temperature is correct and stable. 

(2). From a distance of several inches, direct the airflow 

at the guard protecting the thermistor. The detector 
should alarm within 30 seconds. 

(3). Upon alarm immediately remove the heat source 

and   check that the red LED of the detector is 
illuminated. Reset the detector from the control 
panel. 

(4). 

If a detector fails to activate within 60 seconds, confirm 

connections and programming. If necessary replace and return to 
distributor for recalibration.

 

(5). After testing, check that the system is set for 

normal operation and notify the appropriate 
authorities that the testing operation is complete 
and the system is active again. 

z

 

NOTE 

This heat detector is particularly designed to 

initiate and 

activate 

emergency action, but will do so only when it is 

used in conjunction with an authorized fire alarm system. 
This detector must be installed in accordance with Local Fire 
Authority recommendations. 

 
Heat detectors are primarily designed for property 
protection.

  For Life protection early warning is required, 

this can be obtained by the installation of appropriate Smoke 
detectors. (GFE-CS) Heat detectors do not provide early 

warning of fire and cannot detect smoke, gas, combustion 
particles, or flame. They will alarm when the temperature at 
the heat detector reaches 57

o

C (135

o

F) or above. Given the 

rapid growth of certain types of fires, heat detectors cannot 
be expected to provide adequate warning of fires resulting 
from smoking in bed, inadequate fire protection practices, 
violent explosions, escaping gas, and improper storage of 
flammable liquids like cleaning solvents, other safety 
hazards, or arson. 
 
Heat detectors are components in professionally installed fire 
alarm systems. 

They will not function if they have been 

improperly wired into the fire alarm system or if power to 
them is disconnected for any reason. 

 

Heat detectors 

should be tested and maintained following 

the instructions in this manual. To be safe, they should be 
replaced after they have been installed for ten years. 
 

 

Note: This product is factory sealed and does not 
contain user serviceable parts. Opening THE DETECTOR 
HEAD WILL VOID THE WARRANTY. 

 

REFERENCE TO THE TECHNICAL BULLETIN ISSUE NO. 
NB022A001 REV.2.0

 
SPECIFICATION 

Model 2/4 

 

wire 

Voltage 

DC 

Standby 

Current 

(Max.) 

Alarm 

Current 

(Max.) 

Surge 

Current 

(Max.) 

Start-Up 

Time 

(Max.) 

Permissible 

Current 

(Max.) 

LED Flash 

Frequency 

Alarm contact 

Base model 

EN-54 & CE listed 

 

 

 

 

 

 

 

 

 

 

GFE-CH-2 2 

10~35V 

55

µ

A 50mA 150

µ

60 Seconds

80mA 

4-6 Seconds 

 P/N772912 

GFE-CH-2-L 2 

10~35V 

55

µ

A 50mA 150

µ

60 Seconds

80mA 

4-6 Seconds 

 P/N774912 

GFE-CH-4-12  

10~15V 

55

µ

A 50mA 150

µ

60 Seconds

80mA 

4- 6Seconds 

Form A 

P/N774912 

GFE-CH-4-24  

21~27V 

55

µ

A 50mA 150

µ

60 Seconds

80mA 

4-6 Seconds 

Form A 

P/N774912 

CE 

Listed 

        

 

 

 

 

GFE-CH-4-AR-12  

10~15V 

55

µ

A 50mA 150

µ

60 Seconds

80mA 

4-6 Seconds 

Form A /Auto Reset 

P/N774912 

GFE-CH-4-AR-24  

21~27V 

55

µ

A 50mA 150

µ

60 Seconds

80mA 

4-6 Seconds 

Form A /Auto Reset 

P/N774912 

Remarks:

 

AR

-auto reset function/ 

L

-remote LED indicator output 

 
Detector Alarm Specification: 

 

Fixed Temperature: 57

o

Rate of Rise Characteristic:   

ROR °C/min 

Lower Limit (Mins:Secs) 

Upper Limit (Mins:Secs) 

1 29:00 

40:20 

3 7:13 

13:40 

5 4:09 

8:20 

10 2:00 

4:20 

20 1:00 

2:20 

30 0:40 

1:40 

 
En 54 part 5     

Certificate number:    0845-CPD-232.1479 

LIMITED WARRANTY STATEMENT 

Global Fire Equipment Ltd.

 declares that this product is free from defects in material and workmanship. And it will repair or replace any product or 

part thereof which proves to be defective in workmanship or material for a period of 24 months from the date of purchase. Please visit the Global 
Fire Website for a full description of Global Fire Equipment

s LIMITED WARRANTY, which, among other things, limits the duration of warranties 

of merchantability and fitness for a particular purpose and excludes liability for consequential damages. Acceptance of order and/or original 
invoice which will become part of your sales agreement. Please contact Global Fire Equip directly for a return merchandise authorization (RMA) 
number before returning goods to the factory . Shipment must be prepaid and Global Fire repair or replace your returned detector. 

                     

Global Fire Equipment Ltd.

 

Urb. Vale da Amoreira, Lt. 16 & 17,   
Porta A, Cave, 8005-334 FARO, PORTUGAL 

ISSUE NO.NBUM 20050527 REV.A

 