Glow-worm Hideaway 80B FF Instructions For Use Manual Download Page 16

16

221958B

4.13 Water & Gas connections

Replace fan access door, heat shield and control box.

Note: When replacing the fan access door make sure the lip at
the top of door fits into and behind the slotted bracket located at
the top of the boiler.

As there are two casing height options, the control box height
and the heat shield may have to be adjusted to suit your
requirements.

Complete the water connections to the boiler.

Fill, vent and flush the system.

Check for any water leaks and put right.

Make the gas connection to the service cock, at the lower left
hand side of the boiler, see diagram 1.1.

The whole of the gas installation, including the meter, should be
inspected, tested for soundness and purged in accordance with
the current issue of BS6891.

4.14 Top Casing

Refer to diagram 4.21.

Fit two plastic pegs, one on each side, in the holes on the top
casing. The plastic pegs are a tight fit and are best pushed home
with a flat faced tool.

Secure front of top casing with the screws provided.

4  Installation

Diagram 4.21

TOP CASING

9865

SCREW  (2)

PLASTIC
PEG (2)

Diagram 4.20

FRONT AIR PRESSURE
SWITCH TUBE (CLEAR)

FAN ELECTRICAL
CONNECTORS

10149

Diagram 4.19

FLUE DUCT
EXTENSION PIECE

FAN

AIR
PRESSURE
TUBE (RED)

FAN
SECURING
SCREW

REAR AIR PRESSURE
SWITCH TUBE (RED)

10259

Summary of Contents for Hideaway 80B FF

Page 1: ...r Service number 01773 828100 Our Guarantee gives you peace of mind plus valuable protection against breakdown by covering the cost of Guarantee Registration Balanced Fanned Flue Boiler This is a Cat I2H Appliance Reference in these instructions to British Standards and Statutory Regulations Requirements apply only to the United Kingdom For Ireland the rules in force must be used The instructions ...

Page 2: ...provide information on substances hazardous to health Ceramic fibre Insulation Pads Glassyarn These can cause irritation to skin eyes and the respiratory tract If you have a history of skin complaint you may be susceptible to irritation High dust levels are usual only if the material is broken Normal handling should not cause discomfort but follow normal good hygiene and wash your hands before eat...

Page 3: ...pendupon the particular installation conditions and usage but in general once a year should be enough It is the law that servicing must be carried out by a competent person If this appliance is installed in a rented property there is a duty ofcareimposedontheownerofthepropertybythecurrentissue of the Gas Safety Installation and Use Regulations Section 35 To obtain service please call your installe...

Page 4: ...rol wait at least 30 seconds before switching on again When the boiler switches off the burner will go out The automatic lighting sequence will operate again when heat is required It should be noted that this is a fanned flue appliance and fan operation may be heard If the reset neon lights turn the boiler temperature control to 0 off wait 30 seconds then repeat the lighting instructions To Turn t...

Page 5: ... in millimetres except as noted Approximate weight of complete boiler 131 5kg 290lb Water content 5 76 litre 1 27gallons Gas connection Rc1 2 1 2 in BSPT Water connection Rc1 1in BSPT Electrical supply 230V 50Hz fused 3A Burner Aeromatic GENERAL DIMENSIONS given in millimetres Diagram 1 1 9921 WATER CONNECTIONS Rc1 1in B S P T WATER CONNECTIONS Rc1 reduced with DISTRIBUTOR TUBE to Rc 3 4 3 4 in B ...

Page 6: ...ssue of BS6891 The supply from the governed meter must be of adequate size to provide a steady inlet working pressure of 20mbar 8in wg at the boiler On completion test the gas installation using the pressure drop method and suitable leak detection fluid purge in accordance with the current issue of BS6891 1 6 Electrical WARNING This boiler must be earthed The electrical installation must be carrie...

Page 7: ... installation of the boiler will be in an unusual location special procedures are necessary the current issue of BS6798 gives detailed guidance on this aspect 2 Water Systems 2 1 Water Pressure Head The boiler shall only be connected to a cistern water supply with a minimum head of 1metre 3ft3in and a maximum head of 27metres 90ft which has an open vent in the system The working pressure must be w...

Page 8: ...pedflow rate the pressure loss through the boiler can be found from the graph diagram 2 3 Use a pump with integral valves or fit isolating valves as close to the pump as possible 2 6 Cylinder For all systems supplying domestic hot water the cylinder must be indirect 2 7 Safety Valve A safety valve need not be fitted to an open vented system 2 8 Draining Tap A draining tap must be provided at the l...

Page 9: ...e from the local gas undertaking or Hepworth Heating Ltd 3 3 Terminal Guard A terminal guard is required if persons come into contact with the terminal or the terminal could be subject to damage If a terminal guard is required it must be positioned to provide a minimum of 50mm clearance from any part of the terminal and be central over the terminal A suitable guard reference Type K3 can be obtaine...

Page 10: ...n optional wall liner kit part no 900862 is available complete with instructions All flue assemblies are designed for internal installation Make sure that the ductings do not slope down towards the boiler Diagram 4 1 9867 9868 4 2 Flue Position and Length Select the boiler location with due regard to the flue length and terminal position see diagrams 3 1 and 4 1 For a wall thickness up to 300mm pr...

Page 11: ...nal restrictor and secure with locking screw but do not tighten see diagram 4 5 Engage the terminal restrictor on the flue terminal by hooking it over the terminal end and engaging the clamping bracket behind the inner ring of the terminal securing it by tightening the locking screw see diagram 4 5 9869 SCREW 4 SPIGOT GASKET FLUE BAYONET CONNECTION Diagram 4 4 7148 OPTIONAL FLUE COLLAR 4 Installat...

Page 12: ...of the three remaining lower connections may be used for the gravity domestic hot water return Fit plugs into any unused boiler tappings 4 7 Water Connections Fully Pumped Systems Fit suitable fittings into the boiler tappings as required see diagram 4 9 Make sure that all pipes are taken backwards and will clear the casings It is important that all connections are made as shown in diagram 4 9 Fit...

Page 13: ...re that it will clear the boiler air duct and if working to minimum clearance does not project too far from the boiler see diagram 4 11 Do not route any pipework water or gas across the front of the combustion chamber cover The gas pipework must be along the left hand side of the boiler 4 Installation No 8 SCREW 4 4 9 Casing Brackets Fit the two upper and two front casing brackets shown in diagram...

Page 14: ...tory with the control box and heat shield fitted in the lower casing height position 9863 SIDE CASINGS FITTING Diagram 4 14 MAX SIDE CASING R H MIN BOILER PLINTH FRONT CASING BRACKET No 8 SCREW 4 LOCATING SLOTS 4 Installation Diagram 4 13 Diagram 4 15 SCREW SIDE CASING R H SHOWN UPPER CASING BRACKET PLASTIC PEG PLASTIC PEG SPRING CLIP SIDE CASING R H SHOWN UPPER VIEW LOWER VIEW SPRING CLIP SIDE CA...

Page 15: ...the fittings pack Connect the flue spigot and gasket to the rear flue outlet of the boiler using the self tapping screws provided see diagram 4 3 IMPORTANT WithregardstotheManual HandlingOperations 1992 Regulations the following operation exceeds the recommended weight for one man lift Place the boiler in position taking care not to damage the casing panels With access to the flue system through t...

Page 16: ...ervice cock at the lower left hand side of the boiler see diagram 1 1 The whole of the gas installation including the meter should be inspected tested for soundness and purged in accordance with the current issue of BS6891 4 14 Top Casing Refer to diagram 4 21 Fit two plastic pegs one on each side in the holes on the top casing Theplasticpegsareatightfitandarebestpushedhome with a flat faced tool ...

Page 17: ...lamp Make sure the cable is suitably secured When making connections make sure that the earth conductor ismadeofagreaterlength thanthecurrentcarryingconductors so that if the cable is strained the earth conductor would be the last to become disconnected 5 3 Pump Connection The pump must be connected to the external controls 5 4 Testing Electrical Checks to ensure electrical safety must be carried ...

Page 18: ...PONENTS 10052 A CONTROL BOX B PHIAL POCKET C GAS SERVICE COCK D BURNER ON NEON E RESET NEON F TEMPERATURE CONTROL G BURNER PRESSURE TEST POINT H GAS PRESSURE ADJUSTMENT SCREW J DATA LABEL E D A G Turn the boiler temperature control clockwise to Max The ignition system will operate to light the boiler After a pre set time if ignition has not taken place the boiler will shutdown To re start the ligh...

Page 19: ...etting Turn the boiler temperature control fully anti clockwise to 0 Isolate from the electrical supply Remove the pressure gauge from the test point and refit screw making sure a gas tight seal is made Whentheboilertemperaturecontrolisturnedtothe 0 position by hand wait at least 30 seconds before turning On again Theremaybeaninitialsmellgivenofffromtheboilerwhennew this is quite normal and it wil...

Page 20: ... operate on mains voltage terminals will become live Switch on the electrical supply and gas supply then operate the boiler On completion of the test switch off the electrical supply and gas supply remove analyser tube and replace sampling point cap Servicing Before servicing turn off the gas and isolate the electrical supply to the boiler After completing a service always test for gas soundness m...

Page 21: ... sliding back to disengage the retaining lugs then lift up see diagram 8 7 Remove the flue hood When replacing the flue hood ensure that it rests on the guides and that the rear of flue hood is located under the pegs at the rear and pushed down and back fully IMPORTANT When re fitting fan check that it fits fully into the flue duct extension piece COMBUSTION CHAMBER COVER IGNITION AND EARTH LEADS ...

Page 22: ...ng the relevant instructions in sections 8 3 and 8 4 8 3 Burner and Injector Remove the two screws and nuts securing the burner support bracket to the combustion chamber cover see diagram 8 9 Remove the graphite coated nuts on the supply feed pipe at the rear of the burner to release the burner see diagram 8 10 Clean the burner Use a vacuum cleaner or suitable stiff brush not wire to clean the bur...

Page 23: ...ault persists continue with fault finding below Before carrying out fault finding ensure that gas electricity and water are available at the boiler Is neon 1 lit NO Check power supply Is neon 2 lit NO YES YES Faulty thermistor Replace With electrical supply isolated disconnect the 2 way thermistor plug from the PCB Check that there is a resistance between 14k 2 5kOhms Faulty PCB Replace Is neon 3 ...

Page 24: ...ove the control box cover refer to section 5 1 Refer to Boiler Fault Finding see diagram 9 1 Fault Finding Wiring Diagram see diagram 9 3 Pictorial Wiring Diagram see diagram 9 4 9 2 Electrical Supply Failure Failure of the electrical supply will cause the burner to go out Operationwillnormallyresumeontherestorationoftheelectrical supply Iftheburnerdoesnotrelightafteranelectricalsupplyfailureand t...

Page 25: ... 3 NEON 4 NEON 5 NEON 6 NEON KEY see P C B FAN P C B CONTROL BOARD GAS CONTROL VALVE TERMINAL BLOCK THERMISTOR AIR PRESSURE SWITCH NEON 1 NEON 5 NEON 4 NEON 6 NEON 2 NEON 3 F4A FUSE p y g p b bk bk bk bk b bk b r g y bk b LS LIVE Switched N LS N br r g y g y g y g y br b b br BROWN b BLUE g y GREEN YELLOW g GREY bk BLACK p PURPLE y YELLOW r RED KEY g y NEUTRAL EARTH MAIN KEY TO TERMINAL BLOCK br ...

Page 26: ... Control Board P C B Remove front panel to gain access see section 6 8 Remove control box lid by undoing the four securing screws two on control box two on the heat shield and lift off see diagram 10 1 CONTROL BOX COVER CONTROL BOX SECURING SCREWS TERMINAL BLOCK Diagram 10 1 9905 ELECTRICAL PLUGS Diagram 10 2 PCB Diagram 10 3 PHIAL POCKET THERMISTOR 0000 BOILER TEMPERATURE CONTROL Carefully pull t...

Page 27: ...t the air pressure tubes are fitted with the clear tube from the air pressure switch to the front fan connection as shown in diagram 10 5 and the electrical connections are made as shown in wiring diagram 9 4 10 9 Fan Remove front panel to gain access see section 6 8 Refer to the relevant paragraphs of the servicing section to remove the burner from combustion chamber Remove the electrical connect...

Page 28: ...ng any spare part please quote the part number and the description from the list together with the model name and serial number information from the data label The data label is positioned on the heat shield see diagram 6 1 Key No Part No Description GC Part No 1 2000461752 Multifunctional control 2 227132 Fan 3 2000461994 Air pressure switch 4 2000461985 Electrical thermistor 5 202635 Spark elect...

Reviews: