work from the center out, 
positioning the positive terminal next to the negative terminal 
of the adjacent cell. 

If a lubricant is needed to facilitate battery 

positioning, use only Dow Corning 111.  

Lubricants that contain solvents may damage 

the battery containers and void warranty.

4.6 FLASH ARRESTORS

After the batteries have been positioned on the rack (but 
before the inter-unit and inter-tier connections have been 
made), replace the shipping caps with the provided flame/
flash arrestors. 

4.7 CONTACT SURFACES

Gently clean the contact surfaces of the battery terminal 
posts using a 3M Scotch Brite or similar scouring pad.  Coat 
the electrical contact surfaces lightly with provided No-Ox 
grease.

4.8 ELECTRICAL CONNECTIONS

Install and torque the provided M8 stainless steel hardware 
and torque the cell connector (or terminal plate) to the post. 
Target connection torque is 100 - 110 inch-lbs. (11.3-12.0 
N-m). Re-torque the stainless steel hardware 24 hours after 
the initial tightening to account for relaxation of the lead-
hardware connection. 

Electrical connections must be clean to minimize voltage drop 

and prevent connector heating.  If corrosion is observed, DO 
NOT RE-TORQUE!  The connection must be disassembled, 
cleaned, neutralized, and then re-torqued.

Install the inter-tier cables as necessary.   Do not connect 
cables directly to the battery post.  Utilize the terminal 
plates provided for main terminal and inter-tier connections.  
Re-check to be certain that the batteries are connected 
positive terminal to negative terminal throughout the string.  
Before connecting the battery string to the charger/load, 
measure the total voltage at the battery terminals.  The 
voltage should be equal to the number of cells times the 
voltage of one cell.  For example, 60 cells times 2.09 volts 
per cell = 125.40 volts (1.250 SG) or 60 cells times 2.05 volts 
per cell = 123.0 volts (1.215 SG). 

4.9 CONNECTION RESISTANCE

Connection resistance or micro-ohm (µ

Ω

) measurements 

should be taken at the time of installation and annually 
thereafter.  Initial measurements at installation become 
benchmark values.  Future values are compared to 
this benchmark as an indication of connection integrity. 

 

Re-torque of connections should be performed annually or 
when connection resistance increases to more than 20% 
over the benchmark value. 

4.10 Labels and Markings

Numerals and polarity markings should not be applied 
until after the cells have been installed on the rack. It is 
recommended that they be applied to jar surfaces only, and 
not to cell covers or rack rails.

2. Clean the plastic jar surface, in the area where the 
numeral is to be located, by using a cloth dampened with a 
washing soda solution. Immediately dry the area using a soft 
dry cloth to remove residual washing soda. 

CAUTION!! 

Do not use any solvent type materials as they 

may cause damage to the plastic jar material.

3. It is a general practice to designate the positive terminal 
cell as #1 with succeeding cells in series in ascending order.

4.11 INITIAL CHARGE

The first charge that the battery receives after shipping, 
storage and installation is very important as it may affect the 
life of the battery.  Determine the maximum charge voltage 
output that the charge system can provide and charge the 
battery in the least amount of time possible according to 
Table A.  This maximum voltage divided by the number of 
cells connected in series is the maximum charge voltage per 
cell (VPC).  If long periods of continuous charging are not 
possible at the installation, (e.g. photovoltaic applications) 
the battery should be charged where such capability exists.

The recommended times given in TABLE A are considered 
minimum. Charge the cells until the charge current tapers 
and stabilizes for 3 hours.  Then, charge the battery for the 
times and voltages given in TABLE A.

3

Summary of Contents for 93.10G

Page 1: ... INSTALLATION OPERATING INSTRUCTIONS FOR TCXG TUBULAR LEAD CALCIUM BATTERIES A Division of Exide Technologies SECTION 93 10G 2014 09 ...

Page 2: ... INDUSTRIAL POWER REPRESENTATIVE SALESPERSON__________________________________ TELEPHONE_____________________________________ LOCATION______________________________________ GNB SERVICE ASSISTANCE 1 800 241 4895 ...

Page 3: ...cal Connections 3 4 9 Connection Resistance 3 4 10 Labels and Markings 3 4 11 Initial Charge 3 SECTION 5 5 0 Equalizing Charge 4 SECTION 6 6 0 Specific Gravity 4 SECTION 7 7 0 Operation 5 SECTION 8 8 0 Cell Voltage Variation 5 SECTION 9 9 0 Water Addition 5 SECTION 10 10 0 Tap Connections 5 SECTION 11 11 0 Pilot Bloc 5 SECTION 12 12 0 Records 5 SECTION 13 13 0 Capacity Testing 6 INDEX Page TABLES ...

Page 4: ...ugh handling If such conditions are found make notation on delivery receipt before signing If battery damage is found request an inspection by the carrier and file a damage claim Also notify your GNB Industrial Power representative 2 2 Shortly after receipt within 15 days examine all batteries for concealed damage Pay particular attention to packing materials exhibiting damage or electrolyte stain...

Page 5: ...age drop and prevent connector heating If corrosion is observed DO NOT RE TORQUE The connection must be disassembled cleaned neutralized and then re torqued Install the inter tier cables as necessary Do not connect cables directly to the battery post Utilize the terminal plates provided for main terminal and inter tier connections Re check to be certain that the batteries are connected positive te...

Page 6: ...sed to determine the cell s state of charge SOC The value decreases as the battery is discharged and increases as the battery is recharged 6 2 Specific gravity is expressed to the third decimal place e g 1 250 and is measured by a hydrometer float enclosed in a glass barrel rubber bulb syringe Holding the hydrometer vertically draw sufficient electrolyte into the barrel The reading should be taken...

Page 7: ... fizzing stops then wipe area with a clean cloth dampened only with water to remove the soda Do not get any of the baking soda solution inside the battery SECTION 9 9 0 WATER ADDITIONS 9 1 The water in the electrolyte of a battery is lost by evaporation and through hydrolysis into its component hydrogen and oxygen gases Both the water vapor and electrolytic gases are liberated to the environment t...

Page 8: ...l on each level of the rack s 12 7 Annual Supplement Quarterly reports by tightening all bolted connections to the specified torque values Record connection resistances of each battery post to battery post battery post to terminal Remake any connections that are more than 20 above installation base value Check integrity of the rack 12 8 Record dates of any equalizing charges as well as total quant...

Page 9: ...GB 1000F A Division of Exide Technologies A Division of Exide Technologies A Division of Exide Technologies WHEN ADVICE IS DESIRED PLEASE FORWARD A DUPLICATE OF THIS REPORT TO YOUR GNB REPRESENTATIVE 7 ...

Page 10: ...8 NOTES ...

Page 11: ......

Page 12: ...sales and service GNB Industrial Power is best positioned to satisfy your back up power needs locally as well as all over the world Based on over 100 years of technological innovation the Network Power group leads the industry with the most recognized global brands such as ABSOLYTE GNB FLOODED CLASSIC MARATHON RELAY GEL SONNENSCHEIN and SPRINTER They have come to symbolize quality reliability perf...

Reviews: