ADDRESS PROGRAMMING
DETECTOR BASE - LOOP CONNECTIONS
The ZEOS-AS range of Fire Detectors is SAM enabled and do not have their addresses set using switches.
be either programmed using GFE’s device programmer or using Automatic Address Setting (ASET) which is a special install and commissioning
mode that can be activated on a per loop basis whilst in INSTALLATION mode. ASET mode is only required if Smart Addressing Mechanism (SAM)
is used. When used in conjuction with this mode they automatically assign their own addresses. ASET mode is only available in GFE’s range of
analogue addressable fire detection panels, JUNIOR and JUNO NET. ZEOS-AS can be mixed with other types of devices on the same loop. Each
time a ZEOS-AS detector is programmed it takes the next free address on its loop.
ZEOS-AS range can only be used in conjunction with:
a) JUNO NET and JUNIOR panels.
Software release 3.09 and above.
b) JUNO NET REPEATERS w/ loop card.
Software release 3.09 and above.
c) SUB PANEL (incorporating SIMM module & socket).
Software release 2.09 and above.
NOTES:
Verify panel software version by looking at number on the sticker placed on the SIMM card.
ZEOS-AS detectors cannot operate or be programmed when installed within loops associated with old Sub-Panel versions (i.e. Sub-Panels that do
not include a SIMM card and socket).
Before starting the programming procedure, care should be taken with the following:
a) Main Supply OK.
b) Auxiliary Supply (Batteries) OK.
c) Loop Supply OK.
d) Verify the non-existence of earth faults.
e) Verify the cable lengths for the loop.
f) Confirm the non-existence of short or open circuits within the loop.
g) Verify communications with standard analogue addressable devices is OK.
h) Verify communications between Main Panel, Sub-Panels and Repeaters with integrated Sub-Panel.
Verify that all ZEOS-AS detector connections to the loop are properly made in particular those regarding polarity when detector incorporates a
loop isolator. Reversal of the supply polarity can cause failure or malfunction and prevent the detector from being programmed.
CAUTION
Verify that there are no faults or fire conditions in the loop or system. Clear all fault and fire conditions first.
Reset to normal operation all devices before applying power to the panel, in particular manual call points.
For further information on how to set the address of a ZEOS-AS fire detector please refer to ZEOS-AS Programming and Troubleshooting Guide.
The address of a ZEOS-AS detector can
BASE LOCK
MORE INFO >>
WWW.GLOBALFIRE.PT
To lock beacon remove pin
available at terminal 4 on the
underside of the beacon using
a small screwdriver.
To unlock beacon from its base
push provided unlock key
through hole available on the
base side wall as shown.
Connection applicable only to:
ZEOS-AS-S / ZEOS-AS-H / ZEOS-AS-SH
Connection applicable only to:
ZEOS-AS-SI / ZEOS-AS-HI / ZEOS-AS-SHI
NOTE:
Positive terminal of remote indicator should be connected to terminal 4 (+ Loop IN/ OUT)
-Loop IN/ OUT
- REMOTE LED INDICATOR
+Loop IN/ OUT
-Loop IN/ OUT
SCREEN
To next device
in loop or return
to panel
-Loop IN/ OUT