Global Fire Equipment ORION BCM Installation Manual Download Page 1

 

 

 

 

ORION BCM 

Stand-Alone Battery Charger Module with Integrated 
Sounder Circuit 

 

INSTALLATION MANUAL

 

 

 

OVERVIEW 

The ORION BCM is a self contained EN54-4 certified Battery Charger Module with a Conventional Sounder circuit. It

 

 

     

 

 

 

 

 

 

 

   

 

 

   

also incorporates internal Alarm and Fault relays. 

 
An internal monitoring system continuously checks all circuits, ensuring fault detection and notification, listed below:

 

● Sounder Circuit Integrity Fault

 

● Battery Charger Fault (voltage level and charging behaviour) 
● Mains Fault (voltage level) and Earth Fault 
● Output Supply 

voltage level 

● General System Fault (by the means of independent watchdog system). 

MAIN FEATURES 

● Voltage-free inputs to activate built-in Relay for controlling Door Holders and Sounder Circuit 
● One supervised Conventional Sounder Circuit 
● Dedicated battery charger (Secondary Supply) for Sounder Circuit and Auxiliary Power 
● Two relays output for Fault (NC) and Fire (SPDT) signal - unmonitored 
● Supervised 24V Supply Output with 900 mA 
● EN54-4 Compliant 

 

ORION BCM LSC

 has the following local controls: 

● Internal Buzzer Silence 
● System Reset 
● Lamp Test 
● Sounders circuit ON/OFF operation 
● Disable Auxiliary Outputs 
● Disable Sounders 

 
 

IMPORTANT SAFETY NOTES 

● This equipment must only be installed and maintained by a suitably qualified and technically competent person. 
● This equipment must have an Earth Connection. 
● A basic knowledge and training in the installation of Fire Detection systems is assumed. 
● The Fire Detection system should be designed by a suitably qualified person with reference to the Local 

Regulations and Guidance from the fire Officer where applicable. 

 
 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for ORION BCM

Page 1: ...Circuit One supervised Conventional Sounder Circuit Dedicated battery charger Secondary Supply for Sounder Circuit and Auxiliary Power Two relays output for Fault NC and Fire SPDT signal unmonitored S...

Page 2: ...the terminals in the control panel Mains wiring should be 3 core 1mm to 2 5mm fed from an isolating circuit breaker of 6A This should be secure from unauthorized operation and be marked Fire Alarm Do...

Page 3: ...terminated in their respective terminals and the cable screens connected to earth INPUTS To activate the inputs a shunt must be made between the Common C and the input to be activated by the means of...

Page 4: ...to indicate any FAULT condition present on panel DISABLED Used to indicate that the panel has features that have been disabled in Access Level 2 SUPPLY Used to indicate the presence of supply In Acces...

Page 5: ...SABLE SOUNDER Use this button to disable or re enable Conventional sounder circuit S1 ACCESS LEVEL There are two levels of Access in the ORION BCM Level 1 General user controls This lower level allows...

Page 6: ...With the Addressable system in normal operating mode activate a Fire Alarm and confirm operation of Fire relays Test if manual button Sounder activation also activates the Fire relay On the Fault Rel...

Page 7: ...fault will show when the voltage at the auxiliary supply output is below 20V DC This can be caused by the current limit for this output being exceeded This output is limited to 900mA Other causes for...

Page 8: ...ation of Fire Relay Example of application Door Holder Supply External Control This implementation working as a standalone PSU has the ability to by pressing the ORION BCM sounder activation key activ...

Page 9: ...1 5 Amp Max Max Operating Temperature SOUNDER CIRCUIT NUMBER OF CIRCUITS 1 END OF LINE RESISTOR VALUE 10K Ohms MONITORING Open and Short Circuit ALARM VOLTAGE 27 5V DC SOUNDER CIRCUIT FUSE 1 1 Amp re...