Globe GL-QR Series Manual Download Page 3

MAR 2020

GFS-210

PAGE    3  of  3       

GLOBE

®

 PRODUCT WARRANTY

Globe agrees to repair or replace any of its manufactured 

products found to be defective in material or workmanship 

for a period of one year from date of shipment.

For specific details of our warranty please refer to Price List 

Terms and Conditions of Sale (Our Price List).

4077 Airpark Dr. Standish, MI  48658 • 989-846-4583 • 

www.globesprinkler.com

Technical Support 

 989-414-2600

 

 

[email protected]

ORDERING INFORMATION

SPECIFY

GL5603

SPRINKLER                                                      PART NUMBER

135°F (57°C) .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   . 560313501

155°F (68°C) .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   . 560315501

175°F (79°C) .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   . 560317501

COVER PLATES

SEE TABLE B

 Quantity 

 SIN 

 Temperature Rating 

 Finish 

 Part Number

• 

SPRINKLER

• 

PROTECTIVE CAP 

 Quantity 

 Part Number 332871

• 

WRENCH 

 Quantity 

 Part Number 332765

TABLE B:  COVER PLATE PART NUMBERS

COVER PLATE 

SIZE

WHITE 

135°F (57°C)

CHROME 

135°F (57°C)

WHITE 

155°F (68°C)

CHROME 

155°F (68°C)

BLACK 

135°F (57°C)

BLACK 

155°F (68°C)

CUSTOM 

135°F (57°C)

CUSTOM 

155°F (68°C)

3-5/16” DIA

.

332892

332891

332898

332897

332892-B

332898-B

332893

332899

CARE AND MAINTENANCE

Always obtain permission from the proper authorities to 

shut down the affected fire protection system and notify all 

personnel who may be affected by this action before closing 

a fire protection system main control valve for maintenance 

work on the system that it controls. Sprinklers should only 

be cleaned by means of gently dusting with a feather dust-

er; otherwise, non-operation in the event of a fire or inadver

-

tent operation may result.

When properly installed, there is a nominal 1/8” (3mm) air 

gap between the Cover Plate and the ceiling (FIGURE 4). 

This air gap is necessary for proper operation of the sprin-

kler  by  allowing  heat  flow  from  a  fire  to  pass  below  and 

above the Cover Plate to help assure appropriate release of 

the Cover Plate in a fire situation. This annular “gap” must 

be maintained and should never be sealed or caulked.

Factory painted Cover Plates must not be repainted.

In accordance with NFPA 25, Sprinklers which are found to 

be leaking or exhibiting visible signs of corrosion must be 

replaced.

Automatic sprinklers must never be painted, plated, coated, 

or otherwise altered after leaving the factory.

Care must be exercised to avoid damage to the sprinklers–

before, during, and after installation. Sprinklers damaged 

by dropping, striking, wrench slippage, or similar incidents, 

must be replaced.

The owner is responsible for the inspection, testing, and 

maintenance of their fire protection system and devices in 

compliance with this document, as well as with the appli-

cable standards of the National Fire Protection Association 

(e.g. NFPA 25), in addition to the standards of any other 

authorities having jurisdiction.