MAR 2020
GFS-210
PAGE 3 of 3
GLOBE
®
PRODUCT WARRANTY
Globe agrees to repair or replace any of its manufactured
products found to be defective in material or workmanship
for a period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List).
4077 Airpark Dr. Standish, MI 48658 • 989-846-4583 •
www.globesprinkler.com
Technical Support
•
989-414-2600
•
ORDERING INFORMATION
SPECIFY
GL5603
SPRINKLER PART NUMBER
135°F (57°C) . . . . . . . . . . . . . . . . . . . . 560313501
155°F (68°C) . . . . . . . . . . . . . . . . . . . . 560315501
175°F (79°C) . . . . . . . . . . . . . . . . . . . . 560317501
COVER PLATES
SEE TABLE B
•
Quantity
•
SIN
•
Temperature Rating
•
Finish
•
Part Number
•
SPRINKLER
•
PROTECTIVE CAP
•
Quantity
•
Part Number 332871
•
WRENCH
•
Quantity
•
Part Number 332765
TABLE B: COVER PLATE PART NUMBERS
COVER PLATE
SIZE
WHITE
135°F (57°C)
CHROME
135°F (57°C)
WHITE
155°F (68°C)
CHROME
155°F (68°C)
BLACK
135°F (57°C)
BLACK
155°F (68°C)
CUSTOM
135°F (57°C)
CUSTOM
155°F (68°C)
3-5/16” DIA
.
332892
332891
332898
332897
332892-B
332898-B
332893
332899
CARE AND MAINTENANCE
Always obtain permission from the proper authorities to
shut down the affected fire protection system and notify all
personnel who may be affected by this action before closing
a fire protection system main control valve for maintenance
work on the system that it controls. Sprinklers should only
be cleaned by means of gently dusting with a feather dust-
er; otherwise, non-operation in the event of a fire or inadver
-
tent operation may result.
When properly installed, there is a nominal 1/8” (3mm) air
gap between the Cover Plate and the ceiling (FIGURE 4).
This air gap is necessary for proper operation of the sprin-
kler by allowing heat flow from a fire to pass below and
above the Cover Plate to help assure appropriate release of
the Cover Plate in a fire situation. This annular “gap” must
be maintained and should never be sealed or caulked.
Factory painted Cover Plates must not be repainted.
In accordance with NFPA 25, Sprinklers which are found to
be leaking or exhibiting visible signs of corrosion must be
replaced.
Automatic sprinklers must never be painted, plated, coated,
or otherwise altered after leaving the factory.
Care must be exercised to avoid damage to the sprinklers–
before, during, and after installation. Sprinklers damaged
by dropping, striking, wrench slippage, or similar incidents,
must be replaced.
The owner is responsible for the inspection, testing, and
maintenance of their fire protection system and devices in
compliance with this document, as well as with the appli-
cable standards of the National Fire Protection Association
(e.g. NFPA 25), in addition to the standards of any other
authorities having jurisdiction.