background image

 

D1062 

- Vibration Transducer Interface 

G.M. International ISM0094-7 

When used with separate powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, li/Imax) of the D1062 Associated Apparatus are not exceeded by 
the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below: 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50 % of Co and Lo parameters are applicable and shall not be exceeded 

(50 % of the Co and Lo become the limits which must include the cable such that 

Ci C cable 

 50 % of Co and Li  L cable 

 50 % of Lo). 

If the cable parameters are unknown, the following value may be used: Capacitance 60pF per foot (180pF per meter), Inductance 0.20µH per foot (0.60µH per meter). 
The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system 
when the above conditions are respected. 
For Division 1 and Zone 0 installations, the configuration of Intrinsically Safe Equipment must be FM approved under Entity Concept (or third party approved); 
for Division 2 installations, the configuration of Intrinsically Safe Equipment must be FM approved under non-incendive field wiring or Entity Concept (or third party approved). 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D1062 Associated 

Apparatus Parameters 

Ui / Vmax = 30V 

Uo / Voc 

D1062 Terminals 

15 - 16 

 

Ci = 0 nF, Li= 0 nH 

15 - 16 

Function Diagram 

HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC, 

HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D, 

CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1, 

CLASS I, ZONE 0, GROUP IIC 

SAFE AREA, ZONE 2 GROUP IIC T4, 

NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2, 

GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4 

MODEL D1062S

15

16

3 +

4 - Supply 24 Vdc

=

=

14

13

Out 1

11

12

10

9

1

2

In 1

- Power

3 wires

Vibration

Transducer

- Signal

Common

Signal -

Common

Vibration

Monitor

Programmable

Current

Source

=

=

=

 

Ch1 

Ch1 

Summary of Contents for D1062S

Page 1: ...D1062 Vibration Transducer Interface ISM0094 7 D1062S INSTRUCTION MANUAL Vibration Transducer Interface Din Rail Model D1062S...

Page 2: ...mVrms on 0 5 to 20 KHz band Frequency response DC to 10 KHz within 0 1 dB 10 KHz to 20 KHz within 3 dB Performance Ref Conditions 24 V supply 10 K load 23 1 C ambient temperature Calibration accuracy...

Page 3: ...Rail and plug in terminal blocks 250 Vrms Um max voltage allowed to the instruments associated with the barrier For AC Output Sensor if connected to terminal 14 Terminal block connections HAZARDOUS AR...

Page 4: ...ted 14 16 15 16 with terminals 13 14 connected Li Ri device and L cable R cable IIC A B Lo Ro 61 7 H Lo Ro 247 1 H Lo Ro 494 3 H IIB C IIA D IIC A B Lo Ro 56 8 H Lo Ro 227 3 H Lo Ro 454 7 H IIB C IIA...

Page 5: ...nsically Safe devices approved with entity parameters not specifically examined in combination as a system when the above conditions are respected For Division 1 and Zone 0 installations the configura...

Page 6: ...Out 1 11 12 10 9 1 2 In 1 Signal Common Vibration Monitor Programmable Current Source 2 wires Vibration Transducer AC Signal Common AC Output Sensor Jumper Sensor operating in AC signal mode Jumpers...

Page 7: ...ning substitution of components may impair Intrinsic Safety and suitability for Division 2 Zone 2 Explosion Hazard to prevent ignition of flammable or combustible atmospheres disconnect power before s...

Page 8: ...milar sensor connect sensor negative supply wire at terminal 14 sensor signal wire at terminal 15 and sensor common wire identical for both signal and supply at terminal 16 For 2 wires powered sensor...

Reviews: