GMI D1031D Instruction & Safety Manual Download Page 9

 

D1031 

- SIL 2 Switch / Proximity Detector Repeater Transistor Output 

G.M. International ISM0009-17 

D1031 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN Rail located in Safe Area/Non Hazardous Locations or Zone 2, Group IIC, 
Temperature Classification T4, Class I, Division 2, Groups A, B, C, D, Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA Temperature Code T4 Hazardous Area/Hazardous 
Locations (according to EN/IEC60079-15, FM Class No. 3611, CSA-C22.2 No. 213-M1987, CSA-E60079-15) within the specified operating temperature limits Tamb -20 to +60 °C, 
and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. 

Non-incendive field wiring is not recognized by the Canadian Electrical Code, installation is permitted in the US only. 
For installation of the unit in a Class I, Division 2 or Class I, Zone 2 location, the wiring between the control equipment and the D1031 associated apparatus shall be accomplished 
via conduit connections or another acceptable Division 2, Zone 2 wiring method according to the NEC and the CEC. 
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground. 
D1031 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards 
(e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC) following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones. 
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area/Hazardous Locations or 
unless area is known to be nonhazardous. 

Warning: substitution of components may impair Intrinsic Safety and suitability for Division 2, Zone 2. 
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous. 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. 
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided. 

 

Warning 

D1031 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

FM Approved under Entity Concept,

or third party approval

Hazardous (Classified) Locations

Class I, Division 1, Groups A, B, C, D

Class II, Division 1, Groups E, F, G

Class III, Division 1

Class I, Zone 0, Group IIC, IIB, IIA

Intrinsically 

Safe Equipment

Must not use or generate

more than 250 Vrms or Vdc

Control 

Equipment

Unclassified Locations

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D

Class II, Division 2, Groups E, F, G

Class III, Division 2

Class I, Zone 2, Group IIC, IIB, IIA

FM Approved under non-incendive field

wiring (permitted only for US installations),

or third party approval

13
14

1
2

+

-

-

+

Power Supply

3
4

16

15

-

+

Intrinsically 

Safe Equipment

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

Unclassified Locations

Must not use or generate

more than 250 Vrms or Vdc

6

5

Control 

Equipment

Control 

Equipment

Control 

Equipment

2

6

8

7

Intrinsically 

Safe Equipment

-

+

10

9

Intrinsically 

Safe Equipment

+

-

11

12

+

-

Power Supply

Control 

Equipment

Control 

Equipment

Control 

Equipment

Control 

Equipment

14

9

11

12

10

16

15

13

4

3

2

7

8
6

2

6

5

1

+

-

+

+

-

-

-

+

Non-incendive

Equipment

Non-incendive

Equipment

Non-incendive

Equipment

Non-incendive

Equipment

D1031 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

Testing procedure at T-proof 

The proof test shall be performed to reveal dangerous faults which are undetected by diagnostic. This means that it is necessary to specify how dangerous undetected fault, 
which have been noted during the FMEDA, can be revealed during proof test. 
Note for switch input: use of voltage free electrical contacts with fault detection enabled requires, near the switch at the end of the line, a 1 K

 series connected resistor and a 10 K

    

                    parallel connected resistor in order to allow the fault detection circuit to distinguish between a condition of contact close/open and a line open/short circuit fault. 

The Proof test

 consists of the following steps: 

Steps

 

Action

 

Bypass the Safety PLC or take any other appropriate action to avoid a false trip. 

Vary the state conditions of the input sensors / contacts coming from field and verify that the relay or transistor outputs change their state from energized to de-

energized and vice-versa; also check that the de-energized state condition corresponds to the required Safety Function. 

Disconnect the input wiring coming from the field sensor / contact and check that the corresponding alarm output is de-energized. 

Short the input connections and verify that the corresponding outputs remains de-energized. In both cases, the corresponding alarm LEDs on the front panel must 

be turned red. 

Restore the loop to full operation. 

Remove the bypass from the safety-related PLC or restore normal operation. 

This test will reveal approximately 99 % of possible Dangerous Undetected failures in the repeater. 

Summary of Contents for D1031D

Page 1: ...031 SIL 2 Switch Proximity Detector Repeater Transistor Output ISM0009 17 D1031D D1031Q INSTRUCTION SAFETY MANUAL SIL 2 Switch Proximity Detector Repeater Transistor Output DIN Rail Models D1031D D103...

Page 2: ...ort circuit input and transistors energized 1 4 W for 4 channels D1031Q 1 0 W for 2 channels D1031D Isolation Test Voltage I S In Out 1 5 KV I S In Supply 1 5 KV Out Supply 500 V Out 1 3 Out 2 4 500 V...

Page 3: ...or Output for fault detection on dual channel version Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 In field programmability by DIP Switch ATEX IECEx UL C UL FM...

Page 4: ...Ch 3 7 Output Ch 4 8 D1031D Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact HAZARDOUS AREA SAFE AREA Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact 13 14 Output Ch 1...

Page 5: ...15 16 Ch3 Ch4 9 10 11 12 Li Li device L cable Ch1 Ch2 13 14 15 16 Ch3 Ch4 9 10 11 12 Li Ri device and L cable R cable Ch1 Ch2 13 14 15 16 Ch3 Ch4 9 10 11 12 Co Ca 15 6 F IIC A B Lo La 172 mH Lo La 130...

Page 6: ...DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1031Q 13 14 3 4 1 2 Common Channels 1 3 Supply 12 24 Vdc Out 1 5 6 Common Channels 2 4 Out 2 7 Out 3 8 Out 4 15 16 9 10 11 12 Com...

Page 7: ...erance needed for a higher SIL of a certain Safety Function as they are not completely independent one from another Failure rate date taken from Siemens Standard SN29500 Input signal state Pins 13 14...

Page 8: ...about turn on or turn off of its channel status LED and channel fault LED Failure category Failure rates FIT dd Total Dangerous Detected failures 0 00 du Total Dangerous Undetected failures 49 29 sd...

Page 9: ...vision 2 Groups A B C D T Code T4 Class I Zone 2 Group IIC IIB IIA T Code T4 FM Approved under Entity Concept or third party approval Hazardous Classified Locations Class I Division 1 Groups A B C D C...

Page 10: ...ion Connect SPST output transistors checking the load rating to be within the maximum rating 100 mA 35 V resistive load The enclosure provides according to EN60529 an IP20 minimum degree of mechanical...

Page 11: ...abled contact proximity sensor Enabled proximity sensor or contact with terminating line resistor ON 13 2 OFF NO 14 OR NC 13 14 13 NO 14 OR NC 13 14 CH2 Setting Line fault detection ON IN OUT Operatio...

Page 12: ...or OFF Input Output Input Output Output Input Output Input 9 NO 10 OR NC 9 10 9 NO 10 OR NC 9 10 7 NO 2 NC 7 2 7 NO 2 NC 7 2 Input Output Input Output Output Input Output Input 11 NO 12 OR NC 11 12 11...

Page 13: ...abled proximity sensor or contact with terminating line resistor Input Output Input Output Output Input Output Input 13 NO 14 OR NC 13 14 13 NO 14 OR NC 13 14 1 NO 2 NC 1 2 1 NO 2 NC 1 2 B Output Oper...

Page 14: ...utput Operation Normal Parallel Mode Reverse Mode OFF ON Fault Output ON NO Mode NC Mode OFF ON OFF Out B Out A Out A Out B No Fault No Fault 5 NO 6 8 NO 6 5 NO 6 NC 8 6 8 NO 6 NC 8 6 Channel 1 OFF ON...

Reviews: