HEAT SENSOR TESTING 

The detector to be tested should be subject to a flow of 
warm air at a temperature of between 65

°

C and 80

°

C. 

(This requirement can be met by some domestic hair 
dryers). 
Proceed as follows: 
1. Switch on the warm airflow and check that temperature 

is correct and stable. 

2. From a distance of several inches, direct the airflow at 

the guard protecting the thermistor. The detector 
should alarm within 30 seconds. 

3. Upon alarm immediately remove the heat source and     

check that the red LED of the detector is illuminated. 
Reset the detector from the control panel. 

4. If a detector fails to activate within 60 seconds, confirm 

connections and programming. If necessary replace 
and return to distributor for recalibration. 

5. After testing, check that the system is set for normal 

operation and notify the appropriate authorities that the 
testing operation is complete and the system is active 

again. 

NOT SUITABLE FOR INSTALLATION IN AREAS 
WHERE AIR VELOCITIES EXCEED 300 ft/min 

MAINTENANCE 

The recommended minimum requirement for detector 
maintenance consists of an annual cleaning of dust from 
the detector head by using a vacuum cleaner cleaning 
program should be agreed to the individual environment 
in conformance with NFPA-72A standard. 
 

Note: This product is factory sealed and does not 
contain user serviceable parts. Opening THE 
DETECTOR HEAD WILL VOID THE WARRANTY. 

 
REFERENCE TO THE TECHNICAL BULLETIN ISSUE NO. 
NBTB20031106,REV.A 

 

SPECIFICATION 

Model 2/4 

 

wire 

Ther

mal 

Voltage 

DC 

Standby 

Current 

(Max.) 

Alarm 

Current 

(Max.) 

Surge 

Current 

(Max.) 

Star-Up 

Time 

(Max.) 

Permissible 

Current 

(Max.) 

Frequency Alarm 

 

Sound level

Alarm contact 

Base model 

GFE-S-2 2 

 

28/12V 

90

µ

70mA 

120

µ

60 Seconds

80mA 

3-5 Seconds

 

P/N772912 

GFE-S-2L  

 

28/12V 

90

µ

70mA 

120

µ

60 Seconds

80mA 

3-5 Seconds

 

P/N774912 

GFE-S-4-12 4 

 

12V 

320

µ

35mA 

120

µ

60 Seconds

80mA 

3-5 Seconds

Form A 

P/N774912 

GFE-S-4-24 4 

 

24V 

320

µ

35mA 

120

µ

60 Seconds

80mA 

3-5 Seconds

Form A 

P/N774912 

GFE-SH-2 2 

57

°

C 28/12V  100

µ

70mA 

130

µ

60 Seconds

80mA 

3-5 Seconds

 

P/N772912 

GFE-SH-2L  

57

°

C 28/12V  100

µ

70mA 

130

µ

60 Seconds

80mA 

3-5 Seconds

 

P/N774912 

GFE-SH-4-12  

57

°

C 12V  320

µ

35mA 

130

µ

60 Seconds

80mA 

3-5 Seconds

Form A 

P/N774912 

GFE-SH-4-24  

57

°

C 24V  320

µ

35mA 

130

µ

60 Seconds

80mA 

3-5 Seconds

Form A 

P/N774912 

Remarks:

 

H

-heat/ 

L

-remote LED indicator output

 

 

En 54 part 7     

Certificate number:  0845-CPD-232.1489 

En 54 part 5/7        Certificate number:  0845-CPD-232.1490 

 

LIMITED WARRANTY STATEMENT 

Global Fire Equipment Ltd.

 declares that this product is free from defects in material and workmanship. And it will repair or replace any product or 

part thereof which proves to be defective in workmanship or material for a period of 24 months from the date of purchase. Please visit the Global 
Fire Website for a full description of Global Fire Equipment

s LIMITED WARRANTY, which, among other things, limits the duration of warranties 

of merchantability and fitness for a particular purpose and excludes liability for consequential damages. Acceptance of order and/or original 