GMI D6002S Instruction Manual Download Page 2

 

D6002 

- Dummy Pass-Through Module 

G.M. International ISM0396-2 

 

 

 

Technical Data 

Characteristics 

Electrical Specification: 

Rated Voltage: 

 30 V

 

Rated Current: 

 0.1 A 

Compatibility: 

CE mark compliant, conforms to Directives: 
2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. 

Environmental conditions: 

Operating:

 temperature limits – 40 to + 70 °C, relative humidity 95 %, up to 55 °C. 

Max altitude:

 2000 m a.s.l. 

Storage:

 temperature limits - 45 to + 80 °C. 

Safety Description: 

ATEX:

 II 3G Ex ec IIC T4 Gc 

IECEx:

 Ex ec IIC T4 Gc 

UL:

 NI / I / 2 / ABCD / T4 

C-UL:

 NI / I / 2 / ABCD / T4 

Approvals: 

BVS 18 ATEX E 079 X conforms to EN60079-0, EN60079-7. 
IECEx BVS 18.0066X conforms to IEC60079-0, IEC60079-7. 
UL & C-UL E222308 conforms to UL 61010-1 and UL 121201 for UL and CAN/CSA C22.2 No.61010-1-12 and CSA C22.2 No. 213 for C-UL. 

Mounting: 

on customized Termination Board. 

Weight:

 about 110 g. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accommodate 

terminations up to 2.5 mm

2

Location:

 installation in Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4 or Class I, Division 2, Group A,B,C,D, T4. 

Protection class:

 IP 20. 

Dimensions: 

Width 12.5 mm, Depth 123 mm, Height 120 mm. 

General Description:

 

The single channel D6002S is a Dummy pass-through module, for field and control side circuits marshalling. 

 

Mounting on customized Termination Boards, in Safe Area / Non Hazardous Location or in Zone 2 / Class I, Division 2. 

Summary of Contents for D6002S

Page 1: ...D6002 Dummy Pass Through Module G M International ISM0396 2 Dummy Pass Through Module Termination Board Model D6002S D6002S INSTRUCTION MANUAL ...

Page 2: ...079 0 EN60079 7 IECEx BVS 18 0066X conforms to IEC60079 0 IEC60079 7 UL C UL E222308 conforms to UL 61010 1 and UL 121201 for UL and CAN CSA C22 2 No 61010 1 12 and CSA C22 2 No 213 for C UL Mounting on customized Termination Board Weight about 110 g Connection by polarized plug in disconnect screw terminal blocks to accommodate terminations up to 2 5 mm2 Location installation in Safe Area Non Haz...

Page 3: ...2 Division 2 EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 EN61326 3 1 for safety systems ATEX IECEx UL UL C Certifications Simplified installation using standard customized Termination Boards Terminal block connections 1st pole of channel 1 SAFE AREA 2nd pole of channel 1 11 12 S 1 channel Model D6002 11 12 D6002 11 12 ...

Page 4: ...my Pass Through Module G M International ISM0396 2 Function Diagram SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 MODEL D6002S 11 12 Termination board connector ...

Page 5: ...ctor per each clamping point use conductors up to 2 5 mm 13 AWG and a torque value of 0 5 0 6 Nm Use only cables that are suitable for a temperature of at least 85 C The wiring cables have to be proportionate in base to the current and the length of the cable On the section Function Diagram and enclosure side a block diagram identifies all connections Installation and wiring must be in accordance ...

Reviews: