Installation 7
0020300877_01 Energy
7
Installation and maintenance instructions
25
Open end of pipe direct into gulley below ground level but
above water level
Susceptible to siphonage, must terminate in a gulley
7.11.1.7 External termination into rain water down
pipe
≤ 3 m
Ø22mm
Ø 32mm
NB only combined foul/rainwater drain
7.11.1.8 Additional methods of introducing air
breaks
1
2
3
1
Air break
2
Using a tundish
3
Using a pipe
7.11.1.9 Connection of condensate pump
Ø32mm
Ø22mm
≥ 3 m
Preferred option for external connection
7.12
Flue installation
7.12.1 Installing and connecting the air/flue pipe
1.
You can find out which air/flue pipes may be used by
consulting the enclosed set-up instructions for the
air/flue system.
2.
Observe the information on positioning the air/flue ter-
minal.
Condition
: Installation in damp rooms
▶
You must connect the product to a room-sealed air/flue
system. The combustion air must not be taken from the
installation site.
3.
Install the air/flue pipe using the set-up instructions.
7.13
Electrical installation
Only qualified electricians may carry out the electrical install-
ation.
The product must be earthed.
Danger!
Risk of death from electric shock!
The power supply terminals L and N remain
live even if the product is switched off:
▶
Switch off the power supply.
▶
Secure the power supply against being
switched back on.