3
D1130
- SIL 2 Switch / Proximity Detector Repeater Relay Output
G.M. International ISM0048-12
Model:
D1130
1 channel
S
2 channels
D
Ordering information
Front Panel and Features
SIL 2 according to IEC 61511.
Tproof = 2 / 10 years (
≤
10% / >10 % of total SIF)
PFDavg (1 year) 3.60 E-04, SFF 71.28 % .
Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
Universal AC supply voltage (85 to 250 Vac, 48 to 400 Hz).
NO/NC contact/proximity Detector Input.
Two SPDT Relay Output Signals.
SPDT Relay Output for fault detection on single channel version.
Three port isolation, Input/Output/Supply.
EMC Compatibility to EN61000-6-2, EN61000-6-4.
In-field programmability by DIP Switch.
ATEX, IECEx, UL & C-UL, FM & FM-C, INMETRO, EAC-EX, UKR TR n. 898, TÜV Certifications.
Type Approval Certificate DNV and KR for maritime applications.
High Reliability, SMD components.
High Density, two channels per unit.
Simplified installation using standard DIN Rail and plug-in terminal blocks.
250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
D1130
1 2 3 4
16
15
14
13
5 6 7 8
PWR ON
1 2
STATUS/
FAULT
DIN-Rail accessories:
DIN rail stopper MOR016