D6037 

- SIL 2 Switch/Proximity Detector Repeater Transistor Out 

G.M. International ISM0409-0 

 

Configuration 

D6037D 

A configuration DIP switch is located on component side of pcb. This switch allows the configuration of input/output relationship, fault detection functions and operating mode.

 

Input Input 

Output 

Input 

Output 

Input 

CH1 

Setting 

Line fault 
detection 

IN / OUT 

Operation 

NO-NC or 

NC-NO 

NO-NO or 

NC-NC 

Disabled 

(switch / proximity sensor) 

Enabled 

(proximity sensor or switch 

with end of line resistors, de-energizes 

transistor in fault condition) 

 

NO 

OR 

NC 

 

NO 

OR 

NC 

1

 

OFF 

1

ON  

NC 

NO 

Output 

NO 

Output 

NC 

Position in fault condition 

2

ON 

2

OFF 

Input Input 

Output 

Input 

Output 

Input 

CH2 

Setting 

Line fault 
detection 

IN / OUT 

Operation 

NO-NC or 

NC-NO 

NO-NO or 

NC-NC 

Disabled 

(switch / proximity sensor) 

Enabled 

(proximity sensor or switch 

with end of line resistors, de-energizes 

transistor in fault condition) 

 

NO 

10 

OR 

NC 

10 

 

NO 

10 

OR 

NC 

10 

NC 

NO 

Output 

NO 

Output 

NC 

3

3

ON 

OFF 

Position in fault condition 

4

4

ON 

OFF 

ON 

Dip switch configuration 

1

2

3

4

ON

Dip switch factory settings. All Switches are OFF 

1

2

3

4

ON

CH1

 

CH2

 

For SIL Application 

For SIL Application 

For SIL Application 

For SIL Application 

Summary of Contents for D6037S

Page 1: ...itch Proximity Detector Repeater Transistor Out G M International ISM0409 0 SIL 2 Switch Proximity Detector Repeater Transistor Out DIN Rail and Termination Board Models D6037S D6037D D6037S D6037D INSTRUCTION MANUAL ...

Page 2: ...ls D6037D 12 mA for 1 channel D6037S with short circuit input and transistor closed typical Power dissipation 0 53 W for 2 channels D6037D 0 30 W for 1 channel D6037S with 24 V supply voltage short circuit input and transistor closed typical Isolation Test Voltage In Out 1 5 kV In Supply 1 5 kV In In 500 V Out Supply 500 V Out Out 500 V Input switching current levels ON 2 1 mA 1 9 to 6 2 mA range ...

Page 3: ...stem In field programmability by DIP Switch TÜV Certification TÜV Functional Safety Certification High Density two channels per unit Simplified installation using standard DIN Rail and plug in terminal blocks with or without Power Bus or customized Termination Boards Input Ch 1 for Proximity or Voltage free Contact Terminal block connections Input Ch 1 for Proximity or Voltage free Contact Input C...

Page 4: ...ge free Contact In 2 Proximity voltage free Contact voltage free Contact voltage free Contact R1 R2 R1 R2 Resistors R1 R2 used with voltage free contact required for line fault detection Resistors R1 R2 used with voltage free contact required for line fault detection MODEL D5037S 6 1 2 Out SIL 2 7 8 Termination board connector Power and Fault Bus Supply 24 Vdc F 5 In Proximity voltage free Contact...

Page 5: ... Termination Board D6037 unit can be mounted with any orientation over the entire ambient temperature range Electrical connection of conductors up to 2 5 mm are accommodated by polarized plug in removable screw terminal blocks which can be plugged in out into a powered unit without suffering or causing any damage The wiring cables have to be proportionate in base to the current and the length of t...

Page 6: ...in fault condition 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 1 ON NC 1 2 1 NO 2 Output 1 NO 2 Output NC 1 2 Position in fault condition 1 2 2 ON 2 OFF Input Input Output Input Output Input CH2 Setting Line fault detection IN OUT Operation NO NC or NC NO NO NO or NC NC Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes transistor in fault condi...

Page 7: ...4 ON CH1 3 4 not used For SIL Application For SIL Application Line fault detection SW1 Disabled switch proximity sensor OFF Enabled for SIL application proximity sensor or switch with end of line resistors detects field open circuit and short circuit de energizes transistor in fault condition ON IN OUT Operation SW2 NO NC or NC NO ON NO NO or NC NC for SIL application OFF D6037S Configuration Summ...

Reviews: