D5097S
- 5 A SIL 3 NC contact Relay Out Module for NE or F&G/ND Load with open/short circuit diagnostic
G.M. International ISM0302-4
3
Ordering information
Front Panel and Features
SIL 3 (low demand mode of operation) for NE Load according to IEC 61508:2010 Ed.2 with Tproof = 7 / 20 yrs (
≤
10 / >10 % of total SIF) and
PFDavg (1 year) = 1.36 E-05, SFF = 97.89 %.
SIL 3 (low demand mode of operation) for F&G / ND Load according to IEC 61508:2010 Ed.2 with Tproof = 12 / 20 yrs (
≤
10 / >10 % of total SIF) and
PFDavg (1 year) = 8.12 E-06, SFF = 99.23 %.
SIL 3 (high demand mode of operation) for NE Load according to IEC 61508:2010 Ed.2 with PFH = 3.10 E-09 h
-1
.
SIL 3 (high demand mode of operation) for F&G / ND Load according to IEC 61508:2010 Ed.2 with PFH = 1.85 E-09 h
-1
.
SC 3: Systematic Capability SIL 3.
Installation in Zone 2/Div. 2.
Compatible with DCS/PLC pulse testing.
Line and Load short/open circuit detection.
Presence of load voltage monitoring.
The fault in the field is directly mirrored to the PLC DO.
5 A high availability to avoid spurious trip SIL 3 contacts for NE or F&G/ND load.
6 A inrush current at 24 Vdc / 250 Vac.
Input/Output/Supply isolation.
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
ATEX, IECEx, UL & C-UL, TÜV Certifications.
TÜV Functional Safety Certification.
Simplified installation using standard DIN-Rail and plug-in terminal blocks, with or without Power Bus, or customized Termination Boards.
Model:
D5097S
Power Bus and DIN-Rail accessories:
Bus Connector JDFT049
Bus Mounting Kit OPT5096
Terminal block connections
+ Load Power DC/AC
SAFE AREA
- Load Power DC/AC
1st pole of NO contact for Service load
2nd pole of NO contact for Service load
7
8
9
10
+ Input
1
- Input
2
(SIL 3) + Output NE Load or F&G/ND Load
(SIL 3) - Output NE Load or F&G/ND Load
11
12
7 8
9 10
11 12
1
2
4 3
6 5
Fault Output (35 V, 500 mA)
3
Fault Output (35 V, 500 mA)
4
+ Power Supply 24 Vdc
5
- Power Supply 24 Vdc
6