background image

 

PSD1001 

- SIL 3 - SIL 2 Quad ch. Power Supply for Hazardous Area Equipment 

G.M. International ISM0023-11 

Installation 

 

PSD1001 is a power supply for field devices housed in a plastic enclosure suitable for installation on T35 DIN Rail according to EN50022. 
PSD1001 unit can be mounted with any orientation over the entire ambient temperature range, see section “Installation in Cabinet” and "Installation of Electronic Equipments in Cabinet" 
Instruction Manual D1000 series for detailed instructions. 
Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit 
without suffering or causing any damage 

(for Zone 2 or Division 2 installations check the area to be nonhazardous before servicing)

The wiring cables have to be proportionate in base to the current and the length of the cable. 
On the section “Function Diagram” and enclosure side a block diagram identifies all connections. 
Identify the function and location of each connection terminal using the wiring diagram on the corresponding section, as an example: 
Connect 24 Vdc power supply positive at terminal “3” and negative at terminal “4”. 
Connect positive output of channel 1 at terminal “13” and negative output at “14”. 
Connect positive output of channel 2 at terminal “15” and negative output at “16”. 
Connect positive output of channel 3 at terminal “9” and negative output at “10”. 
Connect positive output of channel 4 at terminal “11” and negative output at “12”. 
If output current required is higher than the capability of a single channel (see output diagram on data sheet for details) you can connect two or more channels in parallel by wiring 
outputs of two or more channels in parallel and use the combined output, consider however the Gas Group allowable and Safety Parameter matching with the field device for this 
combined output as shown in the Safety Parameters on the data sheet and check that it meets your actual Installation. 
 
Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards 
(e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC), make sure that conductors are well isolated from each other and do not produce any unintentional connection. 
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation 
requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. 
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. 
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water. 

Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of PSD1001 must be cleaned only with a damp or antistatic cloth. 

Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. 
According to EN61010, PSD1001 must be connected to SELV or SELV-E supplies. 

 

Start-up 

 

Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires, also check that Intrinsically Safe conductors 
and cable trays are segregated (no direct contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking. Check conductors for exposed 
wires that could touch each other causing dangerous unwanted shorts. Turn on power, the “power on” green led must be lit and the four outputs must provide output power to the 
Hazardous Area. 

Summary of Contents for PSD1001

Page 1: ...PSD1001 SIL 3 SIL 2 Quad ch Power Supply for Hazardous Area Equipment ISM0023 11 PSD1001 INSTRUCTION MANUAL SIL 3 SIL 2 Quad channel Power Supply for Hazardous Area Equipment DIN Rail Model PSD1001...

Page 2: ...10 11 12 Um 250 Vrms 20 C Ta 60 C Approvals DMT 01 ATEX E 042 X conforms to EN60079 0 EN60079 11 EN60079 26 EN61241 0 EN61241 11 IECEx BVS 07 0027X conforms to IEC60079 0 IEC60079 11 IEC60079 26 IEC61...

Page 3: ...FM FM C Certifications Type Approval Certificate KR for marine applications High Reliability SMD components High Density four channels per unit Simplified installation using standard DIN Rail and plug...

Page 4: ...device check that added connecting cable and field device capacitance and inductance do not exceed the limits Co Ca Lo La Lo Ro given in the Associated Apparatus parameters for the effective gas grou...

Page 5: ...Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system when the above conditions are respe...

Page 6: ...ASS I DIVISION 1 GROUPS A B C D CLASS II DIVISION 1 GROUPS E F G CLASS III DIVISION 1 CLASS I ZONE 0 GROUP IIC SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T...

Page 7: ...en installed in Hazardous Area Hazardous Locations or unless area is known to be nonhazardous Warning substitution of components may impair Intrinsic Safety and suitability for Division 2 Zone 2 Explo...

Page 8: ...eets your actual Installation Intrinsically Safe conductors must be identified and segregated from non I S and wired in accordance to the relevant national international installation standards e g EN...

Reviews: