GENERAL DESCRIPTION

The INT-TCP/IP-WEB is an interface that extends new advanced features and functionalities to Chameleon Panels (GEKKO

and OCTO+). Its enhanced hardware allows for an easier integration with existing LANs via Wi-Fi or optional Ethernet cable.

An SD Card socket permits the interface to hold and store valuable data or simple firmware upgrades when needed. This is

extremely handy on network debug and log needed situations.

Using our proprietary ODYSSEY protocol for Panel communication and a secure connection to a dedicated internet broker

(external server), it is possible to receive “Live” events and monitor the connected panels 24/7, controlling and viewing in real

time the panel status. The user-friendly dedicated webpage via internet browser provides a new and safe level of customer

experience. The new added features, such as SMS and e-mail alerts, will push the remote monitoring capabilities even

more.

Interface configuration network, remote internet broker address, and all local parameters are all configured by means of an

user friendly config web page that can be accessed directly by Wi-Fi AP mode (the interface must be in Access Point mode)

TECHNICAL SPECIFICATIONS

INT-TCP/IP-WEB

SUPPLY VOLTAGE

20 to 30 V DC

SUPPLY CURRENT

28 mA

CONFIGURATION

Remotely via Wi-Fi, Web page

COMMUNICATION CONNECTOR

Ethernet RJ45, Wi-Fi 2,4GHZ, BLE (Bluetooth Low Energy as future dev)

INPUT

Reset as default (advanced configurations)

OPERATING TEMPERATURE

-10

º

C to 50

º

C

DIMENSIONS

90 © x 40 (A) mm

WEIGHT

24 g

COMPATIBILITY

Windows XP/7/8/10, MacOS, Linux, Android, IOS

PANEL COMPATIBILITY

OCTO+, GEKKO, G-One and NODE+

INT-TCP/IP-WEB / CONFIGURATION MANUAL / © GFE 210622

2

Summary of Contents for INT-TCP/IP-WEB

Page 1: ...3 PANEL CONFIGURATION 3 BMS port configuration ODYSSEY Protocol 3 INTERFACE CONFIGURATION 4 LEDs behaviour 4 Startup behaviour 4 Operation behaviour 4 Configuration using Wi Fi with module in AP MODE...

Page 2: ...d webpage via internet browser provides a new and safe level of customer experience The new added features such as SMS and e mail alerts will push the remote monitoring capabilities even more Interfac...

Page 3: ...n any of the BMS channel BMS port configuration ODYSSEY Protocol After connecting the interface to the BMS channel the panel address and ODYSSEY protocol must be selected in order to allow the communi...

Page 4: ...NG FLASHING Initializing or wrong settings if blocked in this stage ON FLASHING Not used Operation behaviour GFE TCP IP WEB LED 2 Yellow LED 1 Red DESCRIPTION LED 2 Yellow LED 1 Red OFF OFF No power O...

Page 5: ...micro SD card to easily access config txt and debug txt files This is not mandatory Please check the Advanced Debug Mode chapter of this manual 1 Connect the interface to panel s BMS channel ODYSSEY...

Page 6: ...i Fi network that is not present in the search page The interface can be programmed offline and as soon as it is connected the interface will detect the configured SSID to the selected wifi network 9...

Page 7: ...o send the alert by SMS The number must have the country s code For example for Portugal it should be entered the code 351 before the number example 351960000000 27 Press the Save button to save the s...

Page 8: ...ed LED will stay ON permanently for 5 seconds and the interface will now restart in access point mode with all the settings erased Connecting with Ethernet cable RJ45 1 The settings procedure should b...

Page 9: ...ystem LED is turned on ATTENTION There are no guarantees of receiving alerts If the connection to the mail or SMS server is not possible the alert will not be sent but the interface continues with its...

Page 10: ...erface is now ready to be updated via Wi Fi 3 Search in Wifi network for the interface SSI MAC address this can be identified as GFE UP X X X or GFE AP X X X the X X X Its an open Wi Fi network withou...

Page 11: ...it ATTENTION The link domain of the website may change please contact the manufacturer for more information The connection between the interface and the internet broker external server as well as the...

Page 12: ...below Client ID 702C6EAE114C In order to read saved settings write Installation Name previously set and press the Read button Additional buttons available have the following function Connect Connectin...

Page 13: ...ile in which writes the errors and events that happen with the interface In the config txt file the last settings made are always written In the debug txt file the error messages are cumulative that i...

Page 14: ...Check if the globe flashes if not the interface has stopped communicating B I don t see any information on the panel Wrong settings without interface communication Check that the interface is communic...

Page 15: ...for interface to re start I Constant loss of connection with Internet Broker external Server Connection to the network internet could be faulty Check clients network connections Reset interface and sw...

Reviews: