background image

14

221785B

Diagram 8.2

MULTI-FUNCTIONAL
CONTROL FILTERS

2142

FINE INLET
SCREEN

PILOT
FILTER

Diagram 8.1

MULTI-FUNCTIONAL
CONTROL CONNECTIONS

5313

HEX SCREW (4)

'O' RING

GAS
SERVICE COCK

BURNER
SUPPLY
PIPE

MULTI-FUNCTIONAL
CONTROL

'O' RING

HEX
SCREW (4)

SECURING
SCREW (2)

SAFETY
DEVICE
LOCKNUT

FLUE BLOCKAGE

SAFETY DEVICE

SUPPORT
BRACKET

8 Servicing and Replacement of Parts

8.1 Access

Refer to diagram 4.1 and 6.1.

Slide the controls cover off.  Undo the screws and remove the
outer case.

Lift the combustion chamber shield clear of the lugs and
remove.

8.2 Main Burner

Refer to diagram 6.1.

Remove the main burner.  Lift the left hand end of the burner to
disengage the locating pin.

Slide the burner off the injector by moving it to the left, take care
not to damage the pilot burner and electrode assembly.  Bring
the right-hand end of the burner through the opening first.

Service note:  Clean the burner thoroughly, making sure that all
the flame ports are clear.

8.3 Boiler Flueway Cleaning

Gain access as Section 8.1.  Remove burner as Section 8.2.
Refer to diagram 4.6 and 8.6.

Release split pin.  Remove retaining angle and thermostat
phial.

Undo the screws and remove the flue cleaning door.

Remove flueway baffle.

Place a sheet of paper in the combustion chamber, covering the
electrode/pilot assembly, to catch the flue debris.

Clean the boiler flueways and fins thoroughly with a suitable stiff
brush.

Re-assembly note:  When replacing the flue cleaning door and
flueway baffle ensure they are fitted as shown in diagram 4.6.

8.4 Multifunctional Control - Servicing/
Replacement

Gain access as Section 8.1.

Refer to diagram 6.4 and 8.1.

Remove multifunctional control cover securing screw.

Disconnect the electrical leads, thermocouple and pilot supply
tube at the multifunctional control.

Remove the flue blockage safety device securing locknut and
release from bracket, taking care not to strain the capillary.

Remove the two securing screws from the support bracket.

Undo the four screws each side of the multifunctional control to
release the gas service cock and burner supply tube, take care
not to damage the “O” rings.

Reassembly note 1:  When refitting the gas valve take care not
to damage the “O” rings.

Reassembly note 2:  When fitting a replacement gas valve
remove the bracket and fit to new one.

Refer to diagram 8.2.

To inspect the inlet screen and replace the pilot filter remove the
base of the multifunctional control by releasing the five screws.

When reassembling take care not to damage the screen.

Remake the electrical connections.

NOTE.  Do not tighten the thermocouple nut more than one
quarter turn beyond finger tight.

It will be necessary to purge the pipework and multifunctional
control before relighting, refer to Commissioning.

8.5 Multifunctional Control/Solenoid
Replacement

Refer to diagram 8.3.

Remove the multifunctional control cover as described in Section
8.4.

Disconnect electrical leads, remove the solenoid retaining clip
and solenoid.

Summary of Contents for Ultimate 40CF

Page 1: ...ce of mind plus valuable protection against breakdown by covering the cost of Guarantee Registration Open Flue Boiler This is a Cat I2H Appliance BS 6332 BS 5258 Reference in these instructions to British Standards and Statutory Regulations Requirements apply only to the United Kingdom The instructions consist of three parts User Installation and Servicing Instructions which includes the Guarantee...

Page 2: ...uels 2 Directive 73 23 EEC on the harmonization of the Laws of the Member States relating to the electrical equipment designed for use within certain voltage limits 3 Directive 89 336 EEC on the approximation of the Laws of the Member States relating to electromagnetic compatibility INFORMATION FOR THE INSTALLER AND SERVICE ENGINEER Under Section 6 of The Health and Safety at Work Act 1974 we are ...

Page 3: ...n on the control tray Please be advised that the Benchmark logbook should be completed by the installation engineer on completion of commissioning and servicing All CORGI Registered Installers carry a CORGI ID card and have a registration number Both should be recorded in your boiler Logbook You can check your installer is CORGI registered by calling CORGI direct on 01256 372300 Boiler Clearances ...

Page 4: ...RMOSTAT CONTROL KNOB C GAS SERVICE COCK SHOWN IN OFF POSITION D CONTROL BUTTON GAS E VIEWING WINDOW F FLUE BLOCKAGE SAFETY DEVICE RESET BUTTON E F B A DATA LABEL Turn thermostat knob B faulty anticlockwise to the O Off position Push in control knob D keep pushed in push and release piezo button A until the pilot lights Look through window E After the pilot burner lights keep the button pushed in f...

Page 5: ...Range Rating The boiler is range rated and may be adjusted to suit the individual system requirements The respective Table 1 gives the ratings and settings A B C D E F H K L M N R S 764 265 168 213 149 24 5 39 115 741 417 640 345 23 MODEL Diagram 1 1 GENERAL DIMENSIONS all dimensions in mm 40CF 0020M B D C H F A R L N GAS CONNECTION RC1 2 1 2 in BSPT WATER CONNECTION RC1 1in BSPT M K E S C L C L F...

Page 6: ...boiler must be mounted on a flat wall which is sufficiently robust to take its weight 1 12 Boiler Clearances Refer to diagram 4 4 The boiler must be positioned so that at least the minimum operational and servicing clearances are provided Additional clearances may be required for installation If fixtures are positioned next to the boiler they should be made removable for access to pipework Suffici...

Page 7: ...a cavity wall must be ducted If there are other fuel burning appliances present allowance must be made for their combustion requirements The free area for the boiler is 40CF 38cm2 5in2 Refer also to the current issue of BS5440 Part 2 2 3 Products of Combustion Test the boiler for clearance of flue products at the draught diverter as detailed in the current issue of BS5440 Part 1 2 4 Extract Fans I...

Page 8: ...o C 20o F between flow and return with the boiler thermostat set at MAX which is about 82o C 180o F The resistance through the boiler can be found from diagram 3 3 4 Installation 4 1 Unpacking Unpack and check that the contents listed below are present and undamaged Boiler combustion chamber shield side panels x 2 burner flueway baffle loose items pack with check list With the boiler still in the ...

Page 9: ...e so that the tags on the boiler body locate on the cross member of the wallframe see diagram 4 5 Fasten the boiler to the wallframe using the screws previously removed Remove the flue cleaning door see diagram 4 6 Remove the split pin Withdraw the retaining angle and thermostat phial from its pocket Fit the flueway baffle making sure that it is seated down correctly onto the casing as shown in di...

Page 10: ...fittings Fill vent and cold flush the system as recommended in the current issue of BS6798 Visually check for and put right any water leaks 4 5 Gas Connection Make the gas connection to the flanged Rc1 2 gas service cock 4 6 Flue Installthefluepipeworkandsealtothefluesocketinaccordance with normal practice 5 Electrical Connection 5 2 Cable Connection Thread the mains cable through the clamp at the...

Page 11: ...ntrol knob B to O the off position Remove the gas pressure test nipple screw E and fit a suitable pressure gauge Open gas service cock C Note Make sure that the flue blockage safety device reset button P is fully pushed in Push in control button K keep pressed in and at the same time operate the piezo unit button G until the pilot burner lights After the pilot burner lights keep the button K pushe...

Page 12: ...e cover removed for clarity A ELECTRICAL CONTROL BOX B THERMOSTAT CONTROL KNOB C GAS SERVICE COCK SHOWN IN OFF POSITION D MULTI FUNCTIONAL CONTROL E PRESSURE TEST NIPPLE F GAS BURNER TEST NIPPLE G PIEZO UNIT BUTTON H THERMOCOUPLE PIPE K CONTROL BUTTON GAS M CASE SECURING SCREW N PILOT BURNER PRESSURE SCREW P FLUE BLOCKAGE SAFETY DEVICE RESET BUTTON 8052 E M G B A H P C K D N F Check the operation ...

Page 13: ...ue of the Gas Safety Installation and Use Regulations Section 35 which imposes a duty of care on all persons who let out any property containing a gas appliance It is the Law that any servicing must be carried out by a competent person Advise that the boiler is fitted with a safety device and refer to the Instructions for Use Advisetheuseroftheprecautionsnecessarytopreventdamage to the system and ...

Page 14: ...ay baffle ensure they are fitted as shown in diagram 4 6 8 4 Multifunctional Control Servicing Replacement Gain access as Section 8 1 Refer to diagram 6 4 and 8 1 Remove multifunctional control cover securing screw Disconnect the electrical leads thermocouple and pilot supply tube at the multifunctional control Remove the flue blockage safety device securing locknut and release from bracket taking...

Page 15: ...mocouple spring clip and remove the thermocouple Re assembly note When refitting do not tighten the thermocouple nut more than a quarter turn beyond finger tight 8 10 Pilot Burner Gain access as Section 8 1 Refer to diagram 6 3 and 8 4 Remove the main burner as described in Section 8 2 Remove electrode as described in Section 8 7 Disengage the thermocouple spring clip and carefully ease the thermo...

Page 16: ...led up tidily at the rear of the control box There must be no kinks or sharp bends in the capillary 8 12 Peizo Unit Gain access as Section 8 1 Refer to diagram 8 7 Remove the electrical control box refer to Section 5 1 Disconnect the ignition lead at the piezo unit Note To ease the removal of the piezo unit it is advisable to temporarily remove the boiler thermostat from the control box refer to S...

Page 17: ...ple Check aeration If necessary Clean pilot rectify blockage in pilot injector or replace Check thermocouple circuit using Thermocouple fault finding diagram On pressing piezo unit button is there a spark across electrode gap Pull ignition lead off electrode Hold end of lead close to pilot burner and operate piezo unit Is there a spark across gap Pull ignition lead off piezo unit Using blade of a ...

Page 18: ...the flue blockage safety device Is there continuity YES NO NO PERMANENT LIVE 230V 50Hz 3A FUSE THERMOSTAT L RED C NC BROWN MULTI FUNCTIONAL CONTROL SOLENOID BLUE N 3 4 Diagram 9 3 FUNCTIONAL FLOW WIRING 2327 B Diagram 9 2 THERMOCOUPLE FAULT FINDING 9 1 Pilot Refer to chart 9 1 9 2 Thermocouple Refer to chart and diagram 9 2 9 3 Electrical Refer to diagram 9 3 and 9 4 The preliminary electrical sys...

Page 19: ...s available and the pilot is lit Isolate electrical supply to the control box Remove the control box cover and check all cables Turn boiler thermostat to Max Is there continuity between C and NC Turn boiler thermostat to O Is there open circuit between C and NC Faulty thermostat Replace Restore electrical supply with pilot burner lit and boiler thermostat set between MIN and MAX does the main burn...

Page 20: ...Injector 355 274 4 K2674 Thermocouple 390 894 5 K3580 Clip thermocouple 390 983 6 203416 Pilot burner 381 793 7 900500 Spark electrode 381 733 8 WW4617 Ignition lead 312 997 9 202519 Thermostat 381 798 10 204687 Control knob 11 202713 Piezo unit 12 801236 Mica window and foil gasket 13 203350 Solenoid 14 800755 Safety device 278 469 Because of our constant endeavour for improvement details may var...

Reviews: