Global IFS 1462263 Installation Instruction Download Page 4

Page: 

4

 

of 

9

Global IFS 

Fan Powered Box

FAN POWERED BOX & TERMINAL UNIT

 

START UP & OPERATION

Air System Balancing

Overview 

All ductwork must be complete and connected, and all grilles, filters, access doors and panels must be properly installed to 

establish actual system operating conditions BEFORE beginning air balancing operations. Each individual unit and attached 

ductwork is a unique system with its own operating characteristics. For this reason, air balancing is normally done by balance 

specialists who are familiar with all procedures required to properly establish air distribution and fan system operating 

conditions. 
These procedures should not be attempted by unqualified personnel. 
After the proper system operation is established, the actual unit air delivery and the actual fan motor amperage draw for each 

unit should be recorded in a convenient place for future reference such as the inspection, installation, & start-up check sheet, a 

copy of which is provided on the back of this manual. Contact the sales representative or the factory for additional copies of 

this sheet. 
The manufacturer assumes no responsibility for undesirable system operation due to improper design, equipment or 

component selection, and/or installation of ductwork, grilles, and other field supplied components.

Air Balancing Procedure 

Before Air Balancing the terminal unit, the following general items should be verified

1.

The primary fan system is operating at the specified volume, static pressure, RPM and current.

2.

Return filters (if supplied) are clean.

3.

All balancing dampers are adjusted and locked. Dampers downstream of the terminal unit should be proportionally

balanced.

4.

Thermostats are calibrated and operational.

5.

All duct work and connections are free from leaks.

6.

Sufficient duct static pressure is available at the terminal primary air inlet.

7.

All diffusers are installed and adjusted for the proper air pattern.

NOTE: 

Since fan powered terminals are typically operating within a pressurized plenum, all flooring tiles must be replaced prior to

verifying outlet flows

.

8. A fan powered terminal unit should never be operated if the downstream duct work has not been installed. A

minimum downstream static pressure resistance of 0.1 in. w.g. is recommended.

9. If field adjustment of the primary air valve should be necessary, follow the appropriate calibration procedures for

the controller type supplied with the unit. If DDC controls are supplied, refer to the control contractor’s

documentation for calibration instructions.

10. Set the thermostat to full cooling. The fan should be on and the primary air valve (if present) at maximum air flow.

Verify the air flow with the sensor tube or pitot tube traverse. Adjust if necessary.

11. The fan volume must be field adjusted with the fan speed controller. Fan curves (available at priceindustries.com)

indicate the volume range of each size unit. Adjust the speed control until the desired air flow is measured at the

outlet.

12. Set the thermostat to full heating. The fan should be on and the primary air valve (if present) at minimum flow.

Verify the primary air volume with sensor taps or pitot tube traverse. Adjust if necessary.

13. Always set the fan volume at full cooling.

Summary of Contents for 1462263

Page 1: ...Page 1 of 9 Global IFS Fan Powered Box Global IFS Fan Powered Box Installation Instruction Tool Check List 2 Fan Powered Box Terminal Unit FPB TU...

Page 2: ...l Global IFS fan powered terminal units are tagged with a control assembly label as shown on the left This label identifies the model number location tag controller type actuator type thermostat actio...

Page 3: ...sting or balancing purposes are to be sealed with duct tape or duct sealer 3 A minimum of 0 10 inches W G downstream static pressure is required to prevent overheating of the fan motor Fan Terminal El...

Page 4: ...turn filters if supplied are clean 3 All balancing dampers are adjusted and locked Dampers downstream of the terminal unit should be proportionally balanced 4 Thermostats are calibrated and operationa...

Page 5: ...2 VDC Fan Off 1 5V Recommended 2 10 VDC Remote Control 0 100 Note Refer to Fan Curves performance data documents for fan curves Pressure Independent Flow PIF Motor Program Voltage Equations Box Con i...

Page 6: ...lso has a digital screen and BAS RPM feedback 2 10 VDC which is proportional to motor RPM NOTE 24 VAC COM BAS COM ANALOG OUTPUT COM are all connected together Please observe 24 VAC polarity NOTE Local...

Page 7: ...ce the downstream static pressure is confirmed check the supply voltage is the same as stated on the wiring diagram The supply voltage must be identical to the wiring diagram c For ECM applications th...

Page 8: ...ING 1 4 5 voe MIN TO MAX AIRFLOW 0 1 voe FAN OFF UNE LEGEND FACTORY ELEClRICAL WIRING FIELD EL EClRICAL WIRING OPTIONAL WIRING WH AFS AUT AIR OMATI FLOW C SWITCH RESET SWIT AR CH C1 C2 24V CONTACTOR C...

Page 9: ...dulating Controller with BACnet Manual5 mfd Transformers 019436 001 115V 24V 50 VA Transformer 019436 011 208V 240V 24V 50 VA Transformer 019439 001 277V 24V 50 VA Transformer Disconnect Switch 019903...

Reviews: